Question 4 of 8: First-Order Thermometer — Response to a Ramping Bath

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Reference texts: D. E. Seborg, T. F. Edgar, D. A. Mellichamp & F. J. Doyle III, Process Dynamics and Control (4th ed., Wiley) — Laplace-domain modelling, linearisation, transfer functions, feedback stability, frequency response and IMC design; G. Stephanopoulos, Chemical Process Control: An Introduction to Theory and Practice (Prentice Hall) — Routh test, Nyquist criterion, state-space models and dead-time systems; D. R. Coughanowr & S. E. LeBlanc, Process Systems Analysis and Control (3rd ed., McGraw-Hill) — first-order tank/thermal dynamics, step/ramp response and block-diagram algebra. Standard control conventions (deviation variables; unity valve/sensor gains unless stated) are used throughout. This sitting is an open-book paper of eight problems of which any five constitute a complete exam; all eight are solved here.

Problem 4: First-Order Thermometer — Response to a Ramping Bath (20%)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A first-order sensor driven by a temperature ramp:

QuantitySymbolValue
Time constant$\tau$$0.2$ min
Ramp rate (slope)$a$$1\ ^\circ\mathrm{C/min}$
Sensor model$\dfrac{T_m(s)}{T_b(s)}$$\dfrac{1}{\tau s+1}$
Initial condition—at equilibrium ($T_m=T_b$)

Find. (a) the error $e=T_b-T_m$ at $t=0.1$ and $1$ min; (b) the maximum error and its timing; (c) the ultimate time lag.

P1(c): ramp bath input and lagging thermometer response 00.20.40.60.81.01.2 00.40.81.2 gap → aτ=0.2 bath $T_b=at$ reading $T_m$ time $t$ (min) temperature rise ($^\circ$C)
Problem 1(c): the bath rises as a straight ramp; the thermometer reading is a parallel ramp displaced downward and to the right. The vertical gap grows to the steady error $a\tau=0.2\,{}^\circ$C, equivalent to a constant time lag of $\tau=0.2$ min.

Approach. For a first-order lag the tracking error to a ramp has the closed form $e(t)=a\tau\!\left(1-e^{-t/\tau}\right)$; evaluate it at the two times, take its monotone asymptote for the maximum, and read the ultimate lag from the steady offset divided by the slope.

  1. Error transfer function. The bath is the input $T_b=at$, so $T_b(s)=a/s^2$. The reading follows $T_m(s)=\dfrac{1}{\tau s+1}T_b(s)$, hence the error $$E(s)=T_b(s)-T_m(s)=\Big(1-\tfrac{1}{\tau s+1}\Big)\frac{a}{s^2}=\frac{a\tau}{s(\tau s+1)}.$$
  2. Invert to the time domain. Partial fractions give $\dfrac{a\tau}{s(\tau s+1)}=\dfrac{a\tau}{s}-\dfrac{a\tau^{2}}{\tau s+1}$, so $$\boxed{e(t)=a\tau\left(1-e^{-t/\tau}\right)}=0.2\left(1-e^{-t/0.2}\right).$$ The error starts at zero and rises monotonically toward $a\tau$.
  3. (a-i) At $t=0.1$ min. $e=0.2\left(1-e^{-0.1/0.2}\right)=0.2\left(1-e^{-0.5}\right)=0.2(0.3935)=\boxed{0.0787\,{}^\circ\mathrm C}$ — the reading trails the bath by about $0.08\,{}^\circ$C.
  4. (a-ii) At $t=1$ min. $e=0.2\left(1-e^{-1/0.2}\right)=0.2\left(1-e^{-5}\right)=0.2(0.99326)=\boxed{0.1987\,{}^\circ\mathrm C}$; five time constants have elapsed, so the transient ($e^{-5}=0.0067$) is nearly dead and the error is within $0.7\%$ of its asymptote.
  5. (b) Maximum deviation. Because $e(t)=a\tau(1-e^{-t/\tau})$ increases monotonically (its derivative $ae^{-t/\tau}$ is always positive), the largest deviation is the limit $$\boxed{e_{\max}=a\tau=0.2\,{}^\circ\mathrm C}\quad\text{approached as } t\to\infty.$$ It is not a finite-time peak — the ramp keeps the sensor permanently behind, and the offset saturates at $a\tau$ (already $99.3\%$ reached by $t=1$ min).
  6. (c) Ultimate time lag. At steady state the reading is $T_m=at-a\tau=a(t-\tau)$: an identical ramp shifted right by a fixed time. The lag is the offset divided by the slope, $$\boxed{\Delta t=\frac{a\tau}{a}=\tau=0.2\ \text{min}.}$$ The thermometer forever reports the temperature the bath had $0.2$ min earlier.
QuantityValue
(a-i) Error at $t=0.1$ min$0.0787\,{}^\circ$C
(a-ii) Error at $t=1$ min$0.1987\,{}^\circ$C
(b) Maximum deviation$a\tau=0.20\,{}^\circ$C (as $t\to\infty$)
(c) Ultimate time lag$\tau=0.2$ min