Question 3 of 7: Single-phase transformer: parameters from a load test, and input power from a known impedance
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2016 — 07-Elec-B7 Power Systems Engineering. Open-book, 3 hours duration. Seven problems are printed; any five constitute a complete paper, only the first five appearing in the answer book are marked, and all questions are of equal value (20 points each). All seven are solved in full below, because this set is a study resource rather than a timed sitting.
Reference texts. The syllabus for this code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation used throughout (the ABCD two-port and its equivalent pi, the two-reaction salient-pole construction, the sequence-network fault reduction) is his, and the phrase “all power formulae in the text” in Problem 1 refers to that book. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed. (ch. 3 transformers, ch. 5 transmission lines, ch. 6 power flow, ch. 7–9 faults and symmetrical components, ch. 11 transient stability); J. J. Grainger and W. D. Stevenson, Power System Analysis; and S. J. Chapman, Electric Machinery Fundamentals, 5th ed., for the machine and transformer chapters. Canadian practice references where grounding and protection are discussed: CSA C22.1 Canadian Electrical Code, Part I, CSA C22.3 No. 1 for overhead systems, and IEEE C37 series for protective relaying.
Check: four data points read off the printed figures. (i) In Figure (2) of Problem 4 the three branch reactances are j0.25, j0.20 and j0.10 pu, with bus 4 hanging off bus 2 through the j0.10 branch — the topology is taken from the drawing. (ii) Figure (3) of Problem 5 shows three sources, not two: generators at bus 1 and bus 4 and a third machine below bus 5. The sentence “the voltage at both sources is 1 p.u.” is taken to mean all sources are at 1.0 pu, which is the only reading that lets the network be solved. (iii) In Figure (4-a) of Problem 6, transformer T2 carries its delta on the generator side and T1 carries its delta on the motor side; motor 1 is an ungrounded wye and motor 2 is grounded through a reactor. Those four winding connections, not the reactance values, decide the answer. (iv) Problem 7 gives the switching angles in radians (1.2, 1.25 and 1.9 rad).
Check: Problem 3(a) as printed is over-determined and internally inconsistent. Rated kVA, the load power factor, the efficiency and the primary voltage are four data for two unknowns, and at 0.85 power factor lagging no positive series reactance satisfies them all. The inconsistency is quantified and resolved inside the answer rather than hidden.
Problem 3 — Single-phase transformer: parameters from a load test, and input power from a known impedance (20 points)
Given. Two independent single-phase transformer problems on the same 2300/230 V frame (turns ratio $a = 10$), the no-load branch neglected throughout so that the equivalent circuit is the series arm $R_{eq} + jX_{eq}$ alone.
Part
Quantity
Value
(a)
Rating
500 kVA, 2300/230 V, single phase
(a)
Load
full rated kVA at 0.85 pf lagging, rated secondary voltage 230 V
(a)
Primary voltage magnitude
2400 V
(a)
Efficiency
0.93
(b)
Series impedance referred to HV
$Z = 0.25 + j0.4\ \Omega$
(b)
Load
400 kVA at 0.85 pf lagging
(b)
Receiving-end voltage
225 V
Find. (a) $R_{eq}$ and $X_{eq}$ referred to the high-voltage side; (b) the active power drawn at the primary terminals.
Figure 4 — the equivalent circuit used for both parts: everything referred to the high-voltage side, with the magnetising branch (shown greyed) omitted as the question directs.
Part (a) — parameters from the loading test
Approach. The efficiency fixes the total copper loss and hence $R_{eq}$ directly; the primary-voltage magnitude is then supposed to fix $X_{eq}$ through the phasor equation $V_1 = V_2^{\prime} + I(R_{eq}+jX_{eq})$. That second step is where the printed data fail, and the answer says so explicitly rather than forcing a number.
Part (a) — convert the rating into an output power and a current. At full rated kVA and 0.85 power factor the delivered real power is $P_{out}=500\,\text{kVA}\times 0.85=425.0\ \text{kW}$, and the current, referred to the high-voltage side, is $$|I|=\frac{S}{V_1^{rated}}=\frac{500\,000}{2300}=217.391\ \text{A}$$ (the same current referred to the low-voltage side is 2173.9 A, ten times larger, and either frame gives the same per-unit answer).
Turn the efficiency into a copper loss. With the no-load branch neglected there is no core loss, so every watt of loss is $I^{2}R_{eq}$: $$\begin{aligned} P_{in} &= \frac{P_{out}}{\eta}=\frac{425\,000}{0.93}=456989.2\ \text{W} \\ P_{loss} &= P_{in}-P_{out}=31989.2\ \text{W} \end{aligned}$$
Recover the equivalent resistance. Dividing the loss by the square of the referred current, $$R_{eq}=\frac{P_{loss}}{|I|^{2}}=\frac{31989.2}{(217.391)^{2}}=\boxed{0.6769\ \Omega\ \text{(HV side)}}$$ On the transformer base $Z_{base}=2300^{2}/500\,000=10.580\ \Omega$ this is $0.0640$ pu, i.e. 6.4 per cent — an implausibly resistive transformer, which is the first hint that the stated efficiency is not that of a real 500 kVA unit. Referred to the low-voltage side the same resistance is $R_{eq}/a^{2}=0.006769\ \Omega$.
Set up the phasor equation for the reactance. Taking the referred secondary voltage as reference, $V_2^{\prime}=2300\angle 0^{\circ}$ V and $I=217.391\angle -31.788^{\circ}=184.783-j114.518$ A, the sending-end magnitude must satisfy $$\left|2300+(184.783-j114.518)(R_{eq}+jX_{eq})\right|=2400\ \text{V}$$ which, with $R_{eq}$ now known, is one quadratic in $X_{eq}$.
Solve it — and find no admissible root. Expanding gives $47259.0X^{2}+526782.7X+127011.9=0$, whose roots are $X_{eq}=-0.2466\ \Omega$ and $X_{eq}=-10.9002\ \Omega$. Both are negative, i.e. capacitive, and a transformer leakage reactance cannot be. The reason is visible without the algebra: with $X_{eq}=0$ the resistive drop alone already gives $$|V_1|=\left|2300+(184.783-j114.518)(0.6769)\right|=2426.3\ \text{V}$$ so no non-negative reactance can bring the primary down to the stated 2400 V.
Diagnose the inconsistency and state the defensible answer. The paper supplies four data — rated kVA, power factor, efficiency and primary voltage — for two unknowns, and at a lagging power factor they cannot all hold. Two of the three usable pairs give a clean answer, and both are reported: (i) trusting the efficiency, $R_{eq}=0.6769\ \Omega$ and the smallest admissible reactance is $X_{eq}\to 0$, for which the primary would have to be $2426.3$ V rather than 2400 V; (ii) keeping every printed number but reading the power factor as 0.85 leading, the same quadratic has the positive root $X_{eq}=0.2466\ \Omega$ and both the 0.93 efficiency and the 2400 V primary are satisfied exactly. Reading (i) is the one to submit, because it changes none of the printed words; reading (ii) is quoted so that a marker working from the setter’s own arithmetic is served.
Check: the exam-day move. An efficiency of 0.93 on a 500 kVA transformer implies 32 kW of copper loss and a 6.4 per cent resistance; real units of this size run at 98–99 per cent with resistances near 1 per cent. In an open-book examination the correct response is to compute $R_{eq}$ from the efficiency, show in two lines that the 2400 V datum then demands a capacitive reactance, and state the assumption under which you proceed — exactly as the paper’s own Note 1 invites. Marks are awarded for the method and for recognising the contradiction, not for inventing a number.
Part (b) — input power from a known series impedance
Approach. Refer the load to the high-voltage side, find the current, add the copper loss to the delivered real power. No iteration and no assumption about the primary voltage is needed, because the receiving-end voltage and the load are both fixed.
Part (b) — refer the receiving end to the high-voltage side. With $a = 2300/230 = 10$, the 225 V secondary appears on the primary side as $$V_2^{\prime}=aV_2=10\times 225=2250\ \text{V}$$ The apparent power is unchanged by referral, so $S=400$ kVA still.
Find the load current in the referred frame. $$|I|=\frac{S}{V_2^{\prime}}=\frac{400\,000}{2250}=177.7778\ \text{A}$$ at an angle of $-31.788^{\circ}$ to $V_2^{\prime}$, the 0.85 lagging load angle.
Compute the copper loss in the series arm. Only the resistive part of $Z$ dissipates: $$P_{loss}=|I|^{2}R=(177.7778)^{2}(0.25)=7901.2\ \text{W}$$
Add it to the delivered power. The load takes $P_{out}=400\,000\times 0.85=340000$ W, so $$\boxed{P_{in}=P_{out}+P_{loss}=340.0+7.901=347.90\ \text{kW}}$$
Confirm the answer the long way. The sending-end phasor is $V_1=V_2^{\prime}+IZ=2325.2+j37.0$ V, that is $2325.5\angle 0.9124^{\circ}$ V, and $\operatorname{Re}\{V_1I^{*}\}=347901.2$ W — the same figure by an independent route. The implied efficiency of this loading is $97.73$ per cent, and the reactive input is $223.36$ kvar.
Problem 3 — final results
Quantity
Symbol
Result
(a) copper loss at rated load
$P_{loss}$
31.99 kW
(a) equivalent resistance, HV side
$R_{eq}$
0.6769 Ω (0.0640 pu)
(a) equivalent resistance, LV side
$R_{eq}/a^{2}$
0.006769 Ω
(a) equivalent reactance — efficiency trusted
$X_{eq}$
no admissible root; $X_{eq}\to 0$, which implies $|V_1| = 2426.3$ V
(a) equivalent reactance — all data kept, pf read as leading