NivaarExam PrepOfficial exam papers ↗

22-Elec-B7 Power Systems Engineering · December 2018

Question 6 of 7: Sequence Networks and a Double Line-to-Ground Fault

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Exams, December 2018 — 16-Elec-B7 Power Systems Engineering, 3 hours, open book, any non-communicating calculator permitted. The paper prints seven questions, headed “Problem 1” to “Problem 7”; the rubric states that any five questions constitute a complete paper and that all questions are of equal value. Every one of the seven is solved in full here, because the set is a study resource rather than a three-hour sitting. Sub-part point values are quoted as printed; note that the printed splits total 25 points on Problems 1, 2, 4, 5 and 6, 20 points on Problem 3, and Problem 7 carries no printed split at all — under the “equal value” rubric each question is worth one fifth of the paper regardless.

Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed., IEEE Press / Wiley — the reference text named in the Engineers Canada syllabus for this examination code, and the source of the “cantilever” transformer model used in Problem 3. Supporting texts: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. J. Grainger and W. D. Stevenson, Power System Analysis; S. J. Chapman, Electric Machinery Fundamentals, 5th ed. Canadian practice context (protection philosophy, grounding) follows CSA and IEEE C37 relaying practice as applied by Canadian transmission utilities.

Check — two places where the printed data are not internally consistent, and what was done about each.

(1) Problem 1. The pair A = 0.95∠2°, B = 195∠87.5° forces a shunt parameter with a large real part (Re C = 3.00 × 10−4 S). No real transmission line has a shunt conductance of that size — on a physical line C lands within about a degree of +90°. The consequence is a transmission efficiency of only 80.9 %, of which about 156 MW of the 236 MW loss is charged to that fictitious conductance. The arithmetic below is exactly what the printed constants give and is what the marker will be looking for; the physical caveat is stated so the low efficiency is not read as a slip.

(2) Problem 6. Table (2) lists the line negative-sequence reactance as 0.320 pu against a positive-sequence 0.30 pu. A transmission line is a static, symmetric element, so physically X− must equal X+. The printed 0.320 is used throughout (the paper governs). Taking 0.30 instead moves the answer to Problem 6(b) from 1.4169∠145.58° pu to 1.4212∠146.04° pu — a change of 0.3 %, so neither reading changes any conclusion.

Question 6: Sequence Networks and a Double Line-to-Ground Fault (25 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. The one-line diagram of Figure (4): generator $G_1$ (wye, solidly grounded) feeds the delta winding of transformer $T_1$, whose grounded-wye winding connects to bus 1 through a neutral switch S; bus 1 reaches bus 2 through line $L_1$ and bus 2 reaches bus 3 through line $L_2$; bus 3 connects to the grounded-wye winding of $T_2$, whose delta winding feeds generator $G_2$ (wye, grounded). Reactances as tabulated above; prefault voltage 1.0 pu; a double line-to-ground fault on phases B and C at bus 2.

Find. The three sequence networks including the switch, then the phase-B current in line $L_1$ with S closed and again with S open, and an interpretation of the difference.

1 2 3 Y Δ Y Y Δ Y G1 G2 T1 T2 L1 L2 S Both transformers present their DELTA to the machine, so neither generator reaches the zero-sequence network.
The one-line diagram of Figure (4) read as a circuit. The two winding symbols on each transformer are the load-bearing data in this question — both transformers present their DELTA to the machine.

Part (a) — constructing the three sequence networks. The positive- and negative-sequence networks have the same topology as the one-line diagram: each generator sits behind its own reactance, in series with its transformer, in series with the line reaching the fault point. The zero-sequence network is where the reading of the transformer winding symbols decides the answer.

A delta–grounded-wye transformer offers a path for zero-sequence current on its grounded-wye side only. Zero-sequence current entering that winding circulates in the delta and never appears on the machine side, so the delta bars each generator from the zero-sequence network entirely. Both transformers here carry their delta on the machine side, so both generators are cut out, and the tabulated generator zero-sequence reactance of 0.1 pu is a decoy that never enters any calculation. The only paths from the fault point to the zero-potential reference are the two transformer neutrals — and the $T_1$ neutral path exists only while switch S is closed.

Positive sequence j(0.20 + 0.25) = j0.45 j(0.20 + 0.25) = j0.45 L1: j0.30 L2: j0.30 bus 1 bus 3 bus 2 (fault) reference two equal 0.75 pu paths in parallel: X1 = 0.375 pu Negative sequence j(0.15 + 0.25) = j0.40 j(0.15 + 0.25) = j0.40 L1: j0.320 L2: j0.320 bus 1 bus 3 bus 2 (fault) reference two equal 0.72 pu paths in parallel: X2 = 0.360 pu Zero sequence T1 neutral: j0.25 T2 neutral: j0.25 L1: j0.30 L2: j0.30 bus 1 bus 3 bus 2 (fault) reference generators barred by the deltas; with S closed X0 = 0.275 pu S (closed)
The three sequence networks. In the positive and negative networks each side is a generator plus a transformer plus a line; in the zero-sequence network only the two transformer neutrals reach the reference, and the T1 branch is broken when S opens.

Approach. Reduce each sequence network to a single reactance seen from bus 2, apply the double line-to-ground connection (positive in series with the parallel combination of negative and zero), then divide each sequence current between the two symmetric halves of the network and recombine into phase B by the symmetrical-component synthesis.

  1. Part (b) — reduce the three sequence networks with S closed. Each side of the positive-sequence network presents generator plus transformer plus line, and the two sides are symmetric about the fault: $$X_1=\tfrac{1}{2}\left(0.20+0.25+0.30\right)=\tfrac{1}{2}(0.75)=0.375\ \text{pu}$$ The negative-sequence network is identical in shape with the negative-sequence data: $$X_2=\tfrac{1}{2}\left(0.15+0.25+0.320\right)=\tfrac{1}{2}(0.72)=0.360\ \text{pu}$$ In the zero-sequence network the generators are absent, so each side is only the transformer neutral in series with its line: $$X_0=\tfrac{1}{2}\left(0.25+0.30\right)=\tfrac{1}{2}(0.55)=0.275\ \text{pu}$$
  2. Apply the double line-to-ground connection. For a DLG fault the positive-sequence network drives the parallel combination of the negative- and zero-sequence networks. The parallel term is $$X_2\!\parallel\!X_0=\frac{(0.360)(0.275)}{0.360+0.275}=0.155906\ \text{pu}$$ so the positive-sequence current at the fault is $$\boxed{I_{a1}=\frac{1.0}{j(0.375+0.155906)}=1.88357\angle -90^\circ\ \text{pu}}$$
  3. Recover the sequence voltage and the remaining two sequence currents. All three sequence voltages are equal at a DLG fault: $$\begin{aligned}V_{a1} &= V_{a2} = V_{a0} = 1.0-I_{a1}(j0.375) \\ &= 1.0-0.706340 = 0.293660\ \text{pu}\end{aligned}$$ Each of the other two networks is then driven by that voltage: $$I_{a2}=\frac{-V_{a2}}{jX_2}=\frac{-0.293660}{j0.360}=0.815721\angle +90^\circ\ \text{pu}$$ $$I_{a0}=\frac{-V_{a0}}{jX_0}=\frac{-0.293660}{j0.275}=1.067853\angle +90^\circ\ \text{pu}$$ The check is that the three must sum to zero, because the healthy phase A carries no current in a B–C–ground fault: $-1.88357+0.81572+1.06785 = 0$ to nine decimal places. The total current into earth is $3I_{a0}=3.2036\angle 90^\circ$ pu.
  4. Divide each sequence current into line $L_1$. Line $L_1$ carries only the contribution flowing in from the $G_1$ side. Because the two halves of every sequence network are identical in this system, each sequence current splits exactly in half: $$\begin{aligned}I_1^{L1} &=0.941787\angle -90^\circ \\ I_2^{L1} &=0.407861\angle +90^\circ \\ I_0^{L1} &=0.533927\angle +90^\circ\ \text{pu}\end{aligned}$$ The zero-sequence share is present only because S is closed; that is the whole point of part (c).
  5. Synthesise the phase-B current in $L_1$. With $a = 1\angle 120^\circ$, the phase-B current is $$I_B=I_0+a^{2}I_1+aI_2$$ Term by term, $$\begin{aligned}a^{2}I_1 &= 0.941787\angle 150^\circ = -0.815611+j0.470894\\ aI_2 &= 0.407861\angle 210^\circ = -0.353218-j0.203931\\ I_0 &= 0.533927\angle 90^\circ = 0+j0.533927\end{aligned}$$ Summing, $$\boxed{I_B^{L1}=-1.168829+j0.800890=1.4169\angle 145.58^\circ\ \text{pu}}$$ Two free checks confirm it: phase C in $L_1$ comes out at the mirror value $1.4169\angle 34.42^\circ$ pu, and the two full-network phase currents sum to $I_B+I_C = 3I_{a0} = j3.2036$ pu exactly, as they must.
  6. Part (c) — reopen the switch and rebuild only the zero-sequence network. Opening S breaks the $T_1$ neutral connection, so the entire left-hand branch of the zero-sequence network disappears. The positive- and negative-sequence networks are untouched. The only surviving path from bus 2 to the reference is through $L_2$ and the $T_2$ neutral: $$X_0'=0.30+0.25=0.55\ \text{pu}$$ The zero-sequence reactance has therefore doubled. Repeating the connection, $$X_2\!\parallel\!X_0'=\frac{(0.360)(0.550)}{0.910}=0.217582\ \text{pu}$$ $$I_{a1}'=\frac{1.0}{j(0.375+0.217582)}=1.687529\angle -90^\circ\ \text{pu}$$ $$V_{a}'=1.0-(1.687529)(0.375)=0.367177\ \text{pu}$$ $$\begin{aligned}I_{a2}' &=1.019935\angle 90^\circ \\ I_{a0}' &=0.667594\angle 90^\circ\ \text{pu}\end{aligned}$$
  7. Recompute the phase-B current in $L_1$ — noting that its zero-sequence share is now zero. This is the step where the answer stops being a simple rescaling of part (b). With $T_1$'s neutral open there is no zero-sequence path through $L_1$ at all, so $I_0^{L1} = 0$; the whole of $I_{a0}'$ flows through $L_2$. The positive- and negative-sequence currents still split evenly: $$\begin{aligned}I_1^{L1} &=0.843764\angle -90^\circ \\ I_2^{L1} &=0.509968\angle +90^\circ\ \text{pu}\end{aligned}$$ $$\begin{aligned}a^{2}I_1 &= 0.843764\angle 150^\circ = -0.730721+j0.421882\\ aI_2 &= 0.509968\angle 210^\circ = -0.441645-j0.254984\end{aligned}$$ $$\boxed{I_B^{L1}=-1.172366+j0.166898=1.1842\angle 171.90^\circ\ \text{pu}}$$
  8. Interpret the effect of grounding the transformer. Opening the $T_1$ neutral reduces the phase-B current in line $L_1$ from 1.4169 pu to 1.1842 pu, a fall of 16.4 %, and reduces the total current into earth at the fault from $3I_{a0} = 3.2036$ pu to 2.0028 pu, a fall of 37.5 %. Grounding the transformer therefore increases ground-fault duty. It does so for a specific reason worth stating: the neutral connection adds a second zero-sequence path in parallel with the first, which lowers $X_0$, and because $X_0$ then falls below $X_1$ the earth-fault current is driven up rather than down.

    The engineering trade is the classical one. Solid grounding buys a large, unambiguous earth-fault current that protective relays detect quickly and selectively, and it clamps the healthy-phase voltage rise during an earth fault to about 1.4 times normal, which lets insulation and surge arresters be rated lower. The price is greater fault energy — more arc damage at the fault, more mechanical stress on the windings, and a higher step-and-touch-potential hazard around the station ground grid. Leaving the neutral open reduces the damage but leaves the earth-fault current small and hard to detect, and permits the healthy phases to rise to full line-to-line voltage. Canadian transmission practice at 230 kV and above is effectively grounded for exactly the reasons above; resistance grounding is reserved for industrial and distribution systems where limiting the damage matters more than the speed of detection.

QuantityS closedS open
Positive-sequence reactance $X_1$0.375 pu0.375 pu (unchanged)
Negative-sequence reactance $X_2$0.360 pu0.360 pu (unchanged)
Zero-sequence reactance $X_0$0.275 pu0.550 pu
$I_{a1}$ at the fault$1.8836\angle -90^\circ$ pu$1.6875\angle -90^\circ$ pu
$I_{a2}$ at the fault$0.8157\angle 90^\circ$ pu$1.0199\angle 90^\circ$ pu
$I_{a0}$ at the fault$1.0679\angle 90^\circ$ pu$0.6676\angle 90^\circ$ pu
Ground current $3I_{a0}$$3.2036\angle 90^\circ$ pu$2.0028\angle 90^\circ$ pu
Zero-sequence current in $L_1$$0.5339\angle 90^\circ$ pu0 (no path through $T_1$)
Phase-B current in line $L_1$$\mathbf{1.4169\angle 145.58^\circ}$ pu$\mathbf{1.1842\angle 171.90^\circ}$ pu
Three-phase fault at bus 2, for comparison$1/0.375 = 2.6667$ pu — less than the DLG value, the correct signature of $X_0 < X_1$