22-Elec-B7 Power Systems Engineering · May 2017
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, May 2017 — 16-Elec-B7 Power Systems Engineering. Open-book, 3 hours, seven problems of equal value (25 points each); any five constitute a complete paper, and only the first five in the answer book are marked. All seven are solved here, because the set is a study resource rather than a sitting.
Reference texts. This exam code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation is his throughout: the bundle-conductor mean radii and long-line ABCD constants of Problem 1, the round-rotor power-angle relations of Problem 2, the three-winding equivalent circuit of Problem 3, the sequence-network fault reduction of Problem 6 and the equal-area criterion of Problem 7. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed. (ch. 4–5 transmission-line parameters, ch. 6 power flow, ch. 7–9 symmetrical components and faults, ch. 11 transient stability); J. J. Grainger and W. D. Stevenson, Power System Analysis; and S. J. Chapman, Electric Machinery Fundamentals, 5th ed., for the synchronous-machine and transformer chapters. Canadian practice references where protection and grounding are discussed: CSA C22.1 Canadian Electrical Code, Part I, CSA C22.3 for overhead systems, and IEEE C37 (protective relaying) and IEEE 142 Green Book (grounding).
Check: four judgement calls carried through the solutions, recorded here rather than hedged inside the answers.
(i) Problem 1 states neither a frequency nor a line length. Parts (a)–(c) need neither. Part (d) needs both, so 60 Hz is used (Canadian national exam) and the ABCD constants are given as closed-form functions of length, evaluated at a representative 400 km with a sensitivity table at 200 km and 600 km. The characteristic impedance and the surge-impedance loading do not depend on either quantity.
(ii) Problem 1 gives “bundle separation S” for a bundle whose figure shows eight sub-conductors on a circle. S is read as the distance between adjacent sub-conductors, so the bundle radius is $A = S/[2\sin(\pi/N)] = 0.6533\ \text{m}$ — the standard El-Hawary reading. If a marker instead reads S as the bundle diameter, every mean radius scales by the same factor and the method is unchanged.
(iii) Problem 5 says “the voltage at both sources is 1 p.u.” above a figure that draws three generators. All three are taken at 1.0 pu, which is the only reading that closes the network; the three internal e.m.f.s then merge into one node.
(iv) Problem 6: the zero-sequence source reactance is printed as $X_{0S}=j0.04$, possibly followed by a fifth digit. The value $j0.04$ is used. Reading it as $j0.045$ moves the zero-sequence Thévenin reactance from 0.19978 to 0.20051 pu and the fault current by 0.1 % — below the resolution of any answer here.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
(a) Armature reaction. When a synchronous machine is loaded, the balanced three-phase currents in the stator windings themselves produce a rotating magnetic field. That field turns in synchronism with the rotor field, so the two are stationary relative to one another and add vectorially to give the resultant air-gap flux. Armature reaction is precisely this effect of stator current on the air-gap flux: the machine no longer excites itself from the field winding alone. Its character depends on the phase of the current relative to the internal e.m.f. A lagging current produces a stator field that opposes the rotor field (demagnetising, so the terminal voltage sags and more field current is needed to hold it); a leading current produces a field that aids the rotor field (magnetising, so the terminal voltage rises); a current exactly in phase with the internal e.m.f. produces a cross-magnetising field at right angles to the rotor field, which distorts rather than weakens it and shifts the effective flux axis. Because the reaction flux is proportional to armature current and, in an unsaturated round-rotor machine, in quadrature with it, the whole effect can be represented by a single fictitious reactance in series with the internal e.m.f. Adding the true leakage reactance gives the synchronous reactance $X_s$ used in this problem — so the 0.3 pu reactance is not a stray inductance but mostly armature reaction expressed as a circuit element.
(b) When the machine is a source of reactive power. With armature resistance neglected, the reactive power delivered to the bus is$$Q=\frac{EV\cos\delta-V^{2}}{X_s},$$so the machine exports reactive power (acts as a capacitor seen from the network) precisely when $E\cos\delta > V$ — that is, when the internal e.m.f. projected onto the terminal voltage exceeds the terminal voltage. In operating language this is the over-excited condition: the field current is raised beyond the value that would make the machine deliver its real load at unity power factor. The armature current then lags the terminal voltage, armature reaction is demagnetising, and the extra field ampere-turns supply both the load flux and the exported vars. Under-excite the machine, so that $E\cos\delta$ falls below $V$, and the sign reverses: it absorbs vars, draws a leading current, and behaves as an inductor — the mode used at night on long lightly-loaded EHV lines to soak up line charging. At $E\cos\delta = V$ exactly the machine is at unity power factor, which is the locus conditions A and B sit on. The same statement holds at zero real load: an over-excited unloaded machine is a synchronous condenser, historically the standard var source before static compensators, and still used for inertia and short-circuit strength on networks with heavy inverter penetration.
(c) Given. Infinite bus $V = 1.00\ \text{pu}$; synchronous reactance $X_s = 0.3\ \text{pu}$; armature resistance neglected. The paper prints “neglecting armature reaction”; as part (a) explains, for a round-rotor machine armature reaction is already carried inside $X_s$, so removing it would leave no reactance to work with. The phrase is therefore read as the usual instruction to neglect armature resistance (and saturation), which is the only reading under which the table can be completed. Three operating conditions, each with two of the four quantities $(P,\ Q_2,\ E,\ \delta)$ known.
Find. The two missing entries in each row of the table, with $Q_2$ measured at the machine terminals, i.e. at the infinite bus to which the machine connects directly through $X_s$.
Approach. With resistance neglected the machine obeys the two standard round-rotor relations $P=(EV/X_s)\sin\delta$ and $Q=(EV\cos\delta-V^{2})/X_s$. Each row supplies two of the four unknowns, so each is a two-equation algebraic solve; the $Q_2 = 0$ rows collapse to the single condition $E\cos\delta = V$.
Final Results
| Condition | $P$ (pu) | $Q_2$ (pu) | $E$ (pu) | $\delta$ | Excitation |
|---|---|---|---|---|---|
| A | 1.6813 | 0.0 (given) | 1.12 (given) | 26.77° | unity pf |
| B | 2.7 (given) | 0.0 (given) | 1.2869 | 39.01° | unity pf |
| C | 2.2321 | −0.4244 | 1.1 (given) | 37.5° (given) | under-excited (absorbs vars) |