NivaarExam PrepOfficial exam papers ↗

22-Elec-B8 Power Electronics and Drives · December 2019

Question 1 of 5: Radial distribution feeder with two loads

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, December 2019 — 16-Elec-B8 Power Electronics and Drives. Three hours; closed book with one double-sided aid sheet; an approved Casio or Sharp calculator. Five questions constitute a complete paper and all questions are of equal value, so each carries 20 marks. All a.c. voltages and currents are rms unless noted otherwise; for three-phase circuits voltages are line-to-line and power is total real power unless noted otherwise. Every question is solved below, in the exam's own order.

Reference texts.

Question 1: Radial distribution feeder with two loads (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantitySymbolValue
Feeder section, generator to node A$Z_1$$0.4 + j0.8\ \Omega$
Feeder section, node A to node B$Z_2$$0.4 + j0.8\ \Omega$
Load A real power, power factor$P_A,\ \cos\phi_A$$8\ \text{kW}$, 0.8 leading
Load B real power, power factor$P_B,\ \cos\phi_B$$10\ \text{kW}$, 0.6 lagging
Terminal voltage at load B (reference phasor)$V_B$$215\ \text{V}\ \angle\ 0^\circ$

Find. The terminal voltage at load A, and the apparent power, power factor and terminal voltage at the generator.

[Figure not reproduced: Figure 1.1 — The radial feeder redrawn from the exam schematic. Only the far-end voltage is known, so the solution marches from load B back towards the generator. See the official exam paper.]

Approach. Take $V_B$ as the reference phasor, convert each load's complex power into a current, and walk back towards the source adding the series impedance drop at each section; the generator quantities then follow from its own terminal voltage and current.

  1. Part (a) — express load B as a complex power. The real power and power factor fix the apparent power, and a lagging power factor puts the reactive power in the positive (absorbing) direction: $$S_B = \frac{P_B}{\cos\phi_B}\ \angle\ \arccos(\cos\phi_B) = \frac{10\,000}{0.6}\ \angle\ 53.13^\circ = 16\,666.7\ \text{VA}\ \angle\ 53.13^\circ$$ that is $S_B = 10\,000 + j13\,333\ \text{VA}$.
  2. Convert that power into the current in section 2. With $S = V I^{*}$ the current is the conjugate of the power divided by the voltage, $$I_B = \left(\frac{S_B}{V_B}\right)^{\!*} = \left(\frac{16\,666.7\ \angle\ 53.13^\circ}{215\ \angle\ 0^\circ}\right)^{\!*} = 77.52\ \text{A}\ \angle\ -53.13^\circ$$ The current lags $V_B$ by $53.13^\circ$, as a lagging load must.
  3. Add the drop across $Z_2$ to reach node A. All of $I_B$ — and only $I_B$ — flows in the second section, so $$I_B Z_2 = (77.52\ \angle\ -53.13^\circ)(0.894\ \angle\ 63.43^\circ) = 69.34\ \text{V}\ \angle\ 10.31^\circ = 68.22 + j12.40\ \text{V}$$ Adding this to the reference voltage $V_B = 215 + j0$ gives $$\boxed{\,V_A = 283.22 + j12.40 = 283.5\ \text{V}\ \angle\ 2.51^\circ\,}$$ The far end of the feeder is 68.5 V below node A — a 24 per cent drop across one section.
  4. Part (b) — find the current drawn by load A. Load A is specified at 8 kW and 0.8 leading, so its apparent power is $8\,000/0.8 = 10\,000\ \text{VA}$ and its reactive power is negative ($S_A = 8\,000 - j6\,000\ \text{VA}$). Its current is referred to the node-A voltage just computed, and leads it by $\phi_A = 36.87^\circ$: $$I_A = \left(\frac{S_A}{V_A}\right)^{\!*} = \left(\frac{10\,000\ \angle\ -36.87^\circ}{283.5\ \angle\ 2.51^\circ}\right)^{\!*} = 35.27\ \text{A}\ \angle\ 39.38^\circ$$
  5. Sum the two branch currents at node A. Kirchhoff's current law at the node gives the current the generator must supply: $$I_g = I_A + I_B = (27.26 + j22.37) + (46.51 - j62.01) = 73.78 - j39.64\ \text{A}$$ $$I_g = 83.75\ \text{A}\ \angle\ -28.25^\circ$$ Note that the magnitudes do not add: $35.27 + 77.52 = 112.8\ \text{A}$ arithmetically, but only 83.75 A phasorially, because load A's leading current partly cancels load B's lagging one.
  6. Add the drop across $Z_1$ to reach the generator terminals. $$I_g Z_1 = (83.75\ \angle\ -28.25^\circ)(0.894\ \angle\ 63.43^\circ) = 74.91\ \text{V}\ \angle\ 35.19^\circ = 61.22 + j43.17\ \text{V}$$ $$\boxed{\,V_g = 344.44 + j55.57 = 348.9\ \text{V}\ \angle\ 9.17^\circ\,}$$
  7. Read the generator's apparent power and power factor off its own terminal quantities. The machine sees $V_g$ across it and delivers $I_g$: $$S_g = V_g I_g^{*} = (348.9\ \angle\ 9.17^\circ)(83.75\ \angle\ 28.25^\circ) = 29\,220\ \text{VA}\ \angle\ 37.41^\circ$$ $$\boxed{\,|S_g| = 29.22\ \text{kVA},\qquad \cos\phi_g = \cos 37.41^\circ = 0.794\ \text{lagging}\,}$$ In rectangular form $S_g = 23.21\ \text{kW} + j17.75\ \text{kvar}$.
  8. Close the loop with an independent power balance. The generator must supply both loads plus the $I^2Z$ losses in the two sections: $$I_B^2 Z_2 = (77.52)^2(0.4 + j0.8) = 2\,404 + j4\,807\ \text{VA}$$ $$I_g^2 Z_1 = (83.75)^2(0.4 + j0.8) = 2\,806 + j5\,611\ \text{VA}$$ $$S_A + S_B + I_B^2 Z_2 + I_g^2 Z_1 = 23\,209 + j17\,752\ \text{VA}$$ which reproduces $S_g$ exactly. This single check validates both voltages, both currents and both drops at once.
ReImVᵇ = 215 ∠ 0°Vᵀ = 283.5 ∠ 2.51°Vᵍ = 348.9 ∠ 9.17°IᶲZ₂ dropIᵤZ₁ dropVoltage build-up from load B back to the generator (drawn to scale)
Figure 1.2 — The three voltage phasors drawn to scale. Each section drop is dominated by its reactive part, which is why the voltage magnitude climbs steeply while the angle advances by only about nine degrees in total.

Check: two engineering readings are stated explicitly.

(1) The circuit is treated as single-phase. The exam schematic shows a two-wire loop — an outgoing conductor carrying $Z_1$ and $Z_2$ and a common return — with no neutral, no phase labels and no $\sqrt{3}$ anywhere in the data, so 215 V is a phase-to-phase (two-wire) voltage and the powers are single-phase. Had the same numbers been meant as a balanced three-phase feeder with 215 V line-to-line and 10 kW total, load B's current would have been $10\,000/(\sqrt{3}\cdot 215\cdot 0.6) = 44.8\ \text{A}$ and every result below would scale accordingly.

(2) The feeder impedances are unrealistically large for the load. The generator must hold 348.9 V to deliver 215 V at the far end — a 62 per cent rise — and the copper loss is 5.21 kW against 18 kW of load, i.e. 29 per cent. No real distribution circuit would be built this way (Canadian practice under CSA C22.1 Section 8 would hold the total drop to about 5 per cent). The numbers are internally consistent and are solved as given; the exercise is testing the phasor bookkeeping, not the conductor sizing.

Final results.

PartQuantityResult
(a)Terminal voltage at load A$283.5\ \text{V}\ \angle\ 2.51^\circ$
(b)Generator apparent power$29.22\ \text{kVA}$
(b)Generator power factor0.794 lagging
(b)Generator terminal voltage$348.9\ \text{V}\ \angle\ 9.17^\circ$
—Generator current$83.75\ \text{A}\ \angle\ -28.25^\circ$
—Total feeder copper loss$5.21\ \text{kW}$ (and $10.42\ \text{kvar}$)
← Paper overview