Question 4 of 7: Water Quality Measurement, BOD Test and Dissolved Air Flotation
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
National Exam 16-Chem-B2, Environmental Engineering — May 2018. 3 hours, Closed-Book Exam with
a candidate-prepared 8½×11" double-sided aid sheet. Any five (5) of the seven questions
constitute a complete paper (100 marks); all seven are solved below for completeness.
Reference texts: Metcalf & Eddy (Tchobanoglous, Burton, Stensel), Wastewater
Engineering: Treatment and Reuse, 4th ed.; Davis & Cornwell, Introduction to Environmental
Engineering, 5th ed.; Turner, Workbook of Atmospheric Dispersion Estimates, 2nd ed.;
Cooper & Alley, Air Pollution Control: A Design Approach, 4th ed.
Problem 4: Water Quality Measurement, BOD Test and Dissolved Air Flotation (20 marks)
Direct potentiometric measurement with a glass combination electrode/pH meter,
calibrated against certified buffer standards (e.g. pH 4, 7, 10) immediately before use; continuous online
probes are used for process control.
(b) Conductivity
Direct measurement with a conductivity (electrical resistivity) cell/meter,
calibrated against a certified KCl conductivity standard; conductivity is used as an indirect surrogate for
total dissolved solids (TDS ≈ conductivity × a site-specific empirical factor, typically
0.55–0.9).
(c) Toxicity
Measured indirectly via standardized whole-effluent toxicity (WET) bioassays
(e.g. Ceriodaphnia or fathead-minnow acute/chronic tests, or the Microtox® bioluminescence assay)
that report an LC50/EC50 or percent-effect endpoint, since no single chemical measurement captures the
combined/synergistic toxic effect of a real effluent's contaminant mixture.
(ii) BOD5 dilution test
Given.
Quantity
Value
Tertiary effluent sample volume
300 mL
Dilution water volume
200 mL
Total mixture volume
500 mL
Initial DO, DOi
7 mg/L
DO after 5 days, DO5
2.0 mg/L
DO after 20 days (stabilized), DO20
0.05 mg/L
Find. The 5-day CBOD (CBOD5) and the ultimate CBOD (L0) of the undiluted tertiary
effluent.
Approach. Apply the standard BOD dilution formula, scaling the bottle's DO depletion by
the reciprocal of the sample fraction P = Vsample/Vtotal (no seed correction given, so
none is applied); the stabilized 20-day reading is taken as the ultimate carbonaceous demand.
(a) 5-day CBOD of the undiluted effluent.
$$CBOD_5 = \frac{DO_i - DO_5}{P} = \frac{7 - 2.0}{0.60} = \boxed{8.33\ \text{mg/L}}$$
(b) Ultimate CBOD (L0), from the stabilized 20-day DO. Since the DO has stopped falling
by day 20, essentially the full carbonaceous demand has been exerted, so DOi−DO20
scaled the same way is the ultimate CBOD of the undiluted sample.
$$L_0 \approx \frac{DO_i - DO_{20}}{P} = \frac{7 - 0.05}{0.60} = \boxed{11.58\ \text{mg/L}}$$
Consistency check (not asked, verification only). Back-calculating the first-order rate
constant from CBOD5/L0 via $CBOD_5=L_0(1-e^{-k\cdot5})$ gives k ≈ 0.254 d-1, inside the
typical municipal-effluent range (0.1–0.4 d-1), confirming the two readings are mutually
consistent with first-order BOD kinetics.
Quantity
Value
Dilution fraction, P
0.60
(a) 5-day CBOD, CBOD5
8.33 mg/L
(b) Ultimate CBOD, L0
11.58 mg/L
(iii) Dissolved air flotation (DAF): main functions
The DAF unit sits between flocculation and filtration in the treatment train (rapid mix → floc tank
→ DAF tank → filtration), with a side-stream of clarified/filtered water pressurized through a
saturator and recycled back into the DAF tank as the air source:
Fig. 2a — Water treatment train: rapid mix → floc tank → DAF tank →
filtration, with recycle taken after DAF/filters, pressurized through a saturator, and re-injected into the
DAF tank.
Fig. 2b — DAF reactor, side-view cross-section: influent and recycle (with
dissolved air) enter the contact zone; bubble-floc agglomerates float to the surface and are skimmed as froth
in the separation zone; clarified effluent exits at the bottom.
Fig. 2c — DAF reactor, front-view cross-section: the air-distribution system
releases micro-bubbles uniformly across the full tank width so bubble–floc attachment is not confined
to one side of the reactor.
Clarification (solids/floc removal). The DAF tank replaces (or precedes) a
gravity-settling clarifier for light, poorly-settling floc — attaching micro-bubbles to the flocculated
solids lowers their effective density below water, so they float and are skimmed rather than needing to
settle.
Thickening of the removed solids. The skimmed froth is a concentrated (thickened) sludge
(typically several percent solids), reducing the downstream sludge-handling volume compared to the more
dilute underflow of a conventional gravity clarifier.
Pre-conditioning ahead of filtration. By removing the bulk of the floc load upstream, the
DAF stage protects the downstream granular-media filter from premature headloss build-up/breakthrough,
extending filter run length between backwashes.