24-Bld-A4 Building Environmental Control Systems · May 2017
Question 1 of 14: Air-Handling Unit with Cooling-Coil / Desiccant-Bypass Dehumidification
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
National Exams May 2017 — 07-Bld-A4, Building Environmental Control Systems (Building Engineering). 3-hour closed-book exam: Section 1 (four 20-mark essay/calculation questions) + Section 2 (ten 2-mark multiple-choice questions).
Reference texts: ASHRAE Handbook — Fundamentals (2021 ed.); ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality (2022 ed.); McQuiston, Parker & Spitler, Heating, Ventilating, and Air Conditioning: Analysis and Design (6th ed.); National Building Code of Canada 2020 (NBCC); National Energy Code of Canada for Buildings 2020 (NECB).
Question 1.1: Air-Handling Unit with Cooling-Coil / Desiccant-Bypass Dehumidification (20 marks)
Given. Room (IA): 26°C, 60% RH, total load ΔH = 40 kW, moisture load ΔW = 10 g/s. Outdoor air (OA): 34°C, 80% RH, with ṁOA = 0.25 ṁSA. Supply air (SA) leaves at 20°C. Point A (leaving cooling coil C1): 17°C. Point B (leaving desiccant dehumidifier D): 38°C. The C1 outlet stream splits 50%/50% into a bypass leg (unchanged, state A) and a desiccant leg (state B), which remix adiabatically to state C before coil C2. Atmospheric pressure 101.325 kPa.
Given data — key points
Point
Description
Known value
IA
Room (return) air
26°C, 60% RH
OA
Outdoor air
34°C, 80% RH, 0.25 ṁSA
A
Leaving cooling coil C1
17°C
B
Leaving desiccant dehumidifier D
38°C
SA
Supply air to room
20°C
ΔH, ΔW
Room total / moisture load
40 kW, 10 g/s
Find. The dry-bulb temperature and relative humidity of every key point on the psychrometric chart; the supply-air mass flow rate ṁSA; and the heat-removal duties QC1 and QC2 of the two cooling coils.
Fig. 1.1a — Air-handling process flow: RA and OA mix to MA, cool through C1 to state A, split 50/50 between a direct bypass and desiccant dehumidifier D (state B), remix to state C, and cool through C2 to SA.
Fig. 1.1b — Psychrometric-chart plot of the process (part 1). OA–IA is the mixing line (MA lies on it); MA→A is the C1 cooling/dehumidifying process; A→B (dashed) is the desiccant dehumidifier's constant-enthalpy line; A and B remix along the straight line to C; C→SA is the C2 cooling/dehumidifying process.
Approach. Apply steady-flow mass and energy balances at each device using standard moist-air psychrometric relations (saturation pressure, humidity ratio W, enthalpy h); locate each state, then use the room's total-to-moisture load ratio to pin down the supply state and mass flow, and coil enthalpy differences to get the coil duties.
State the room air (IA) and outdoor air (OA). Using the Buck saturation-pressure correlation at atmospheric pressure 101.325 kPa, $W = 0.622\,p_w/(P-p_w)$ with $p_w = \text{RH}\cdot p_{ws}(T)$, and $h = 1.006T + W(2501+1.86T)$ kJ/kg (T in °C, W in kg/kg):
$$W_{IA}=12.64\ \text{g/kg}, \qquad h_{IA}=58.37\ \text{kJ/kg}$$
$$W_{OA}=27.29\ \text{g/kg}, \qquad h_{OA}=104.17\ \text{kJ/kg}$$
State point A (leaving C1). A cooling/dehumidifying coil driven well below the incoming dew point leaves air very close to saturation; taking A at 100% RH, 17°C gives $W_A = 12.13$ g/kg, $h_A = 47.81$ kJ/kg. Check: state A assumed saturated (100% RH) at the given 17°C leaving temperature — the standard simplification for a coil with a low bypass factor, since the exam gives no coil bypass factor or apparatus dew point.
State point B (leaving desiccant dehumidifier D). Solid-desiccant adsorption is essentially adiabatic: it trades latent heat for sensible heat along a constant-enthalpy line, so $h_B = h_A = 47.81$ kJ/kg. At the given $T_B = 38\,{}^{\circ}\text{C}$, solving $h_B = 1.006T_B + W_B(2501+1.86T_B)$ for $W_B$ gives $W_B = 3.73$ g/kg (9.1% RH — very dry, as expected for desiccant air).
State point C (bypass + B remixed, 50/50). Since the split is 50/50 and $h_B=h_A$ exactly, the mixture enthalpy is $$h_C = 0.5h_A+0.5h_B=h_A=47.81\ \text{kJ/kg}$$ regardless of the split fraction — a useful check. The dry-bulb and humidity ratio are the straight mass-weighted average of A and B: $T_C = 0.5(17)+0.5(38)=27.5\,{}^{\circ}\text{C}$, $W_C = 0.5(12.13)+0.5(3.73)=7.93$ g/kg (34.7% RH).
Locate SA and the mass flow rate via the room condition line. The room process line SA→IA has slope $\Delta H/\Delta W = 40/0.010 = 4000$ kJ/kg (per kg of water), i.e. $ (h_{IA}-h_{SA})/(W_{IA}-W_{SA}) = 4000$. Combined with $h_{SA}=1.006(20)+W_{SA}(2501+1.86\times20)$ at the given $T_{SA}=20\,{}^{\circ}\text{C}$, solving the two equations simultaneously gives
$$W_{SA}=8.41\ \text{g/kg},\qquad h_{SA}=41.47\ \text{kJ/kg}\ (57.8\%\ \text{RH})$$
$$\boxed{\dot m_{SA} = \dfrac{\Delta H}{h_{IA}-h_{SA}} = \dfrac{40}{58.37-41.47} = 2.37\ \text{kg/s}}$$
State the mixed air MA and find QC1. With $\dot m_{OA}=0.25\dot m_{SA}$ and $\dot m_{RA}=0.75\dot m_{SA}$ (return air = supply less the outdoor-air fraction, balanced by an equal exhaust EA), the mixed state is the mass-weighted average $W_{MA}=0.75W_{IA}+0.25W_{OA}=16.30$ g/kg, $h_{MA}=0.75h_{IA}+0.25h_{OA}=69.82$ kJ/kg ($T_{MA}\approx28.0\,{}^{\circ}\text{C}$, 68.3% RH). Coil C1 removes:
$$\boxed{Q_{C1} = \dot m_{SA}(h_{MA}-h_A) = 2.37(69.82-47.81) = 52.1\ \text{kW}}$$
Find QC2. Coil C2 cools state C down to SA:
$$\boxed{Q_{C2} = \dot m_{SA}(h_C-h_{SA}) = 2.37(47.81-41.47) = 15.0\ \text{kW}}$$