22-Elec-B8 Power Electronics and Drives · December 2019
Question 1 of 5: Radial distribution feeder with two loads
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, December 2019 —
16-Elec-B8 Power Electronics and Drives. Three hours; closed book with one
double-sided aid sheet; an approved Casio or Sharp calculator. Five questions
constitute a complete paper and all questions are of equal value, so each carries
20 marks. All a.c. voltages and currents are rms unless noted otherwise; for
three-phase circuits voltages are line-to-line and power is total real power
unless noted otherwise. Every question is solved below, in the exam's own order.
Reference texts.
M. H. Rashid, Power Electronics: Circuits, Devices and Applications,
4th ed. — the primary reference for this exam code (thyristor statics ch. 7,
a.c. voltage controllers ch. 11, d.c. choppers ch. 5).
N. Mohan, T. M. Undeland and W. P. Robbins, Power Electronics: Converters,
Applications and Design, 3rd ed. — switching-converter analysis and
d.c.–d.c. converter waveforms.
C. W. Lander, Power Electronics, 3rd ed. — a compact treatment of
phase control and of the chopper current equations used in Question 5.
B. K. Bose, Modern Power Electronics and AC Drives, and R. Krishnan,
Electric Motor Drives: Modeling, Analysis and Control — for the drive
context behind Questions 3 and 4.
J. J. Grainger and W. D. Stevenson, Power System Analysis — for the
radial-feeder and three-phase load calculations of Questions 1 and 2.
Question 1: Radial distribution feeder with two loads (20 marks)
Find. The terminal voltage at load A, and the apparent power, power factor and terminal voltage at the generator.
[Figure not reproduced: Figure 1.1 — The radial feeder redrawn from the exam schematic. Only the far-end voltage is known, so the solution marches from load B back towards the generator. See the official exam paper.]
Approach. Take $V_B$ as the reference phasor, convert each load's complex power into a current, and walk back towards the source adding the series impedance drop at each section; the generator quantities then follow from its own terminal voltage and current.
Part (a) — express load B as a complex power.
The real power and power factor fix the apparent power, and a lagging power factor
puts the reactive power in the positive (absorbing) direction:
$$S_B = \frac{P_B}{\cos\phi_B}\ \angle\ \arccos(\cos\phi_B)
= \frac{10\,000}{0.6}\ \angle\ 53.13^\circ
= 16\,666.7\ \text{VA}\ \angle\ 53.13^\circ$$
that is $S_B = 10\,000 + j13\,333\ \text{VA}$.
Convert that power into the current in section 2.
With $S = V I^{*}$ the current is the conjugate of the power divided by the voltage,
$$I_B = \left(\frac{S_B}{V_B}\right)^{\!*}
= \left(\frac{16\,666.7\ \angle\ 53.13^\circ}{215\ \angle\ 0^\circ}\right)^{\!*}
= 77.52\ \text{A}\ \angle\ -53.13^\circ$$
The current lags $V_B$ by $53.13^\circ$, as a lagging load must.
Add the drop across $Z_2$ to reach node A.
All of $I_B$ — and only $I_B$ — flows in the second section, so
$$I_B Z_2 = (77.52\ \angle\ -53.13^\circ)(0.894\ \angle\ 63.43^\circ)
= 69.34\ \text{V}\ \angle\ 10.31^\circ = 68.22 + j12.40\ \text{V}$$
Adding this to the reference voltage $V_B = 215 + j0$ gives
$$\boxed{\,V_A = 283.22 + j12.40 = 283.5\ \text{V}\ \angle\ 2.51^\circ\,}$$
The far end of the feeder is 68.5 V below node A — a 24 per cent drop
across one section.
Part (b) — find the current drawn by load A.
Load A is specified at 8 kW and 0.8 leading, so its apparent power is
$8\,000/0.8 = 10\,000\ \text{VA}$ and its reactive power is negative
($S_A = 8\,000 - j6\,000\ \text{VA}$). Its current is referred to the node-A voltage
just computed, and leads it by $\phi_A = 36.87^\circ$:
$$I_A = \left(\frac{S_A}{V_A}\right)^{\!*}
= \left(\frac{10\,000\ \angle\ -36.87^\circ}{283.5\ \angle\ 2.51^\circ}\right)^{\!*}
= 35.27\ \text{A}\ \angle\ 39.38^\circ$$
Sum the two branch currents at node A.
Kirchhoff's current law at the node gives the current the generator must supply:
$$I_g = I_A + I_B = (27.26 + j22.37) + (46.51 - j62.01) = 73.78 - j39.64\ \text{A}$$
$$I_g = 83.75\ \text{A}\ \angle\ -28.25^\circ$$
Note that the magnitudes do not add: $35.27 + 77.52 = 112.8\ \text{A}$
arithmetically, but only 83.75 A phasorially, because load A's leading current
partly cancels load B's lagging one.
Add the drop across $Z_1$ to reach the generator terminals.
$$I_g Z_1 = (83.75\ \angle\ -28.25^\circ)(0.894\ \angle\ 63.43^\circ)
= 74.91\ \text{V}\ \angle\ 35.19^\circ = 61.22 + j43.17\ \text{V}$$
$$\boxed{\,V_g = 344.44 + j55.57 = 348.9\ \text{V}\ \angle\ 9.17^\circ\,}$$
Read the generator's apparent power and power factor off its own
terminal quantities. The machine sees $V_g$ across it and delivers $I_g$:
$$S_g = V_g I_g^{*} = (348.9\ \angle\ 9.17^\circ)(83.75\ \angle\ 28.25^\circ)
= 29\,220\ \text{VA}\ \angle\ 37.41^\circ$$
$$\boxed{\,|S_g| = 29.22\ \text{kVA},\qquad
\cos\phi_g = \cos 37.41^\circ = 0.794\ \text{lagging}\,}$$
In rectangular form $S_g = 23.21\ \text{kW} + j17.75\ \text{kvar}$.
Close the loop with an independent power balance.
The generator must supply both loads plus the $I^2Z$ losses in the two sections:
$$I_B^2 Z_2 = (77.52)^2(0.4 + j0.8) = 2\,404 + j4\,807\ \text{VA}$$
$$I_g^2 Z_1 = (83.75)^2(0.4 + j0.8) = 2\,806 + j5\,611\ \text{VA}$$
$$S_A + S_B + I_B^2 Z_2 + I_g^2 Z_1 = 23\,209 + j17\,752\ \text{VA}$$
which reproduces $S_g$ exactly. This single check validates both voltages, both
currents and both drops at once.
Figure 1.2 — The three voltage phasors drawn to scale. Each section drop is dominated by its reactive part, which is why the voltage magnitude climbs steeply while the angle advances by only about nine degrees in total.
Check: two engineering readings are stated explicitly.
(1) The circuit is treated as single-phase. The exam schematic shows a
two-wire loop — an outgoing conductor carrying $Z_1$ and $Z_2$ and a common
return — with no neutral, no phase labels and no $\sqrt{3}$ anywhere in the
data, so 215 V is a phase-to-phase (two-wire) voltage and the powers are
single-phase. Had the same numbers been meant as a balanced three-phase feeder
with 215 V line-to-line and 10 kW total, load B's current would have been
$10\,000/(\sqrt{3}\cdot 215\cdot 0.6) = 44.8\ \text{A}$ and every result below
would scale accordingly.
(2) The feeder impedances are unrealistically large for the load. The
generator must hold 348.9 V to deliver 215 V at the far end — a
62 per cent rise — and the copper loss is 5.21 kW against 18 kW
of load, i.e. 29 per cent. No real distribution circuit would be built this
way (Canadian practice under CSA C22.1 Section 8 would hold the total drop to
about 5 per cent). The numbers are internally consistent and are solved as
given; the exercise is testing the phasor bookkeeping, not the conductor
sizing.