22-Mec-B2 Environmental Control in Buildings · May 2014
Question 2 of 8: Winter preheat, humidify and reheat plant
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of Ontario / Engineers Canada annual examination, 07-Mec-B2 Environmental Control in Buildings, May 2014. Three hours, open book, non-communicating calculator permitted. Eight problems of 20 points each; candidates answer five. All eight are solved here, because the set is a study resource. Psychrometric charts (SI and I-P) and a DuPont HFC-134a pressure-enthalpy diagram are attached to the paper.
Reference texts.
ASHRAE, Handbook — Fundamentals (2021): Ch. 1 Psychrometrics, Ch. 14 Climatic Design Information, Ch. 16 Ventilation and Infiltration, Ch. 18 Nonresidential Cooling and Heating Load Calculations, Ch. 21 Duct Design, Ch. 25–27 Heat, Air and Moisture Control.
F. C. McQuiston, J. D. Parker and J. D. Spitler, Heating, Ventilating and Air Conditioning: Analysis and Design, 6th ed., Wiley.
E. G. Pita, Air Conditioning Principles and Systems, 4th ed., Prentice Hall.
W. P. Jones, Air Conditioning Engineering, 5th ed., Butterworth-Heinemann (fan laws, spray chambers).
Y. A. Çengel and M. A. Boles, Thermodynamics: An Engineering Approach, 9th ed., McGraw-Hill (vapour-compression cycles).
ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality; ANSI/ASHRAE Standard 55, Thermal Environmental Conditions for Human Occupancy.
National Research Council Canada, National Building Code of Canada and National Energy Code of Canada for Buildings.
Question 2: Winter preheat, humidify and reheat plant (20 marks)
Given. A winter preheat — adiabatic-humidify — reheat plant taking 25% outdoor air by mass, serving a space with an all-sensible heating load, as tabulated.
Design data, Problem 2
Quantity
Symbol
Value
Outdoor-air fraction by mass
$x$
0.25
Room heating load (all sensible)
$q$
75 kW
Room dry-bulb temperature
$t_R$
21 °C
Room relative humidity
$\phi_R$
30 %
Outdoor dry-bulb temperature
$t_O$
−12 °C
Outdoor relative humidity
$\phi_O$
saturated (see assumption below)
Supply air temperature
$t_6$
40 °C
Barometric pressure
$p$
101.325 kPa
Find. The plant arrangement and its psychrometric cycle with every state identified, the total mass flow, the preheater and reheater ratings in Btu/h, and the adiabatic efficiency and make-up water demand of the spray cabinet.
Figure 2.1 — (a) Plant arrangement. 1 outdoor air, 2 return air, 3 mixed air, 4 leaving the preheater, 5 leaving the adiabatic spray cabinet, 6 supply air leaving the reheater.
Check: the printed outdoor humidity is incomplete. The source reads “outside air −12°C, and essentially percent relative humidity” — the numeral is missing from the printed paper. Saturated outdoor air is assumed here, the usual Canadian winter design convention. The alternative reading (essentially zero humidity) changes the answers by only a few per cent and is quantified at the end of this solution; no conclusion depends on the choice.
Approach. Fix the room and outdoor states, obtain the mass flow from the all-sensible room load and the stated supply temperature, mix the two air streams, and then test whether the mixed air already has enough adiabatic-saturation capacity to reach the humidity the room needs. That test decides the preheater duty; the reheater then closes the sensible balance to 40 °C.
Room and outdoor states. At 21 °C the saturation pressure is 2.487 kPa, so at 30% RH $$W_R = \frac{0.622(0.30 \times 2.487)}{101.325 - 0.746} = 0.004615\ \text{kg/kg}, \qquad h_R = 32.85\ \text{kJ/kg}$$and saturated air at −12 °C (saturation pressure 0.2176 kPa over ice) carries $$W_O = 0.001337\ \text{kg/kg}, \qquad h_O = -8.76\ \text{kJ/kg}$$
(d) Total system mass flow. The load is entirely sensible, so the supply air need only carry a temperature difference into the room. With the moist-air specific heat $c_p = 1.006 + 1.86\,W_R = 1.015$ kJ/kg·K, $$\dot m = \frac{q}{c_p\,(t_6 - t_R)} = \frac{75}{1.015\,(40-21)} = \boxed{3.89\ \text{kg/s}}$$which is about 3.3 m³/s at room conditions. The outdoor-air stream is $0.25(3.89) = 0.973$ kg/s and the return stream 2.92 kg/s.
Supply humidity ratio. The room has no latent load, so in steady state the air leaves the room carrying exactly the moisture it brought in: $$W_6 = W_5 = W_R = 0.004615\ \text{kg/kg}$$The whole purpose of the spray cabinet is therefore to replace the moisture that the dry outdoor air dilutes out of the mixture, not to serve a room latent load.
(c) Mixed state 3. Mass-weighting the return and outdoor streams, $$t_3 = 0.75(21) + 0.25(-12) = 12.75\ ^\circ\text{C}, \qquad W_3 = 0.75(0.004615) + 0.25(0.001337) = 0.003795\ \text{kg/kg}$$$$h_3 = 1.006(12.75) + 0.003795\,[2501 + 1.86(12.75)] = 22.41\ \text{kJ/kg}$$The mixture is 3.8 g/kg short of the 4.6 g/kg the room needs.
(e) Preheater duty — test it, do not assume it. An adiabatic spray cabinet moves the air along a line of constant enthalpy, so the wettest state it could possibly deliver is saturation at the adiabatic saturation temperature of the entering air. For $h_3 = 22.41$ kJ/kg that temperature is $$t_3^{*} = 6.88\ ^\circ\text{C}, \qquad W^{*} = 0.006161\ \text{kg/kg}$$The mixed air can therefore reach 6.16 g/kg unaided, comfortably more than the 4.62 g/kg required. Preheating would raise the enthalpy and increase that capacity further, so it is not needed: $$\boxed{q_{preheat} = 0 \ \text{at the design point}}$$For completeness, an ideal washer discharging saturated air at the required humidity ratio would need entering air at only 4.8 °C — well below the 12.75 °C the mixing box already provides.
Rating the preheater anyway. The coil still has to be selected for its worst duty, which is the morning warm-up or purge condition with the outdoor damper fully open. Lifting the whole 3.89 kg/s from −12 °C to a +5 °C freeze-protection set point requires $$q_{preheat,rating} = \dot m\,c_p\,\Delta t = 3.89(1.008)(5-(-12)) = 66.7\ \text{kW} = \boxed{2.28\times10^{5}\ \text{Btu/h}}$$
State 5, leaving the spray cabinet. With no preheat, state 4 coincides with state 3 and the adiabatic process runs from $W_3$ to $W_5 = 0.004615$ kg/kg at constant enthalpy: $$h_5 = h_3 \;\Rightarrow\; t_5 = \frac{h_3 - 2501\,W_5}{1.006 + 1.86\,W_5} = \frac{22.41 - 11.54}{1.0146} = 10.7\ ^\circ\text{C}$$which is 58% relative humidity — the cabinet is deliberately operating well short of saturation.
(e) Reheater duty. The reheater raises state 5 to the 40 °C supply condition at constant humidity ratio: $$q_{reheat} = \dot m\,c_p\,(t_6 - t_5) = 3.89(1.015)(40 - 10.7) = 115.6\ \text{kW} = \boxed{3.94\times10^{5}\ \text{Btu/h}}$$This checks against an overall plant balance: the 75 kW room load, plus $0.973(1.008)(21-(-12)) = 32.4$ kW to warm the ventilation air from outdoor to room temperature, plus 8.0 kW of latent heat carried by the evaporating spray water, total 115.4 kW — the same figure to within rounding.
(f) Adiabatic efficiency and make-up water. The saturation efficiency of a spray cabinet compares the moisture actually picked up with the moisture an ideal, fully saturating washer would add on the same enthalpy line: $$\eta = \frac{W_5 - W_3}{W^{*} - W_3} = \frac{0.004615-0.003795}{0.006161-0.003795} = \boxed{0.35}$$The identical figure follows from the temperature form, $(t_3 - t_5)/(t_3 - t_3^{*}) = (12.75-10.7)/(12.75-6.88) = 0.35$. Make-up water is simply the moisture added: $$\dot m_w = \dot m\,(W_5 - W_3) = 3.89\,(0.000820) = 0.00319\ \text{kg/s} = \boxed{11.5\ \text{kg/h}}$$
Figure 2.2 — (b) and (c) The operating cycle on the SI psychrometric chart. 1 outdoor air (−12 °C saturated), 2 room air (21 °C, 30% RH), 3 the mixed state on the straight mixing line, 5 the spray-cabinet discharge on the constant-enthalpy line through 3, and 6 the 40 °C supply state reached by sensible reheat. State 4 coincides with 3 because no preheat is required.
A saturation efficiency of only 35% means the cabinet must be throttled — one bank of sprays in service, or a face-and-bypass damper — rather than run flat out. That is the practical control conclusion of the problem: the humidity is held by modulating the washer, and the preheater exists for frost protection rather than for humidification duty.
Taking the alternative reading of the incomplete printed line, with essentially dry outdoor air, the mixed humidity ratio falls to 3.46 g/kg, the required saturation efficiency rises to 46%, the reheater duty rises to 118.9 kW and the make-up water to 16.2 kg/h. The preheater duty remains zero and every qualitative conclusion is unchanged.
Final results, Problem 2
Quantity
Result
Room state (2)
21 °C, W = 0.004615 kg/kg, h = 32.85 kJ/kg
Outdoor state (1)
−12 °C saturated, W = 0.001337 kg/kg, h = −8.76 kJ/kg