22-Elec-B7 Power Systems Engineering · May 2018
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams May 2018, 16-Elec-B7 Power Systems Engineering — open book, 3 hours, non-communicating calculator permitted. Seven problems of equal value; a complete paper (100 per cent) corresponds to 100 points scored out of a total possible 140 points, so every problem carries 20 points. Candidates are told to attempt all parts of all questions and to state any interpretive assumptions with the answer script.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, revised printing, IEEE Press / Wiley — the text whose notation (the cantilever transformer model, the sequence-network reduction, the two-curve equal-area construction) this paper follows throughout. J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th ed. — line parameters, bundling, power flow and symmetrical components. J. J. Grainger and W. D. Stevenson, Power System Analysis — fault analysis and network reduction. P. Kundur, Power System Stability and Control — the generator capability diagram and transient stability. S. J. Chapman, Electric Machinery Fundamentals, 5th ed. — transformer and synchronous-machine behaviour. For Canadian protection and insulation-coordination practice, the IEEE C37 relay standards and CSA C22.3 overhead-systems series apply.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (a) — a 50 Hz transformer operated at 60 Hz, load unchanged.
Everything follows from the EMF equation $V\approx4.44\,N\,f\,\phi_{max}$. If the same rated voltage is applied at a frequency twenty per cent higher, the peak core flux must fall in inverse proportion, to $50/60=0.833$ of its design value. That is the safe direction: the core moves further away from saturation, and none of the thermal or mechanical ratings of the winding are threatened. (The dangerous case is the reverse one, a 60 Hz transformer energised at 50 Hz, where the flux would rise by twenty per cent and drive the core hard into saturation.)
Reactive-power requirement. The magnetising reactance is proportional to frequency, $X_m=2\pi fL_m$, so at constant applied voltage the magnetising current falls as $V/f$, again to about eighty-three per cent, and the magnetising reactive power $V^{2}/X_m$ falls in the same proportion. Because the core is less saturated the incremental permeability is also a little higher, so the real reduction is slightly greater than the linear estimate. Working against this, the leakage reactance $X_{eq}$ is likewise proportional to frequency and therefore rises by twenty per cent, so the reactive power absorbed in the series path, $I^{2}X_{eq}$, increases by twenty per cent at unchanged load current. In a distribution transformer the magnetising branch dominates at light load and the leakage term dominates near full load, so the net change in reactive demand is a clear reduction at light load and roughly a wash at full load.
Losses and efficiency. Copper loss is unchanged, because the load and hence the current are unchanged. Core loss splits into two parts that behave differently. Hysteresis loss follows $P_h\propto fB_{max}^{n}$ with $n$ near 1.6 to 2.0; substituting $B_{max}\propto V/f$ gives $P_h\propto V^{n}f^{1-n}$, so at constant voltage it falls, by about seventeen per cent for $n=2$. Eddy-current loss follows $P_e\propto f^{2}B_{max}^{2}\propto V^{2}$ and is therefore essentially unchanged. Total core loss thus decreases and total loss decreases with it, so efficiency improves slightly — on a unit of the size treated in parts (b) to (d), by roughly a tenth of a percentage point.
Primary power factor and regulation. Two opposing effects again. The smaller exciting current removes lagging reactive current at the primary terminals, which improves the power factor; the larger leakage reactance adds lagging reactive absorption in the series arm, which worsens it, and also worsens voltage regulation on a lagging load because the $I X_{eq}\sin\phi$ term in the approximate regulation expression grows by twenty per cent. At light and medium load the exciting current dominates and the primary power factor improves; at heavy lagging load the leakage term wins and both the power factor and the regulation deteriorate marginally. A separate practical caution is that the transformer, if it carries cooling fans or an oil pump driven from an auxiliary supply, will see those motors run twenty per cent faster, which is usually beneficial for cooling.
Given. A 50 kVA, 2400/240 V, 60 Hz single-phase distribution transformer with all parameters referred to the high-voltage side, feeding a stated secondary load.
| Quantity | Symbol | Value |
|---|---|---|
| Rating | $S_{rated}$ | 50 kVA, 2400/240 V, 60 Hz, single phase |
| Turns ratio | $a$ | 2400/240 = 10 |
| Equivalent series resistance (HV side) | $R_{eq}$ | 1.5 $\Omega$ |
| Equivalent series reactance (HV side) | $X_{eq}$ | 2.0 $\Omega$ |
| Magnetising reactance (HV side) | $X_m$ | 4500 $\Omega$ |
| Core-loss resistance (HV side) | $R_c$ | 30 000 $\Omega$ |
| Secondary load | $S_{load}$ | 40 kVA at 0.8 power factor lagging |
| Receiving-end voltage | $V_r$ | 240 V (maintained) |
Find. The primary voltage and current, the active and reactive power drawn at the primary, and the efficiency and primary power factor of the transformer at this load.
[Figure not reproduced: Figure 3.1 — the cantilever equivalent circuit of Figure (1) of the examination paper, all parameters referred to the high-voltage side. See the official exam paper.]
Approach. In the cantilever model the entire excitation branch hangs across the primary terminals, so the load current passes through $R_{eq}+jX_{eq}$ alone. Working from the known secondary voltage outward, add the series drop to find $V_p$, then compute the excitation current from $V_p$ and add it to the referred load current. No iteration is required.
| Quantity | Symbol | Value |
|---|---|---|
| Referred load current | $I_s/a$ | $16.6667\,/\,{-36.8699^{\circ}}$ A |
| Primary voltage | $V_p$ | $2440.03\,/\,0.2740^{\circ}$ V |
| Excitation current | $I_{h+e}$ | $0.5483\,/\,{-81.195^{\circ}}$ A |
| Primary current | $I_p$ | $17.0632\,/\,{-38.1564^{\circ}}$ A |
| Active power input | $P_p$ | 32.6151 kW |
| Reactive power input | $Q_p$ | 25.8786 kVAr |
| Apparent power input | $|S_p|$ | 41.6347 kVA |
| Core loss / copper loss | $P_c$ / $P_{cu}$ | 198.46 W / 416.67 W |
| Efficiency | $\eta$ | 98.11 per cent |
| Primary power factor | $\cos\phi_p$ | 0.7834 lagging |