22-Elec-B7 Power Systems Engineering · May 2016
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, May 2016 — 07-Elec-B7 Power Systems Engineering. Open-book, 3 hours duration. Seven problems are printed; any five constitute a complete paper, only the first five appearing in the answer book are marked, and all questions are of equal value (20 points each). All seven are solved in full below, because this set is a study resource rather than a timed sitting.
Reference texts. The syllabus for this code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation used throughout (the ABCD two-port and its equivalent pi, the two-reaction salient-pole construction, the sequence-network fault reduction) is his, and the phrase “all power formulae in the text” in Problem 1 refers to that book. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed. (ch. 3 transformers, ch. 5 transmission lines, ch. 6 power flow, ch. 7–9 faults and symmetrical components, ch. 11 transient stability); J. J. Grainger and W. D. Stevenson, Power System Analysis; and S. J. Chapman, Electric Machinery Fundamentals, 5th ed., for the machine and transformer chapters. Canadian practice references where grounding and protection are discussed: CSA C22.1 Canadian Electrical Code, Part I, CSA C22.3 No. 1 for overhead systems, and IEEE C37 series for protective relaying.
Check: four data points read off the printed figures. (i) In Figure (2) of Problem 4 the three branch reactances are j0.25, j0.20 and j0.10 pu, with bus 4 hanging off bus 2 through the j0.10 branch — the topology is taken from the drawing. (ii) Figure (3) of Problem 5 shows three sources, not two: generators at bus 1 and bus 4 and a third machine below bus 5. The sentence “the voltage at both sources is 1 p.u.” is taken to mean all sources are at 1.0 pu, which is the only reading that lets the network be solved. (iii) In Figure (4-a) of Problem 6, transformer T2 carries its delta on the generator side and T1 carries its delta on the motor side; motor 1 is an ungrounded wye and motor 2 is grounded through a reactor. Those four winding connections, not the reactance values, decide the answer. (iv) Problem 7 gives the switching angles in radians (1.2, 1.25 and 1.9 rad).
Check: Problem 3(a) as printed is over-determined and internally inconsistent. Rated kVA, the load power factor, the efficiency and the primary voltage are four data for two unknowns, and at 0.85 power factor lagging no positive series reactance satisfies them all. The inconsistency is quantified and resolved inside the answer rather than hidden.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Given. Four buses joined by three lossless branches, with one unknown voltage magnitude and one specified injection.
| Bus | $|V_i|$ (pu) | $\delta_i$ | $P_i$ (pu) | $Q_i$ (pu) |
|---|---|---|---|---|
| 1 | 1.00 | 0° | ? | ? |
| 2 | ? | −10° | −0.95 | ? |
| 3 | 1.02 | −12° | ? | ? |
| 4 | 0.98 | −8° | ? | ? |
Branch reactances (from Figure 2): $x_{12}=0.25$, $x_{23}=0.20$, $x_{24}=0.10$ pu, all purely inductive, so the network is lossless in real power.
Find. The seven missing entries: $|V_2|$ and the eight injections implied by the specified voltage profile.
Approach. Every branch is a pure reactance, so the real-power injection at bus 2 is exactly linear in $|V_2|$; solve that one equation for $|V_2|$, then evaluate the four complex injections from $S_i = V_i\left(\sum_k Y_{ik}V_k\right)^{*}$.
Check: the answer is dictated by the printed angle set, and it is an unusual operating point. Holding bus 2 at −10° while its neighbours sit at −12° and −8° forces a large reactive injection there (+2.425 pu) and a bus voltage of 1.106 pu, above the 1.00 pu swing bus. Physically that means bus 2 must carry substantial local reactive support — a capacitor bank or a compensator — alongside its 0.95 pu real load. Nothing in the arithmetic is wrong; the question specifies a voltage profile and asks what injections sustain it, which is the reverse of the usual power-flow question, and the profile it specifies is a demanding one.
| Bus | $|V_i|$ (pu) | $\delta_i$ | $P_i$ (pu) | $Q_i$ (pu) |
|---|---|---|---|---|
| 1 | 1.0000 | 0° | 0.7685 | -0.3585 |
| 2 | 1.1064 | −10° | −0.9500 | 2.4252 |
| 3 | 1.0200 | −12° | -0.1969 | -0.4373 |
| 4 | 0.9800 | −8° | 0.3784 | -1.2324 |
| Branch | $P$ leaving the first bus (pu) | $Q$ leaving the first bus (pu) | Reactive absorption $|I|^{2}x$ (pu) |
|---|---|---|---|
| 1 → 2 | 0.7685 | -0.3585 | 0.1798 |
| 2 → 3 | 0.1969 | 0.4816 | 0.0442 |
| 2 → 4 | -0.3784 | 1.4054 | 0.1730 |