24-Bld-A4 Building Environmental Control Systems · May 2017
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
National Exams May 2017 — 07-Bld-A4, Building Environmental Control Systems (Building Engineering). 3-hour closed-book exam: Section 1 (four 20-mark essay/calculation questions) + Section 2 (ten 2-mark multiple-choice questions).
Reference texts: ASHRAE Handbook — Fundamentals (2021 ed.); ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air Quality (2022 ed.); McQuiston, Parker & Spitler, Heating, Ventilating, and Air Conditioning: Analysis and Design (6th ed.); National Building Code of Canada 2020 (NBCC); National Energy Code of Canada for Buildings 2020 (NECB).
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Given/Find. Each room's volume (floor area × 2.8 m ceiling height) is ventilated at its own room-type ACH; total flow = Σ(volume × ACH). Check: the source table prints the ACH row as "2, 3, 6, 15" under column headers "Room | Bedroom | Living Room | Bathroom | Kitchen" — the leading "Room"/ "ACH (1/hr)" pair is the row LABEL, not a fifth data category, so the four numbers map to Bedroom=2, Living Room=3, Bathroom=6, Kitchen=15.
| Answer: (b) 568.4 m³/hr |