22-Elec-A6 Power Systems and Machines · December 2015
Question 5 of 5: Synchronous Machines
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format: Professional Engineers Ontario / EGBC national exam
07-Elec-A6 Power Systems and Machines — Fall (December) 2015. Closed book;
formula sheet supplied. FIVE questions, all of equal value (20 marks each). All AC
voltages and currents are rms; three-phase quantities are line-to-line voltages and
total power unless stated otherwise.
Reference texts: S. J. Chapman, Electric Machinery
Fundamentals, 5th ed. (transformers Ch 2; DC machines Ch 8–9; induction motors
Ch 6; synchronous machines Ch 4–5); T. Wildi, Electrical Machines, Drives, and
Power Systems, 6th ed. (three-phase circuits, power-factor correction,
two-wattmeter method).
Part (a) — Effect of increasing excitation on an infinite bus
With the machine tied to an infinite bus, both terminal voltage \(V_\phi\) and
frequency are fixed, and the real power is set by the prime mover, not by the field. The
real power is \(P=\dfrac{3V_\phi E_a}{X_s}\sin\delta\); since \(P\) and \(V_\phi\) are
constant, raising the excitation increases \(|E_a|\), so \(\sin\delta\) (and hence the
power angle \(\delta\)) must decrease to keep \(P\) fixed. The extra excitation
therefore does not change the real power — it changes the reactive power: the
machine becomes over-excited and supplies lagging reactive power to the grid (it looks
capacitive to the system), and the armature current increases and becomes more lagging.
This is the well-known synchronous "V-curve" behaviour, and it is the basis of using an
over-excited synchronous machine as a source of vars (a synchronous condenser).
Part (b) — Generator on an infinite bus
Given. Six-pole, Y-connected synchronous machine, 208 V (L-L),
5500 VA, \(X_s=8\ \Omega\)/phase, \(R_a\approx0\); generating onto an infinite bus.
Given data — Question 5
Quantity
Value
Phase voltage \(V_\phi=208/\sqrt3\)
120.1 V
Rated apparent power \(S\)
5500 VA
Synchronous reactance \(X_s\)
8 Ω/phase
Rated line (= phase) current \(I_a=S/\sqrt3V_L\)
15.27 A
Poles / connection
6 / Y
Find. (i) excitation voltage \(E_a\) and power angle \(\delta\) at
rated kVA, 0.8 lag, and the phasor diagram; (ii) after a 20% rise in field at constant
\(P\): new \(I_a\), power factor and reactive power; (iii) the steady-state stability
limit (max power) at the original excitation, with the corresponding \(I_a\), power
factor and reactive power.
Phasor diagram for part (i): the internal
voltage \(E_a\) leads the terminal voltage \(V_\phi\) by the power angle \(\delta\);
\(jX_sI_a\) is perpendicular to the lagging armature current \(I_a\).
Approach. Use the round-rotor phasor equation
\(E_a=V_\phi+jX_sI_a\) for part (i). For part (ii), hold \(P\) fixed while \(|E_a|\)
rises 20%: get the new \(\delta\) from \(P=\dfrac{3V_\phi E_a}{X_s}\sin\delta\), then
recompute \(I_a=(E_a-V_\phi)/jX_s\). For part (iii), the steady-state stability limit is
\(\delta=90^\circ\) at the original \(|E_a|\).
Part (i): excitation voltage and power angle. The armature current
at rated kVA and 0.8 lag is \(I_a=15.27\angle{-36.87^\circ}\text{ A}\). Then
$$E_a=V_\phi+jX_sI_a=120.1+j8(15.27\angle{-36.87^\circ})
=193.4+j97.7=216.7\angle26.8^\circ\text{ V}.$$
So the excitation voltage is \(E_a=216.7\text{ V/phase}\) and the power angle is
\(\delta=26.8^\circ\).
Part (ii): new operating point after a 20% field increase. The
per-phase converted power is fixed at
\(P_\phi=V_\phi I_a\cos\theta=120.1(15.27)(0.8)=1467\text{ W}\). The new excitation is
\(E_a'=1.20(216.7)=260.0\text{ V}\), so
$$\sin\delta'=\frac{P_\phi X_s}{V_\phi E_a'}=\frac{1467(8)}{120.1(260.0)}=0.376
\;\Rightarrow\;\delta'=22.1^\circ.$$
The new armature current is
$$I_a'=\frac{E_a'-V_\phi}{jX_s}=\frac{260.0\angle22.1^\circ-120.1}{j8}
=19.4\angle{-51.1^\circ}\text{ A},$$
i.e. \(I_a'=19.4\text{ A}\) at power factor \(\cos51.1^\circ=0.629\) lagging. The
reactive power supplied is
$$Q=3V_\phi I_a'\sin\theta'=3(120.1)(19.4)(0.778)=5.44\text{ kvar (supplied).}$$
(The real power checks: \(3V_\phi I_a'\cos\theta'=4.40\text{ kW}\), unchanged.)
Part (iii): steady-state stability limit at the original field.
Restoring \(E_a=216.7\text{ V}\) and increasing the prime-mover power drives \(\delta\)
toward \(90^\circ\), where the power-angle characteristic peaks:
$$P_{max}=\frac{3V_\phi E_a}{X_s}=\frac{3(120.1)(216.7)}{8}=9.76\text{ kW}.$$
At \(\delta=90^\circ\), \(E_a=216.7\angle90^\circ\), so
$$I_a=\frac{E_a-V_\phi}{jX_s}=\frac{216.7\angle90^\circ-120.1}{j8}
=30.96\angle{+29.0^\circ}\text{ A}.$$
The current now leads the voltage: power factor \(\cos29.0^\circ=0.874\)
leading, and the machine absorbs reactive power
$$Q=3V_\phi I_a\sin\theta=3(120.1)(30.96)(-0.485)=-5.41\text{ kvar}$$
(i.e. it draws 5.41 kvar from the grid). Note the armature current 30.96 A is about
twice rated — the stability-limit condition is a ceiling, not a continuous rating.