NivaarExam PrepOfficial exam papers ↗

22-Elec-A6 Power Systems and Machines · December 2013

Question 1 of 6: Two-Wattmeter Method and Power-Factor Correction

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format: Professional Engineers Ontario — 07-Elec-A6 Power Systems and Machines, Fall 2013 (closed book, formula sheet supplied). Six questions of equal value; any five constitute a complete paper. All ac voltages/currents are rms; three-phase voltages are line-to-line unless noted. All six questions are solved below as a complete study resource.

Reference texts: S. J. Chapman, Electric Machinery Fundamentals, 5th ed. (McGraw-Hill); T. Wildi, Electrical Machines, Drives, and Power Systems, 6th ed. (Pearson); Fitzgerald, Kingsley & Umans, Electric Machinery, 6th ed.


Question 1: Two-Wattmeter Method and Power-Factor Correction (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. Three parallel 3-phase loads on a 440 V (line-to-line) system, measured by the two-wattmeter connection of Figure 1 (W1: current coil in line a, voltage coil a–c; W2: current coil in line b, voltage coil b–c; line c carries no current coil).

Given load data
LoadRatingP (kW)Q (kVAR, ind.)
A21.5 kW, 0.6 pf lag21.5028.67
B22 kVA, 11 kW ind.11.0019.05
C17.6 kVAR, 0.8 pf lag23.4717.60

Find. (a) the two wattmeter readings W1 and W2; (b) the per-phase capacitive reactance to raise the overall power factor to unity, and the two wattmeter readings after correction.

[Figure not reproduced: Figure 1 (redrawn): W1 current coil in line a , voltage coil a–c ; W2 current coil in line b , voltage coil b–c (line c is the common line). See the official exam paper.]

Approach. Resolve every load into real (P) and reactive (Q) power, sum to a system complex power, obtain the line current and overall angle, then apply the two-wattmeter identities for the Figure 1 connection (common line c, abc sequence): W1 = VLILcos(30°−θ), W2 = VLILcos(30°+θ). Unity correction supplies the total lagging vars with capacitors.

  1. Resolve each load into P and Q. For A, $S_A=P_A/\text{pf}=21.5/0.6=35.83\ \text{kVA}$, so $Q_A=\sqrt{S_A^2-P_A^2}=28.67\ \text{kVAR}$. For B, $Q_B=\sqrt{22^2-11^2}=\sqrt{363}=19.05\ \text{kVAR}$. For C, $\tan\theta_C=0.6/0.8=0.75$, so $P_C=Q_C/\tan\theta_C=17.6/0.75=23.47\ \text{kW}$. All are lagging (inductive), so the vars add.
  2. Sum to the system complex power. $$P_T=21.5+11+23.47=55.97\ \text{kW},\qquad Q_T=28.67+19.05+17.60=65.32\ \text{kVAR}$$ $$\boxed{S_T=\sqrt{P_T^2+Q_T^2}=86.02\ \text{kVA},\quad \theta=\tan^{-1}\!\frac{65.32}{55.97}=49.4^\circ\ (\text{pf}=0.651\ \text{lag})}$$
  3. Line current. For a balanced three-phase system $I_L=\dfrac{S_T}{\sqrt{3}\,V_L}=\dfrac{86.02\times10^3}{\sqrt3\,(440)}=112.9\ \text{A}.$
  4. Wattmeter readings (part a). In Figure 1, W1 measures $I_a$ against $V_{ac}$ and W2 measures $I_b$ against $V_{bc}$. With positive (abc) sequence and $V_{an}=V_\phi\angle0^\circ$: $V_{ac}=V_L\angle{-}30^\circ$, $I_a=I_L\angle{-}\theta$, and $V_{bc}=V_L\angle{-}90^\circ$, $I_b=I_L\angle({-}120^\circ-\theta)$, so $$W_1=V_L I_L\cos(\theta-30^\circ)=440(112.9)\cos(19.4^\circ)=46.84\ \text{kW}$$ $$W_2=V_L I_L\cos(30^\circ+\theta)=440(112.9)\cos(79.4^\circ)=9.13\ \text{kW}$$ $$\boxed{W_1=46.84\ \text{kW},\qquad W_2=9.13\ \text{kW}}$$ Check: $W_1+W_2=55.97\ \text{kW}=P_T$ ✓. The large split reflects the low 0.651 power factor. (If the supply sequence were acb, the two readings would swap meters; the pair of values is unchanged.)
  5. Capacitor sizing for unity pf (part b). To reach unity the bank must supply the entire lagging reactive power, $Q_C=65.32\ \text{kVAR}$, i.e. $21.77\ \text{kVAR}$ per phase. Taking the capacitors delta-connected across the 440 V lines (each capacitor sees $V_L$): $$X_C=\frac{V_L^2}{Q_{C,\text{ph}}}=\frac{440^2}{21.77\times10^3}=\boxed{8.89\ \Omega\ \text{per phase}}\quad\Big(C=\tfrac{1}{2\pi f X_C}=298\ \mu\text{F}\Big)$$
  6. Wattmeter readings after correction. At unity pf $\theta=0$ and $Q_T=0$, so the line current falls to $I_L'=\dfrac{P_T}{\sqrt3\,V_L}=73.4\ \text{A}$. Both meters now read equally: $$W_1'=W_2'=V_L I_L'\cos(30^\circ)=\tfrac{1}{2}P_T=\boxed{27.98\ \text{kW each}}$$
Check: "per phase" reactance depends on the bank connection. The boxed 8.89 Ω assumes a delta bank (standard for line-connected PFC, using the given 440 V directly). If the capacitors are instead wye-connected, each sees the phase voltage 254 V and $X_C=254^2/21.77\text{k}=2.96\ \Omega$ per phase. The kVAR, the corrected current and the wattmeter readings are identical either way.
Question 1 — results
QuantityValue
System complex power55.97 kW + j65.32 kVAR (86.02 kVA, pf 0.651 lag)
Line current (before)112.9 A
W1, W2 (before)46.84 kW, 9.13 kW
Correction capacitor (Δ)8.89 Ω/phase (298 µF); wye alt. 2.96 Ω
Line current (unity pf)73.4 A
W1, W2 (after)27.98 kW each
← Paper overview