22-Elec-B7 Power Systems Engineering · December 2017
Question 6 of 7: Line-to-line fault at the mid-point of a line — fault current and phase voltages
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, December 2017 — 16-Elec-B7 Power
Systems Engineering, 3 hours, open book, any non-communicating calculator permitted.
The paper prints seven problems; the rubric states that any five questions constitute a
complete paper and that all questions are of equal value, so only the first
five in the answer book are marked. All seven are worked here, because this set is a study
resource rather than a sitting. Sub-part point values are reproduced from the paper.
Reference texts. This exam code follows M. E. El-Hawary,
Electrical Power Systems: Design and Analysis (IEEE Press) — the notation used
below is his: the long-line ABCD constants of Problem 1, the round-rotor power-angle
relations of Problem 2, the cantilever transformer equivalent of Problem 3, the
power-flow injection equations of Problem 4, the network-reduction fault analysis of
Problems 5 and 6, and the equal-area criterion of Problem 7. Corroborating
references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and
Design, 6th ed. (ch. 5 transmission lines, ch. 6 power flow,
ch. 7–9 symmetrical components and unsymmetrical faults, ch. 11 transient
stability); J. J. Grainger and W. D. Stevenson, Power System Analysis; and
S. J. Chapman, Electric Machinery Fundamentals, 5th ed. (ch. 2
transformers, ch. 4–5 synchronous machines). Canadian practice references for the
protection and grounding discussion: CSA C22.1 Canadian Electrical Code, Part I
and the relevant IEEE C37 and C57 series.
Question 6: Line-to-line fault at the mid-point of a line — fault current and phase
voltages (25 points)
Given. The positive-sequence network of Figure (4), stated to be
identical to the negative-sequence network, on a 100 MVA base: a 1.00 pu source at the
reference node $N^+$, a left-hand path of $j0.20+j0.15$ pu reaching bus W, a right-hand
path of $j0.05+j0.15$ pu reaching bus V, and a $j0.20$ pu line joining W to V with
a line-to-line fault at its mid-point.
Given data (per unit at 100 MVA)
Path
Elements
Total to the reference
Reference to bus W
$j0.20$ in series with $j0.15$
$j0.35$
Reference to bus V
$j0.05$ in series with $j0.15$
$j0.20$
Line W–V
$j0.20$, fault at mid-point
$j0.10$ each side of F
Negative-sequence network
identical to positive
$X_2=X_1$
Find. (a) the current flowing into the fault; (b) all three phase voltages at
bus W and all three at bus V while the fault is on.
Figure 6.1 — The positive- (and identical negative-) sequence network of Figure (4). Reading it as a circuit rather than a picture, bus W sits 0.20 + 0.15 = 0.35 pu from the reference and bus V sits 0.05 + 0.15 = 0.20 pu from it.
Approach. Reduce the positive-sequence network to its Thevenin reactance at
F, connect the positive and negative networks in opposition (the line-to-line connection), take
the sequence currents, then recover the phase currents and the phase voltages at each bus from
the transfer reactances.
Figure 6.2 — Sequence-network interconnection for a line-to-line fault: positive and negative in opposition at the fault point, with no zero-sequence connection at all.
Read the network as a circuit. Each vertical reactance and the horizontal
reactance beneath it are in series on the way from the reference to the bus, so
$$X_{NW}=0.20+0.15=0.35\ \text{pu},\qquad X_{NV}=0.05+0.15=0.20\ \text{pu}$$
The fault splits the $j0.20$ pu line into two halves of $j0.10$ pu, so from F the
reference is reachable by $0.35+0.10=0.45$ through W and by $0.20+0.10=0.30$ through V.
Reduce to the Thevenin reactance at F. The two paths are simply in
parallel, and no delta–star transform is needed because there is no third branch bridging
W and V:
$$X_1=\frac{(0.45)(0.30)}{0.45+0.30}=\boxed{X_1=X_2=0.1800\ \text{pu}}$$
The transfer reactances that will be needed for part (b) come out of the same current
division. Injecting unit current at F, the fraction $0.30/0.75=0.400$ returns through W and
$0.45/0.75=0.600$ through V, so
$$Z_{WF}=0.400\times0.35=j0.1400,\qquad Z_{VF}=0.600\times0.20=j0.1200\ \text{pu}$$
Both must reproduce $X_1$ when the remaining half-line is added, and they do:
$0.1400+0.400(0.10)=0.1800$ and $0.1200+0.600(0.10)=0.1800$.
Connect the sequence networks for a line-to-line fault. Take the fault to
be between phases b and c, with phase a healthy. The boundary conditions are $I_a=0$,
$I_b=-I_c$ and $V_b=V_c$, which transform into $\hat I_{a0}=0$, $\hat I_{a2}=-\hat I_{a1}$ and
$\hat V_{a1}=\hat V_{a2}$ — that is, the positive and negative networks joined in
opposition at F with the zero-sequence network left entirely out of the problem. This is why
the paper supplies no zero-sequence diagram: a phase-to-phase fault has no earth path, so no
zero-sequence current can exist. Hence
$$\begin{aligned}
\hat I_{a1}&=\frac{1.0\angle0^\circ}{j(X_1+X_2)}=\frac{1.0}{j(2\times0.1800)}
=-j2.77778\ \text{pu}\\
\hat I_{a2}&=+j2.77778\ \text{pu},\qquad \hat I_{a0}=0
\end{aligned}$$
Recover the phase currents. Applying the symmetrical-component synthesis
with $a=1\angle120^\circ$,
$$\hat I_a=\hat I_{a1}+\hat I_{a2}=0$$
$$\hat I_b=a^{2}\hat I_{a1}+a\hat I_{a2}=(a^{2}-a)\hat I_{a1}=-j\sqrt3\,\hat I_{a1}$$
so the answer to part (a) is
$$\boxed{|\hat I_b|=|\hat I_c|=\sqrt3\,|\hat I_{a1}|=\sqrt3\,(2.77778)=4.81125\ \text{pu}}$$
with $\hat I_b=4.81125\angle180^\circ$ and $\hat I_c=4.81125\angle0^\circ$ — equal
and opposite, as the boundary condition $I_b=-I_c$ demands, and both real because the network is
purely reactive and the driving voltage is real. Phase a carries nothing. On the stated
100 MVA base this is 4.81125 times the base current at the fault location. The free
check is the ratio to the three-phase current at the same point,
$|I_{3\phi}|=1/X_1=5.5556$ pu, giving 0.86603 — exactly $\sqrt3/2$, which must
hold whenever $X_1=X_2$.
Compute the sequence voltages at each bus. The positive-sequence network
still contains its source, so its bus voltages fall from 1.0 by the transfer drop; the
negative-sequence network has no source, so its bus voltages are purely the transfer drop:
$$\hat V_{k1}=1.0-Z_{kF}\hat I_{a1},\qquad \hat V_{k2}=-Z_{kF}\hat I_{a2}=+Z_{kF}\hat I_{a1}$$
At bus W, with $Z_{WF}=j0.1400$,
$$\hat V_{W1}=1.0-(j0.1400)(-j2.77778)=0.61111,\qquad \hat V_{W2}=0.38889$$
and at bus V, with $Z_{VF}=j0.1200$,
$$\hat V_{V1}=0.66667,\qquad \hat V_{V2}=0.33333$$
Both sets are purely real because every impedance is a pure reactance and $\hat I_{a1}$ is purely
imaginary.
Synthesise the phase voltages at bus W. With $\hat V_{a0}=0$,
$$\hat V_a=\hat V_1+\hat V_2,\qquad
\hat V_b=a^{2}\hat V_1+a\hat V_2,\qquad
\hat V_c=a\hat V_1+a^{2}\hat V_2$$
At bus W,
$$\hat V_a=0.61111+0.38889=\boxed{1.0000\angle0^\circ\ \text{pu}}$$
$$\hat V_b=0.53576\angle-158.948^\circ,\qquad \hat V_c=0.53576\angle158.948^\circ\ \text{pu}$$
The healthy phase holding exactly 1.0 pu is not a coincidence: since
$\hat I_{a2}=-\hat I_{a1}$, the two transfer drops cancel in $\hat V_a=\hat V_1+\hat V_2$ at
every bus. It is the single most useful check on this class of problem.
Synthesise the phase voltages at bus V, and interpret. Repeating with
$\hat V_{V1}=0.66667$ and $\hat V_{V2}=0.33333$,
$$\hat V_a=\boxed{1.0000\angle0^\circ},\qquad
\hat V_b=0.57735\angle-150.0^\circ,\qquad
\hat V_c=0.57735\angle--150.0^\circ\ \text{pu}$$
Bus V holds its faulted phases higher (0.57735 pu) than bus W does
(0.53576 pu) because it is electrically stiffer — it sits only 0.20 pu from the
reference against W's 0.35 pu. At the fault point itself the two sequence voltages are each
0.5 pu, so $\hat V_b=\hat V_c=-0.5$ pu there, equal as the boundary condition
$V_b=V_c$ requires, while phase a remains at 1.0 pu. The faulted phase voltages at the two
buses therefore bracket that value, which is the qualitative shape of every line-to-line
fault.
Final results — Question 6 (per unit at 100 MVA)
Quantity
Symbol
Value
Thevenin reactance at F (each of positive and negative)
Check: the faulted phases are assumed to be b and c. The paper says only
"a line to line fault", without naming the phases. Phases b and c are the universal convention
because they make the healthy phase the reference phase and keep the sequence algebra real;
choosing any other pair rotates every phasor by $\pm120^\circ$ but changes no magnitude. Also
worth stating explicitly: the paper's text calls the diagram "Figure (5)" while the caption
on the page reads "Figure (4)". There is only one diagram, so the reference is
unambiguous.