22-Mec-B2 Environmental Control in Buildings · December 2014
Question 2 of 8: Winter plant with heating coil and steam humidifier
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of
Ontario / Engineers Canada annual examination, 07-Mec-B2 Environmental Control
in Buildings, December 2014. Three hours, open book, any non-communicating
calculator. Eight problems of 20 points each; candidates are required to solve
five. ASHRAE psychrometric charts (SI and IP) and an HFC-134a
pressure-enthalpy diagram are attached to the paper. All eight problems are
solved here.
Reference texts.
ASHRAE, Handbook — Fundamentals (Ch. 1 Psychrometrics, Ch. 16
Ventilation and Infiltration, Ch. 18 Nonresidential Cooling and Heating Load
Calculations, Ch. 19 Energy Estimating, Ch. 21 Duct Design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning:
Analysis and Design, 6th ed., Wiley.
W. P. Jones, Air Conditioning Engineering, 5th ed., Butterworth-Heinemann.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed., McGraw-Hill.
Carrier Air Conditioning Company, Handbook of Air Conditioning System
Design, Part 1 (the ESHF / apparatus-dew-point method used in Problem 1).
CSA B52 Mechanical Refrigeration Code; Canada's Ozone-depleting
Substances and Halocarbon Alternatives Regulations (SOR/2016-137); National
Building Code of Canada (vapour and air barriers).
Reading the numbers. Chart properties here are
computed from the ASHRAE psychrometric formulations rather than scaled off the
printed chart, so a candidate working graphically should expect agreement to about
the width of a pencil line — roughly ±0.3 °F on a dew point and
±1 % on a humidity ratio.
Question 2: Winter plant with heating coil and steam humidifier (20 points)
Given. A once-through-plus-recirculation winter air-handling unit serving a single space whose load, state and supply air rate are all specified.
Given data — Problem 2
Quantity
Symbol
Value
Space heating load
$q_t$
30 kW
Sensible heat ratio
SHR
0.60
Space state
$t_r$ / RH
$21^\circ\text{C}$ DB / 50 % RH
Outdoor state
$t_o$ / RH
$10^\circ\text{C}$ DB / 10 % RH
Outdoor-air fraction (dry-air mass)
$f_o$
0.40
Supply air rate
$\dot m$
7,000 kg/hr
Humidifier steam
$t_g$ / $h_g$
$120^\circ\text{C}$ saturated, 2,706 kJ/kg
Find. A plant schematic and the corresponding chart cycle with every state point identified, then the heating-coil duty and the humidifier moisture rate.
Problem 2 (a) and (c) — plant schematic. Outdoor air and return air mix ahead of the filter (state 1); the heating coil raises the dry-bulb temperature at constant humidity ratio (state 2); the fan adds a small amount of heat (state 3); the steam humidifier adds moisture at essentially constant dry-bulb temperature (state 4), and the air is delivered to the space as state 5.
Problem 2 (b) and (c) — the same cycle on the SI psychrometric chart. The mixing line runs from O to R through state 1; the coil process 1→2 is horizontal (sensible heating); the humidification 2→5 is very nearly vertical because saturated steam at $120^\circ\text{C}$ enters at close to the air's own dry-bulb enthalpy per unit moisture; and the room process 5→R has the slope set by SHR = 0.60.
Approach. Convert the load and the supply rate into the required supply state, mix outdoor and return air to fix the coil entering state, obtain the moisture addition from the humidity-ratio difference across the humidifier, and back out the coil leaving enthalpy from an energy balance on the humidifier — the coil duty is then the enthalpy rise from the mixed state to that leaving state.
Reduce the given data to rates. The dry-air mass flow is $\dot m = 7{,}000/3{,}600 = 1.944\ \text{kg}/\text{s}$, and the load splits as $q_s = 0.60(30) = 18.0\ \text{kW}$ sensible and $q_l = 0.40(30) = 12.0\ \text{kW}$ latent. Because this is a heating load, the supply air must be both warmer and wetter than the room.
Fix the room and outdoor states. At $21^\circ\text{C}$ and 50 % RH, $W_r = 0.00773\ \text{kg}/\text{kg}$; at $10^\circ\text{C}$ and 10 % RH the outdoor air is extremely dry, $W_o = 0.00076\ \text{kg}/\text{kg}$. That dryness is what makes the humidifier necessary.
Supply state (point 5). The supply air gives up its sensible heat and its moisture to the space, so $$t_5 = t_r + \frac{q_s}{\dot m\,c_p} = 21 + \frac{18.0}{1.944(1.0204)} = 30.1^\circ\text{C}, \qquad W_5 = W_r + \frac{q_l}{\dot m\,h_{fg}} = 0.00773 + \frac{12.0}{1.944(2501)} = 0.01020\ \text{kg}/\text{kg}$$ giving $h_5 = 56.33\ \text{kJ}/\text{kg}$.
(c) Mixed air (point 1). Mixing on a dry-air mass basis, $$t_1 = 0.40(10)+0.60(21) = 16.6^\circ\text{C}, \qquad W_1 = 0.40(0.00076)+0.60(0.00773) = 0.00494\ \text{kg}/\text{kg}$$ so $h_1 = 29.21\ \text{kJ}/\text{kg}$ and the mixed air stands at about 42 % RH.
(f) Moisture addition by the humidifier. Only the humidifier changes the humidity ratio, and it must carry the air from $W_1$ to $W_5$: $$\dot m_w = \dot m\,(W_5-W_1) = 1.944\,(0.01020-0.00494) = 0.01022\ \text{kg}/\text{s} = \boxed{36.8\ \text{kg}/\text{hr}}$$
State leaving the heating coil (point 2). The humidifier adds steam carrying $h_g = 2{,}706\ \text{kJ}/\text{kg}$, so an energy balance across it gives $h_2 = h_5 - (W_5-W_1)h_g = 56.33 - 0.00526(2706) = 42.10\ \text{kJ}/\text{kg}$ at the unchanged humidity ratio $W_1$, which is $t_2 = 29.3^\circ\text{C}$. The humidifier therefore raises the dry-bulb temperature by less than one degree — steam humidification is very nearly a vertical line on the chart.
(e) Heating-coil duty. The coil carries the air from state 1 to state 2 at constant humidity ratio, $$q_{\mathrm{coil}} = \dot m\,(h_2-h_1) = 1.944\,(42.10-29.21) = \boxed{25.1\ \text{kW}}$$
Check the whole plant against the room load. The supply air delivers $\dot m (h_5 - h_r) = 1.944(56.33-40.76) = 30.3\ \text{kW}$ to the space against the stated 30 kW — agreement to about 1 %, which is the expected residual from reading chart properties. The coil duty plus the steam enthalpy, $25.1 + 27.7 = 52.8\ \text{kW}$, exceeds the room load because the plant is also warming and wetting 40 % outdoor air from $10^\circ\text{C}$ and 10 % RH.
Note on the lettering. The examination paper labels this problem's parts a, b, c, e, f — there is no part (d) in the printed paper. The five printed parts are answered as printed.
First, the coil duty (25.1 kW) is smaller than the space load (30 kW) even though the plant also conditions outdoor air, because the humidifier's steam carries in roughly 28 kW of enthalpy of its own; a system using an adiabatic washer instead would need a much larger coil, since the evaporating water would take its latent heat out of the air stream. Second, the supply temperature of 30.1°C is high for a ceiling-diffuser system and would stratify in a tall space, so on a real project this would prompt either a higher supply air rate or perimeter heating — the arithmetic is only the beginning of the design decision.