22-Elec-A7 Electromagnetics · May 2015
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Examinations, May 2015 — 07-Elec-A7 Electromagnetics. Three hours, closed book; one of two approved calculators (Casio or Sharp) permitted. Eight questions, all of equal value; the paper’s note 3 states that any five questions constitute a complete paper and only the first five presented will be marked. Because this set is a study resource, all eight questions are solved here. The permitted aids printed on the cover are used throughout: $\varepsilon_0 = 8.85\times10^{-12}\ \text{F/m}$ and $\mu_0 = 4\pi\times10^{-7}\ \text{H/m}$, giving $\eta_0 = \sqrt{\mu_0/\varepsilon_0} = 376.6\ \Omega$ and $c = 1/\sqrt{\mu_0\varepsilon_0} \approx 3\times10^{8}\ \text{m/s}$.
Reference texts. D. M. Pozar, Microwave Engineering, 4th ed. (transmission-line transients, matching, waveguides); M. N. O. Sadiku, Elements of Electromagnetics, 7th ed. (magnetostatics, Faraday’s law, plane waves); W. H. Hayt and J. A. Buck, Engineering Electromagnetics, 9th ed. (polarisation, boundary conditions); C. A. Balanis, Antenna Theory: Analysis and Design, 4th ed. (short elements, image theory); F. T. Ulaby and U. Ravaioli, Fundamentals of Applied Electromagnetics, 8th ed. (waves and power density).
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Given. An ideal 60 Hz source feeds a quarter-wavelength, 1000 $\Omega$ line through a 1:5 step-up transformer; the far end is a purely resistive load held at 100 kV whose absorbed power falls from 5 MW to 4 MW.
| Quantity | Symbol | Value |
|---|---|---|
| Supply frequency | $f$ | $60\ \text{Hz}$ |
| Transformer turns ratio (step-up) | $1{:}N$ | $1{:}5$ |
| Line characteristic impedance | $Z_0$ | $1000\ \Omega$ |
| Phase velocity | $v_p$ | $3\times10^{8}\ \text{m/s}$ |
| Line length | $\ell$ | $1250\ \text{km} = \lambda/4$ |
| Load voltage (held constant) | $V_L$ | $100\ \text{kV}$ |
| Load power range | $P_L$ | $5\ \text{MW} \rightarrow 4\ \text{MW}$ |
Find. The percentage change in generator EMF needed to hold $V_L$ at 100 kV as the load power falls from 5 MW to 4 MW.
Approach. Confirm the line really is a quarter wavelength, then use the quarter-wave inversion in its current form — the input voltage of a $\lambda/4$ line is $Z_0$ times the load current — to convert each load condition into a required primary EMF, and compare the two.
The reason the answer is so clean is worth stating: on a quarter-wave line the input voltage tracks the load current, and at fixed load voltage the current is directly proportional to power. The EMF therefore scales exactly as the load power, so a 5:4 power ratio is a 5:4 voltage ratio, i.e. 20 %. This is the same inversion that makes a quarter-wave line a natural constant-current driver, and it is why $\lambda/4$ sections are used as impedance transformers and as fault-tolerant feeds in practice. At 60 Hz, of course, a genuine 1250 km quarter-wave line is an idealisation — real long-distance AC lines are compensated well short of that length — but the algebra is the standard textbook exercise.
| Quantity | Symbol | Value |
|---|---|---|
| Wavelength at 60 Hz | $\lambda$ | $5000\ \text{km}$ |
| Load current at 5 MW | $I_L$ | $50.0\ \text{A}$ |
| Load current at 4 MW | $I_L$ | $40.0\ \text{A}$ |
| Line input voltage at 5 MW | $|V_{\text{in}}|$ | $50.0\ \text{kV}$ |
| Line input voltage at 4 MW | $|V_{\text{in}}|$ | $40.0\ \text{kV}$ |
| Generator EMF at 5 MW | $E$ | $10.0\ \text{kV}$ |
| Generator EMF at 4 MW | $E$ | $8.0\ \text{kV}$ |
| Required variation | $\Delta E/E$ | $20\ \%$ reduction |