Question 6 of 7: Sealing fault – distance to fault and test-duration validity
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
EGBC National Exam — Petroleum Engineering, 2014-Dec. 3 hours, closed book. This sitting's own cover page reads “98-Pet-B5, Well Testing,” not Reservoir Mechanics, and every question is pressure-transient/well-test analysis (radial diffusivity, drawdown/buildup, double-porosity, sealing-fault, interference). NOTES item 4/5 state that five (5) questions constitute a complete exam and only the first five as they appear are marked; all seven questions on the paper are solved in full below. Three of the seven questions (Q3, Q4, Q6) are chart-reading questions built around semilog/log-log plots with no printed data table — every plotted value used below was read from the printed figure and is flagged check where it feeds a boxed result.
Reference texts: Lee, J., Well Testing, SPE Textbook Series Vol. 1 (diffusivity equation, type curves, radius of investigation); Earlougher, R.C., Advances in Well Test Analysis, SPE Monograph Vol. 5 (Horner analysis, superposition in time, interference and reservoir-limit tests); Bourdet, D., Well Test Analysis: The Use of Advanced Interpretation Models, Elsevier (double-porosity/Warren–Root model, sealing faults); Warren, J.E. & Root, P.J., “The Behavior of Naturally Fractured Reservoirs,” SPE Journal, 1963.
Question 6: Sealing fault – distance to fault and test-duration validity (20 marks)
Find. Distance to the sealing fault, and whether the test ran long enough to reliably confirm it.
Approach. A sealing fault behaves, by the method of images, like a second (image) well starting to produce once the transient reaches it – which doubles the apparent semilog slope at late shut-in time. Fit the true (early) and doubled (late) slopes, use the observed time of doubling to back out the fault distance $L$, then compare the theoretical time for doubling (computed from that same $L$) against how long the test was actually run.
Fig. 5 – Horner buildup plot (digitized markers, with the fitted true and doubled-slope lines). Because $\Delta t$ increases toward the right (Horner ratio $\to1$), the LEFT portion (large Horner ratio, small $\Delta t$) is the true, fault-undisturbed early-time slope, and the RIGHT portion (small Horner ratio, large $\Delta t$) is the doubled, fault-affected late-time slope.
Fit the true (early) and doubled (late) slopes. A least-squares changepoint search across the chart data locates the break at Horner ratio $\approx14{,}500$, with $$m_1\approx4.94\ \text{psi/cycle (true, undisturbed)},\qquad m_2\approx8.92\ \text{psi/cycle (after the fault is felt)}$$ the ratio $m_2/m_1\approx1.8$ is close to the theoretical 2 (the residual gap is ordinary chart-reading scatter), confirming the fault interpretation. (Check: both slopes read from the printed chart.)
Permeability from the true (undisturbed) slope.
$$k=\frac{162.6\,q\mu B_o}{m_1h}=\frac{162.6(500)(1)(1.2)}{(4.94)(50)}$$
$$\boxed{k\approx 395\ \text{mD}}$$
Distance to the fault. The break occurs at Horner ratio $\approx14{,}531$, i.e. $\Delta t^*=t_p/(14{,}531-1)\approx0.00688$ hr. Substituting into the formula sheet's distance-to-fault relation,
$$L=\sqrt{\frac{0.000148\,k\,\Delta t^*}{\phi\mu c_t}}=\sqrt{\frac{0.000148(395)(0.00688)}{(0.1)(1)(1\times10^{-6})}}$$
$$\boxed{L\approx 63\ \text{ft}}$$
Theoretical time for the slope to double, and test-duration check. Using that same $L$ in the formula sheet's companion relation for the time the slope takes to double,
$$\Delta t_{theory}=\frac{3.8\times10^5\,\phi\mu c_t L^2}{k}=\frac{3.8\times10^5(0.1)(1)(1\times10^{-6})(63)^2}{395}\approx0.39\ \text{hr}$$
The test's longest reliably digitized shut-in point sits at Horner ratio $\approx64$, giving $\Delta t_{test}=t_p/(64-1)\approx1.6$ hr already comfortably run; the plot's visible data extend further still, toward a Horner ratio near 10 (i.e. $\Delta t\approx t_p/(10-1)\approx11.1$ hr). Either way,
$$\Delta t_{theory}\ (0.39\text{ hr}) \ll \Delta t_{test}\ (\text{several hours})$$
so the buildup was run well beyond the time theoretically required for the doubled slope to appear – the test duration is adequate, and the observed slope-doubling is a reliable confirmation of the fault, not a premature reading.