Question 7 of 7: Transient Stability under a Sustained Fault, by the Equal-Area Criterion
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams May 2018, 16-Elec-B7 Power Systems Engineering — open book, 3 hours, non-communicating calculator permitted. Seven problems of equal value; a complete paper (100 per cent) corresponds to 100 points scored out of a total possible 140 points, so every problem carries 20 points. Candidates are told to attempt all parts of all questions and to state any interpretive assumptions with the answer script.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, revised printing, IEEE Press / Wiley — the text whose notation (the cantilever transformer model, the sequence-network reduction, the two-curve equal-area construction) this paper follows throughout. J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and Design, 6th ed. — line parameters, bundling, power flow and symmetrical components. J. J. Grainger and W. D. Stevenson, Power System Analysis — fault analysis and network reduction. P. Kundur, Power System Stability and Control — the generator capability diagram and transient stability. S. J. Chapman, Electric Machinery Fundamentals, 5th ed. — transformer and synchronous-machine behaviour. For Canadian protection and insulation-coordination practice, the IEEE C37 relay standards and CSA C22.3 overhead-systems series apply.
Question 7: Transient Stability under a Sustained Fault, by the Equal-Area Criterion (20 points)
Given. A machine of internal EMF $E$ feeding an infinite bus of voltage $V$ through a transient reactance, one series line and two parallel lines, as drawn in Figure (5).
Given data for the stability study
Element
Symbol
Value
Machine internal EMF
$E$
1.20 pu
Infinite-bus voltage
$V$
1.00 pu
Machine transient reactance
$x_d'$
$j0.01$ pu
Line 1 (series)
$x_1$
$j0.02$ pu
Line 2 (parallel)
$x_2$
$j0.03$ pu
Line 3 (parallel, faulted)
$x_3$
$j0.03$ pu
Fault
F
bolted three-phase, mid-point of line 3, sustained
Mechanical input, case (a)
$P_{m}$
6.0 pu
Mechanical input, case (b)
$P_{m}$
8.0 pu
Find. The initial power angle in each case, and whether the machine retains synchronism if the fault is never cleared.
Figure 7.1 — the circuit of Figure (5) with the sustained three-phase fault at the mid-point of line 3.
Approach. Compute the pre-fault transfer reactance by series and parallel combination, take the initial angle from the pre-fault power-angle curve, then obtain the during-fault transfer reactance by a star-to-delta transformation about the faulted node and apply the equal-area criterion between the two curves only, since a sustained fault means there is no third, post-fault curve.
Pre-fault transfer reactance and power-angle curve. With both parallel lines healthy the reactance from the internal EMF to the infinite bus is $$\begin{aligned} X_{pre}&=x_d'+x_1+\frac{x_2x_3}{x_2+x_3}=0.01+0.02+\frac{(0.03)(0.03)}{0.06} \\ &=0.01+0.02+0.015=0.045\ \text{pu} \end{aligned}$$ so the pre-fault curve is $$P_{e}=\frac{EV}{X_{pre}}\sin\delta=\frac{(1.2)(1.0)}{0.045}\sin\delta=\boxed{26.667\sin\delta\ \text{pu}}$$ The system is very stiff — a total reactance of under five per cent means a pull-out power of nearly twenty-seven times base — which is why loads of 6 and 8 pu still correspond to small angles.
During-fault transfer reactance requires a star-to-delta transformation. A bolted three-phase fault holds the mid-point of line 3 at zero potential, so that point becomes a connection to the reference. Around the junction node where the two parallel lines separate there are now three arms: $a=x_d'+x_1=0.03$ back to the EMF, $b=x_2=0.03$ forward to the infinite bus, and $c=0.015$ down to the faulted point. Converting that star to a delta, the branch that joins the EMF to the infinite bus is $$X_{f}=\frac{ab+bc+ca}{c}=\frac{(0.03)(0.03)+(0.03)(0.015)+(0.015)(0.03)}{0.015}=\frac{0.0018}{0.015}$$ $$\boxed{X_{f}=0.12\ \text{pu}}\qquad P_{e,fault}=\frac{1.2}{0.12}\sin\delta=10.000\sin\delta\ \text{pu}$$ The other two delta branches run from each source to the reference; they carry current into the fault but transfer no real power between the two machines, so they play no part in the power-angle curve. Note that a series-parallel combination cannot produce this result — the shunt arm must land in the denominator, and that is exactly what makes a fault close to the sending end so much more severe than one far from it.
Part (a) — initial power angle at 6 pu. Before the fault the machine sits on the pre-fault curve at the angle that matches the mechanical input, $$\sin\delta_0=\frac{P_m}{26.667}=\frac{6.0}{26.667}=0.22500 \quad\Longrightarrow\quad \boxed{\delta_0=13.0029^{\circ}=0.226943\ \text{rad}}$$
Part (a) — does an equilibrium exist during the fault? The during-fault peak is 10.0 pu, comfortably above the mechanical input of 6.0 pu, so the faulted curve does cross the $P_m$ line and there is a new equilibrium angle $$\sin\delta_1=\frac{6.0}{10.0}=0.600 \quad\Longrightarrow\quad \delta_1=36.8699^{\circ}=0.643501\ \text{rad}$$ Had $P_{max,f}$ been at or below $P_m$ the machine would accelerate without limit and the answer would be “unstable” with no integration needed at all. Because the fault is sustained there is no third curve, so the limiting angle is read off the faulted curve: $\delta_{max}=180^{\circ}-\delta_1=143.1301^{\circ}=2.498092$ rad.
Part (a) — accelerating and decelerating areas. $$A_1=\int_{\delta_0}^{\delta_1}\left(P_m-P_{max,f}\sin\delta\right)d\delta=P_m(\delta_1-\delta_0)+P_{max,f}(\cos\delta_1-\cos\delta_0)$$ $$\begin{aligned} A_1&=6.0(0.643501-0.226943)+10.0(0.800000-0.974359) \\ &=2.499348-1.743587=0.75576 \end{aligned}$$ $$A_{2,max}=P_{max,f}(\cos\delta_1-\cos\delta_{max})-P_m(\delta_{max}-\delta_1)$$ $$\begin{aligned} A_{2,max}&=10.0(0.800000+0.800000)-6.0(1.854591) \\ &=16.000000-11.127543=4.87246 \end{aligned}$$ Both angle differences must be in radians; this is the one place in the calculation where working in degrees silently destroys the answer.
Part (a) — verdict. Since $A_{2,max}=4.8725$ greatly exceeds $A_1=0.7558$, $$\boxed{\text{the machine remains stable at }P_m=6.0\ \text{pu}}$$ with a margin of about six and a half to one in area. The rotor swings out from $13.00^{\circ}$, passes through the new equilibrium at $36.87^{\circ}$ and reaches a maximum angle where the areas balance — well short of the $143.13^{\circ}$ limit — then oscillates about $36.87^{\circ}$, settling there if any damping is present.
Part (b) — initial power angle at 8 pu. On the same pre-fault curve, $$\sin\delta_0=\frac{8.0}{26.667}=0.30000 \quad\Longrightarrow\quad \boxed{\delta_0=17.4576^{\circ}=0.304693\ \text{rad}}$$ and during the fault $$\begin{aligned} \sin\delta_1&=\frac{8.0}{10.0}=0.800 \\ \delta_1&=53.1301^{\circ}=0.927295\ \text{rad} \\ \delta_{max}&=126.8699^{\circ}=2.214297\ \text{rad} \end{aligned}$$
Part (b) — areas and verdict. $$\begin{aligned} A_1&=8.0(0.927295-0.304693)+10.0(0.600000-0.953939) \\ &=4.980820-3.539392=1.44143 \end{aligned}$$ $$\begin{aligned} A_{2,max}&=10.0(0.600000+0.600000)-8.0(2.214297-0.927295) \\ &=12.000000-10.296018=1.70398 \end{aligned}$$ $A_{2,max}$ still exceeds $A_1$, so $$\boxed{\text{the machine remains stable at }P_m=8.0\ \text{pu, but only just}}$$ The ratio has collapsed from 6.45 to 1.18. Raising the load by a third has consumed more than eighty per cent of the stability margin, and the rotor now swings to $108.6^{\circ}$ before the areas balance, against $63.6^{\circ}$ in case (a). That is deep into the region where any modelling optimism — neglected damping, a slightly larger fault reactance, governor lag — would change the verdict.
Locate the true limit, since the two cases straddle it so closely. Setting $A_1=A_{2,max}$ and solving $$P_m\left(\pi-\delta_1-\delta_0\right)=P_{max,f}\left(\cos\delta_0+\cos\delta_1\right)$$ with $\delta_0=\arcsin(P_m/26.667)$ and $\delta_1=\arcsin(P_m/10.0)$ gives a critical mechanical input of $$\boxed{P_{m,crit}=8.155\ \text{pu}}$$ So case (a) is safe by a wide margin, case (b) sits within two per cent of the sustained-fault stability limit, and any load above about 8.16 pu would lose synchronism if this fault were never cleared. In practice, of course, protection would clear a mid-line three-phase fault in three to five cycles, and the post-fault curve with line 3 removed, $$P_{e,post}=\frac{1.2}{0.06}\sin\delta=20.0\sin\delta$$ would restore a large stability margin at both loadings.
Figure 7.2 — equal-area construction for case (a), $P_m=6.0$ pu. The accelerating area A1 is far smaller than the largest decelerating area available on the faulted curve.
Figure 7.3 — equal-area construction for case (b), $P_m=8.0$ pu. The two areas are now nearly equal, and the critical loading is only 8.155 pu.
Final results — Question 7
Quantity
Symbol
Case (a), $P_m=6.0$ pu
Case (b), $P_m=8.0$ pu
Pre-fault transfer reactance
$X_{pre}$
$j0.045$ pu
$j0.045$ pu
Pre-fault peak power
$P_{max,pre}$
26.667 pu
26.667 pu
During-fault transfer reactance
$X_{f}$
$j0.12$ pu
$j0.12$ pu
During-fault peak power
$P_{max,f}$
10.000 pu
10.000 pu
Initial power angle
$\delta_0$
$13.0029^{\circ}$
$17.4576^{\circ}$
During-fault equilibrium angle
$\delta_1$
$36.8699^{\circ}$
$53.1301^{\circ}$
Limiting angle on the faulted curve
$\delta_{max}$
$143.1301^{\circ}$
$126.8699^{\circ}$
Accelerating area
$A_1$
0.75576 pu-rad
1.44143 pu-rad
Maximum decelerating area
$A_{2,max}$
4.87246 pu-rad
1.70398 pu-rad
Area margin
$A_{2,max}/A_1$
6.45
1.18
Verdict
—
stable
stable, marginally
Critical sustained-fault loading
$P_{m,crit}$
8.155 pu
8.155 pu
Check: the machine transient reactance is read from Figure (5) as the $j0.01$ pu element in series with the source E, and lines 2 and 3 are taken as the two parallel circuits between the junction node and the infinite bus, exactly as drawn. Damping and governor action are neglected, the mechanical input is constant during the swing, and $E$ is held constant behind the transient reactance — the standard classical-model assumptions under which the equal-area criterion is valid. Because the fault is stated to be sustained, only two power-angle curves exist and $\delta_{max}$ is read from the faulted curve; if the fault were cleared by opening line 3 a third curve would apply and a critical clearing angle, not a stability verdict, would be the question.