24-Bld-A5 Building Science · May 2016
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
07-Bld-A5 Building Science — National Exam, May 2016. Six questions of 20 marks each were printed; per the paper's own NOTES only the first five in the answer book are graded, but all six are answered below as a complete study resource.
Reference texts: ASHRAE Handbook — Fundamentals (Chapters 1 Psychrometrics, 14 Climatic Design Information, 25 Thermal and Water Vapor Transmission Data, 26 Heat, Air, and Moisture Control in Building Assemblies); McQuiston, Parker & Spitler, Heating, Ventilating, and Air Conditioning: Analysis and Design; National Building Code of Canada (NBCC).
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (A) — required characteristics of an air-barrier material. An air barrier's job is to stop uncontrolled, pressure-driven bulk airflow through the enclosure, which is a far larger energy and moisture-damage risk than vapour diffusion, so the material chosen for it must satisfy several requirements simultaneously. It must be air-impermeable in its own right: the accepted material-level acceptance criterion (ASTM E2178, adopted by NBCC and ASHRAE 90.1) is an air leakage rate no greater than 0.02 L/(s·m²) at a 75 Pa test pressure, roughly two orders of magnitude tighter than the 0.2 L/(s·m²) allowed for a completed air barrier ASSEMBLY once seams, fasteners and transitions are included. It must be structurally adequate: the layer has to carry the full range of wind, stack and mechanical-pressurization loads expected over the building's life without rupturing, delaminating, or deflecting enough to open a path at its fasteners or laps — this is why flexible sheet air barriers are rated to a design wind pressure (CAN/CSA A440 or the NBCC's own wind-load provisions) rather than assumed adequate by default. It must be continuous, or capable of being made continuous: the material only performs as a SYSTEM once every seam, penetration, window/door rough opening, and transition to roof or foundation is sealed with a compatible tape, sealant, or transition membrane — a perfect sheet material with unsealed laps is not an air barrier. It must be durable for the service life of the assembly (resist embrittlement, UV exposure during the construction sequence, and loss of adhesion over decades) and compatible with the layers on either side of it. Finally, its vapour permeance must be chosen deliberately for the climate and assembly — an air barrier is not automatically also a vapour barrier, and combining or separating the two functions is a design decision, not a given.
Part (B).
Given. 8 mm plywood sheathing, total area 30 m², pressure difference across it ΔP = 24 kPa (24 000 Pa) per the question as printed.
Find. The air flow rate through the sheathing at this pressure difference, and whether plywood is adequate as an air barrier material.
Approach. Treat the sheathing as a sheet material with a rated air permeance at the standard ASTM E2178 test pressure of 75 Pa, then extrapolate to the stated pressure using the linear (Darcian) scaling appropriate to flow through a continuous solid sheet rather than through a discrete crack.
| Quantity | Value |
|---|---|
| Reference permeance, plywood @ 75 Pa | 0.02 L/(s·m²) |
| Permeance @ 24 kPa (linear scaling) | 6.40 L/(s·m²) |
| Total flow @ 24 kPa, 30 m² | 192 L/s (0.192 m³/s) |
| Total flow @ realistic 75 Pa, 30 m² | 0.6 L/s |
At the pressures a building envelope actually experiences, plywood's own air permeance is at or below the code threshold for a certified air barrier material, so it comments favourably: plywood sheathing is adequate as the air-barrier COMPONENT, provided its seams and penetrations are sealed to bring the assembly (not just the sheet) under the 0.2 L/(s·m²) @ 75 Pa system limit.