Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
07-Bld-A5 Building Science — National Exam, May 2017. Six questions of 20 marks each were printed; per the paper's own NOTES only the first five in the answer book are graded, but all six are answered below as a complete study resource.
Reference texts: ASHRAE Handbook — Fundamentals (Chapters 1 Psychrometrics, 14 Climatic Design Information, 16 Ventilation and Infiltration, 25 Thermal and Water Vapor Transmission Data, 26 Heat, Air, and Moisture Control in Building Assemblies); McQuiston, Parker & Spitler, Heating, Ventilating, and Air Conditioning: Analysis and Design; National Building Code of Canada (NBCC).
Wall assembly and boundary conditions (interior → exterior)
Layer / condition
Value
Concrete slab
160 mm, k ≈ 1.7 W/(m·K), μ ≈ 4.5 ng/(s·m·Pa)
Type 3 XPS
80 mm, k ≈ 0.029 W/(m·K), μ ≈ 1.5 ng/(s·m·Pa)
Air space
30 mm, R ≈ 0.17 m²K/W, μ ≈ 194 ng/(s·m·Pa)
Face brick
90 mm, k ≈ 0.9 W/(m·K), μ ≈ 10 ng/(s·m·Pa)
Interior air
22 °C, 55% RH
Exterior air
−14 °C, 20% RH
Check: the k and vapour-permeability values for concrete, XPS and brick are not printed in the question (very likely a supplied properties table); the figures above are standard ASHRAE Fundamentals Ch. 25/26 values for these materials, adopted explicitly. Standard interior/exterior surface film resistances Rᵣᵢ=0.12, Rᵣᵢ=0.03 m²K/W are used, and surface-film vapour resistance is taken as negligible (the usual Glaser-method simplification).
Find. (i) The steady-state vapour pressure at each material interface; (ii) the relative humidity at each interface; (iii) whether — and where — condensation occurs within the wall.
The much drier exterior air (20% RH) keeps this assembly non-condensing.
Approach. Compute the steady-state temperature at each interface from the thermal-resistance chain (Q/A = ΔT/Rₜₖₜₕ), compute the steady-state vapour pressure at each interface from the analogous vapour-resistance chain (w = ΔP/Zₜₖₜₕ), then compare each interface's actual vapour pressure against the saturation pressure at that interface's temperature.
Thermal resistances (R=L/k, plus the airspace's tabulated R):
$$R_{conc}=\frac{0.160}{1.7}=0.094,\ R_{xps}=\frac{0.080}{0.029}=2.759,\ R_{air}=0.170,\ R_{brick}=\frac{0.090}{0.9}=0.100\ \ (\text{m}^2\text{K/W})$$
$$R_{total}=R_{si}+R_{conc}+R_{xps}+R_{air}+R_{brick}+R_{so}=0.12+0.094+2.759+0.170+0.100+0.03=3.273\ \text{m}^2\text{K/W}$$
Heat flux and interface temperatures. With ΔT=22−(−14)=36 K,
$$q=\frac{36}{3.273}=11.00\ \text{W/m}^2$$
Stepping T = T₀ − q·R progressively from the interior:
$$T_1(\text{int. surf.})=20.68^\circ\text{C},\ T_2(\text{conc/XPS})=19.65^\circ\text{C},\ T_3(\text{XPS/air})=-10.70^\circ\text{C},\ T_4(\text{air/brick})=-12.57^\circ\text{C},\ T_5(\text{ext. surf.})=-13.67^\circ\text{C}$$
(the chain closes to −14.00°C at the outside air, confirming the resistance bookkeeping).
Boundary vapour pressures (Magnus-Tetens saturation curve, over water for T≥0°C and over ice for T<0°C):
$$P_{sat}(22^\circ\text{C})=2639\ \text{Pa}\ \Rightarrow\ P_0 = 0.55\times2639 = 1451\ \text{Pa (interior)}$$
$$P_{sat}(-14^\circ\text{C})=181\ \text{Pa}\ \Rightarrow\ P_6 = 0.20\times181 = 36\ \text{Pa (exterior)}$$
(i) Vapour flux and interface vapour pressures, stepping P = P₀−w·Z progressively (surface-film vapour resistance neglected, so P at the interior wall surface equals the room's vapour pressure):
$$w=\frac{P_0-P_6}{Z_{total}}=\frac{1451-36}{0.0980}=14\,432\ \text{ng/(s.m}^2\text{)}$$
$$\boxed{P_1(\text{conc/XPS})=938\ \text{Pa},\ \ P_2(\text{XPS/air})=168\ \text{Pa},\ \ P_3(\text{air/brick})=166\ \text{Pa}}$$
(the chain closes to 36 Pa at the exterior, matching P₆ and confirming the vapour-resistance bookkeeping).
(ii) Relative humidity at each interface, RH = Pₕ₋ₔ₊₌ₓ/Pₛ₊ₜ(T):
Interface temperature, actual vapour pressure and saturation vapour pressure
Interface
T
Pₕ₋ₔ₊₌ₓ
Pₛ₊ₜ(T)
RH
Interior surface
20.68 °C
1451 Pa
2434 Pa
59.6%
Concrete / XPS
19.65 °C
938 Pa
2283 Pa
41.1%
XPS / air space
−10.70 °C
168 Pa
244 Pa
69.0%
Air space / brick
−12.57 °C
166 Pa
206 Pa
80.6%
Exterior surface
−13.67 °C
36 Pa
187 Pa
19.4%
(iii) Condensation check. RH stays below 100% at every interface, peaking at 80.6% at the airspace/brick interface — the theoretical vapour-pressure profile never crosses the saturation curve, so no condensation occurs within this wall. The exterior air is very dry (20% RH), which pulls the boundary vapour pressure P₆ and the whole interior vapour-pressure profile down far enough that it stays under the saturation curve everywhere.