NivaarExam PrepOfficial exam papers ↗

22-Elec-B7 Power Systems Engineering · December 2016

Question 7 of 7: Excitation Voltage and Transient Stability under a Sustained Fault

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Exams, December 2016 — 07-Elec-B7 Power Systems Engineering. Open-book, 3 hours duration. Seven problems are printed; any five constitute a complete paper, only the first five appearing in the answer book are marked, and all questions are of equal value (20 points each). All seven are solved in full below, because this set is a study resource rather than a timed sitting.

Reference texts. This exam code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation is his throughout: the “cantilever” transformer equivalent of Problem 3, the two-reaction salient-pole construction of Problem 2, the ABCD two-port of Problem 1 and the sequence-network fault reduction of Problem 6. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed. (ch. 3 transformers, ch. 4–5 transmission lines, ch. 6 power flow, ch. 7–9 faults and symmetrical components, ch. 11 transient stability); J. J. Grainger and W. D. Stevenson, Power System Analysis; and S. J. Chapman, Electric Machinery Fundamentals, 5th ed., for the machine and transformer chapters. Canadian practice references where grounding and protection are discussed: CSA C22.1 Canadian Electrical Code, Part I, CSA C22.2 and the IEEE C62 / IEEE 142 (Green Book) series on system grounding.

Check: four judgement calls carried through the solutions, all recorded here rather than hedged in the answers.

(i) Problem 1 does not state a frequency. Parts (c) and (d) need one, and the paper is a Canadian national exam, so 60 Hz is used throughout — consistent with the 60 Hz stated in Problems 3 and 7. At 50 Hz the capacitance and surge impedance are unchanged (they do not involve frequency) and only the propagation constant of part (d) rescales by 5/6.

(ii) Problem 2 prints “neglecting armature reaction”. Armature reaction is precisely what the direct- and quadrature-axis reactances represent, so the phrase is read as its standard counterpart, neglecting armature resistance — the only reading under which the two given reactances can be used at all.

(iii) Problem 6 prints a part label “c-” with no question text. The five parts that do carry text (a, b, d, e, f) are marked 4 points each and total the 20 points the paper allots to every problem, so nothing is missing from the assessment; the sequence networks that the empty label most plausibly asked for are drawn anyway.

(iv) Problem 5 gives no reactance between buses 2 and 3. Figure (3) confirms the topology: bus 3 hangs radially off bus 1 through the j0.12 pu line, and the only other tie is line 1–2.

Problem 7: Excitation Voltage and Transient Stability under a Sustained Fault (20 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantitySymbolValue
Generator transient reactance$X_d^{\prime}$0.15 pu
Transformer reactance$X_T$0.10 pu
Each transmission circuit$X_L$0.60 pu (two in parallel)
Real power delivered to bus 1$P_m$0.90 pu
Bus 1 voltage magnitude$|V_1|$1.05 pu
Infinite bus voltage$V_{\infty}$$1.0\angle 0^{\circ}$ pu
Fault location on circuit 2$\alpha$0.25 of the way from bus 1
Excitation held during the fault$E^{\prime}$1.14 pu

Find. The generator excitation voltage behind transient reactance in the pre-fault condition; and whether the machine retains synchronism when a bolted three-phase fault at the quarter point of one circuit is left on indefinitely.

Approach. Work backwards from the infinite bus. The two circuits in parallel fix the angle of bus 1 from the stated power transfer; the line current then follows, and pushing it through the machine and transformer reactance gives $E^{\prime}$. For part (b) the during-fault transfer reactance is obtained by a star–delta transform, and the equal-area criterion is applied — with the observation that a sustained fault admits only two power-angle curves, not three.

  1. Part (a) — combine the two circuits and find the angle of bus 1. The two 0.60 pu circuits in parallel present $X_L=0.60/2=0.30$ pu between bus 1 and the infinite bus. Since the network is lossless, the 0.9 pu delivered to bus 1 also arrives at the infinite bus, so $$P=\frac{\left|V_1\right|V_{\infty}}{X_L}\sin\delta_1\;\Longrightarrow\;\sin\delta_1=\frac{0.9(0.30)}{1.05(1.0)}=0.257143\;\Longrightarrow\;\delta_1=14.901^{\circ}$$ so $\mathbf{V}_1=1.05\angle 14.901^{\circ}=1.01469+j0.27000$ pu.
  2. Compute the line current. With the infinite bus as reference, $$\mathbf{I}=\frac{\mathbf{V}_1-\mathbf{V}_{\infty}}{jX_L}=\frac{\left(1.01469+j0.27000\right)-1.0}{j0.30}=\frac{0.01469+j0.27000}{j0.30}=0.9000-j0.04897\ \text{pu}$$ The real part is exactly 0.9000 pu, which is the arithmetic check that the angle was found correctly: with $V_{\infty}=1.0\angle 0^{\circ}$ the real part of the current is the power delivered.
  3. Push the current through the machine and transformer to reach the internal emf. The two reactances in series between the internal node and bus 1 total $X_d^{\prime}+X_T=0.15+0.10=0.25$ pu, so $$\mathbf{E}^{\prime}=\mathbf{V}_1+j\left(0.25\right)\mathbf{I}=\left(1.01469+j0.27000\right)+j0.25\left(0.9000-j0.04897\right)$$ $$=\left(1.01469+0.012243\right)+j\left(0.27000+0.225000\right)=1.02694+j0.49500$$ $$\boxed{\ \mathbf{E}^{\prime}=1.1400\angle 25.735^{\circ}\ \text{pu}\ }$$ which is the 1.14 pu the question hands back in part (b) — a deliberate consistency check built into the paper.
  4. Part (b) — establish the pre-fault power-angle curve and the initial angle. Referred to the internal emf, the total pre-fault reactance to the infinite bus is $0.25+0.30=0.55$ pu, so $$\begin{aligned}P_{\max,1}&=\frac{E^{\prime}V_{\infty}}{0.55}=\frac{1.14(1.0)}{0.55}=2.0727\ \text{pu}\\\delta_0&=\arcsin\!\frac{0.9}{2.0727}=25.735^{\circ}=0.44916\ \text{rad}\end{aligned}$$ reproducing the angle of $\mathbf{E}^{\prime}$ found in part (a), as it must.
  5. Reduce the faulted network with a star–delta transform. With a bolted three-phase fault at $\alpha=0.25$ along circuit 2, that circuit splits into $0.6(0.25)=0.15$ pu from bus 1 to the fault point F and $0.6(0.75)=0.45$ pu from F onward. Bus 1 is now the centre of a star whose three arms run to the internal emf ($X_a=0.25$), to the infinite bus through the healthy circuit ($X_b=0.60$) and to the fault ($X_c=0.15$). Converting to a delta, the branch that directly joins the emf to the infinite bus is $$X_{\text{transfer}}=X_a+X_b+\frac{X_aX_b}{X_c}=0.25+0.60+\frac{(0.25)(0.60)}{0.15}=0.85+1.00\;\Longrightarrow\;\boxed{\ X_{\text{transfer}}=1.85\ \text{pu}\ }$$ The other two delta branches terminate on the fault point, which is at zero potential, so they carry no transfer power and are discarded. Note how severe the location is: the shunt arm $X_c$ sits in the denominator, so the closer the fault is to bus 1 the smaller $X_c$ becomes and the larger the transfer reactance grows.
  6. Form the during-fault power-angle curve and compare it with the mechanical input. $$P_{\max,2}=\frac{E^{\prime}V_{\infty}}{X_{\text{transfer}}}=\frac{1.14(1.0)}{1.85}=0.6162\ \text{pu}$$ This is the decisive number. The mechanical input is $P_m=0.90$ pu, and the faulted network cannot transmit more than 0.6162 pu at any rotor angle: $$P_{\max,2}=0.6162<P_m=0.90$$
  7. Apply the equal-area criterion — and observe that it cannot be satisfied. A sustained fault means the fault is never cleared, so there are only two curves: the pre-fault curve, which fixes $\delta_0$, and the during-fault curve, on which the machine must find a new equilibrium. An equilibrium requires $P_{\max,2}\sin\delta=P_m$, that is $\sin\delta=0.90/0.6162=1.4605$, which has no solution. The accelerating power $P_a=P_m-P_{\max,2}\sin\delta$ is therefore strictly positive for every angle, the decelerating area $A_2$ available beyond $\delta_0$ is exactly zero, and no accelerating area $A_1$ however small can be balanced: $$A_1=\int_{\delta_0}^{\delta}\left(P_m-P_{\max,2}\sin\delta\right)\mathrm{d}\delta>0\quad\text{for all }\delta>\delta_0,\qquad A_{2,\max}=0$$ $$\boxed{\ \text{The system is UNSTABLE under sustained fault conditions.}\ }$$ The rotor accelerates monotonically, passes $180^{\circ}$ and pole-slips; the machine loses synchronism and must be tripped.
  8. State what this means for protection, and what would change the verdict. The conclusion is reached without integrating anything, and the test is worth remembering: for a sustained fault, $P_{\max,\text{fault}}\le P_m$ settles the question immediately. The engineering consequence is that stability here depends entirely on clearing the fault. Were the faulted circuit tripped out, the post-fault reactance would be $0.25+0.60=0.85$ pu, giving $P_{\max,3}=1.14/0.85=1.3412$ pu — comfortably above $P_m$ — so a critical clearing angle exists and the machine survives if the breakers are fast enough. That is precisely why transmission-line protection on generator outlet circuits is specified in cycles, not seconds.
0°30°60°90°120°150°180°0.50.91.41.9δ0P (pu)rotor angle δpre-faultduring fault (sustained)mechanical input
Figure 7 — Equal-area construction for the sustained fault. The during-fault curve (solid) lies entirely below the mechanical input line (dashed red) for every rotor angle, so the shaded accelerating area grows without limit and there is no decelerating area at all. The machine cannot recover: it is unstable.
QuantitySymbolResult
(a) Angle of bus 1$\delta_1$$14.901^{\circ}$
(a) Line current$\mathbf{I}$$0.9013\angle{-3.114^{\circ}}$ pu
(a) Excitation voltage$E^{\prime}$$1.1400\angle 25.735^{\circ}$ pu
(b) Pre-fault peak power$P_{\max,1}$2.0727 pu
(b) Initial rotor angle$\delta_0$$25.735^{\circ}$
(b) During-fault transfer reactance$X_{\text{transfer}}$1.85 pu
(b) During-fault peak power$P_{\max,2}$0.6162 pu
(b) Verdict—Unstable — $P_{\max,2}<P_m=0.9$ pu
Post-fault peak power if the circuit is tripped$P_{\max,3}$1.3412 pu (stable clearing possible)
Back to the paper →