22-Elec-B7 Power Systems Engineering · December 2018
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, December 2018 — 16-Elec-B7 Power Systems Engineering, 3 hours, open book, any non-communicating calculator permitted. The paper prints seven questions, headed “Problem 1” to “Problem 7”; the rubric states that any five questions constitute a complete paper and that all questions are of equal value. Every one of the seven is solved in full here, because the set is a study resource rather than a three-hour sitting. Sub-part point values are quoted as printed; note that the printed splits total 25 points on Problems 1, 2, 4, 5 and 6, 20 points on Problem 3, and Problem 7 carries no printed split at all — under the “equal value” rubric each question is worth one fifth of the paper regardless.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed., IEEE Press / Wiley — the reference text named in the Engineers Canada syllabus for this examination code, and the source of the “cantilever” transformer model used in Problem 3. Supporting texts: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. J. Grainger and W. D. Stevenson, Power System Analysis; S. J. Chapman, Electric Machinery Fundamentals, 5th ed. Canadian practice context (protection philosophy, grounding) follows CSA and IEEE C37 relaying practice as applied by Canadian transmission utilities.
Check — two places where the printed data are not internally consistent, and what was done about each.
(1) Problem 1. The pair A = 0.95∠2°, B = 195∠87.5° forces a shunt parameter with a large real part (Re C = 3.00 × 10−4 S). No real transmission line has a shunt conductance of that size — on a physical line C lands within about a degree of +90°. The consequence is a transmission efficiency of only 80.9 %, of which about 156 MW of the 236 MW loss is charged to that fictitious conductance. The arithmetic below is exactly what the printed constants give and is what the marker will be looking for; the physical caveat is stated so the low efficiency is not read as a slip.
(2) Problem 6. Table (2) lists the line negative-sequence reactance as 0.320 pu against a positive-sequence 0.30 pu. A transmission line is a static, symmetric element, so physically X− must equal X+. The printed 0.320 is used throughout (the paper governs). Taking 0.30 instead moves the answer to Problem 6(b) from 1.4169∠145.58° pu to 1.4212∠146.04° pu — a change of 0.3 %, so neither reading changes any conclusion.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (a) — how frequency acts on each loss mechanism. A transformer's losses divide into those that live in the core and those that live in the windings, and frequency touches them by entirely different routes.
Hysteresis loss follows the Steinmetz relation $P_h = k_h f B_{max}^{n}$ with the exponent $n$ between about 1.6 and 2.0. Taken alone that expression says the loss rises in direct proportion to frequency, but the qualifier matters: at a fixed applied voltage the peak flux density is set by Faraday's law, $B_{max} \propto V/(f N A)$, so raising the frequency at constant voltage lowers the flux density in the same proportion. The two effects fight, and the hysteresis loss actually falls roughly as $f^{-(n-1)}$, i.e. as $1/f^{0.6}$ to $1/f$. Raising frequency at constant volts per hertz instead holds $B_{max}$ fixed, and then the loss really does rise linearly with $f$.
Eddy-current loss in the core obeys $P_e = k_e f^{2} t^{2} B_{max}^{2}$, where $t$ is the lamination thickness. At constant applied voltage the $f^{2}$ and the $B_{max}^{2} \propto 1/f^{2}$ cancel exactly, so the eddy loss is essentially independent of frequency and depends only on the applied voltage and the lamination design. This is the reason a 50 Hz transformer operated at 60 Hz on the same voltage does not overheat its core — the hysteresis component actually drops and the eddy component is unchanged.
Winding (copper) loss is $I^{2}R$ and at first sight has no frequency term at all. It acquires one through skin effect and proximity effect: the a.c. resistance rises with the square root of frequency once the conductor dimension becomes comparable with the skin depth $\delta = \sqrt{2\rho/(\omega\mu)}$. At 50–60 Hz the skin depth in copper is about 9 mm, so the effect is negligible in small units but is real in large transformers with heavy conductors, which is why those windings are subdivided into transposed strands. Stray loss in the tank, clamps and core bolts, driven by leakage flux, also scales with roughly $f^{2}$ at fixed current.
The practical upshot for design is the reason aircraft and switch-mode power supplies use 400 Hz and higher: at fixed volts per hertz a higher frequency permits a proportionally smaller core, so the transformer shrinks dramatically — provided the lamination thickness (or a ferrite core) is reduced to keep the eddy loss in check.
Given.
| Quantity | Value |
|---|---|
| Rating, voltages, frequency | 25 kVA, 2200/220 V, 60 Hz, single-phase |
| Turns ratio $a = 2200/220$ | 10 |
| Series arm (HV referred) $R_{eq}$, $X_{eq}$ | $5.4\ \Omega$, $21\ \Omega$ |
| Magnetising reactance $X_m$ | $20\,000\ \Omega$ |
| Core-loss resistance $R_c$ | $37\,500\ \Omega$ |
Find. The secondary ammeter and wattmeter readings in a short-circuit test with 20 V on the secondary and the primary shorted; the primary ammeter and wattmeter readings in an open-circuit test with 2250 V on the primary; and the primary voltage when the transformer supplies 15 kVA at 220 V and 0.8 lagging.
Approach. The cantilever arrangement is the key to all three parts. Because the excitation branch is connected directly across the primary terminals rather than at an interior node, shorting the primary removes the excitation branch entirely from the circuit, and opening the secondary removes the series arm entirely. Each test therefore isolates one branch exactly, with no approximation.
| Quantity | Result |
|---|---|
| (b) Secondary ammeter, short-circuit test | 92.24 A |
| (b) Secondary wattmeter, short-circuit test | 459.4 W |
| (c) Primary ammeter, open-circuit test | 0.1275 A at $-61.93^\circ$ (pf 0.4706 lagging) |
| (c) Primary wattmeter, open-circuit test | 135.0 W |
| (d) Primary voltage at 15 kVA, 0.8 lagging | $2317.21\angle 2.287^\circ$ V (5.33 % regulation) |