22-Mec-B2 Environmental Control in Buildings: May 2015

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

  1. Question 1 Mixed-air plant with reheat — cycle, plant loads and energy input
  2. Question 2 Winter heating cycle with a steam humidifier
  3. Question 3 Centrifugal fan power and the fan laws
  4. Question 4 Indoor air quality — controls and standards, and a dilution-ventilation calculation
  5. Question 5 Cavity wall with a window — the window's share of the heat loss
  6. Question 6 Induced-draught cooling tower — leaving water temperature and make-up rate
  7. Question 7 Seasonal heating fuel, and a gas furnace versus an air-source heat pump
  8. Question 8 Ideal R-134a vapour-compression chiller, and refrigerant environmental concerns

Start with Question 1 →

Paper format. Professional Engineers of Ontario / EGBC annual examination, 07-Mec-B2 (now 22-Mec-B2) Environmental Control in Buildings, May 2015 sitting. Three hours, open book. Eight problems of 20 points each; the candidate is instructed to solve five and to nominate on the cover of the first workbook which five are to be graded. Psychrometric charts and a pressure–enthalpy diagram for the refrigerant are appended to the paper, and candidates are expected to bring an environmental-control text and steam tables. Instruction 1 invites the candidate to submit a clear statement of any interpretation assumptions with the answer — that latitude is used explicitly below wherever the printed data are redundant or incomplete.

All eight problems are worked here. Every psychrometric state has been recomputed from the ASHRAE formulation for saturation vapour pressure rather than scaled off a chart, so the numbers below are tighter than a graphical solution would be; chart-quality agreement (about $\pm 0.2$ K in temperature and $\pm 0.0002$ kg/kg in humidity ratio) is all that an examiner expects, and a candidate reading the appended charts should reproduce every answer to within that band.

Reference texts for this subject.

Psychrometric relations used throughout. At barometric pressure $p$ with saturation vapour pressure $p_{ws}(t)$ from the ASHRAE correlation, the humidity ratio, specific enthalpy and humid volume of moist air are

$$W = 0.621945\,\frac{\phi\,p_{ws}(t)}{p - \phi\,p_{ws}(t)}, \qquad h = 1.006\,t + W\,(2501 + 1.86\,t), \qquad v = \frac{0.287042\,(t + 273.15)\,(1 + 1.6078\,W)}{p}$$

with $h$ in kJ per kg of dry air, $t$ in $\,{}^{\circ}$C and $p$ in kPa. In inch-pound units the enthalpy becomes $h = 0.240\,t + W\,(1061 + 0.444\,t)$ Btu per lb of dry air with $t$ in $\,{}^{\circ}$F. Wet-bulb temperatures are obtained by solving the adiabatic-saturation equation, not by eye. Mixing two air streams is exact in moisture and in enthalpy, so $W$ and $h$ of the mixture are the mass-weighted averages and the mixed dry bulb follows from them; weighting the dry bulb directly is the usual shortcut and differs here by about $0.01$ K.