Question 6 of 7: Single Line-to-Ground Fault on a Sequence-Network Representation
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2017 — 16-Elec-B7 Power Systems Engineering. Open-book, 3 hours, seven problems of equal value (25 points each); any five constitute a complete paper, and only the first five in the answer book are marked. All seven are solved here, because the set is a study resource rather than a sitting.
Reference texts. This exam code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation is his throughout: the bundle-conductor mean radii and long-line ABCD constants of Problem 1, the round-rotor power-angle relations of Problem 2, the three-winding equivalent circuit of Problem 3, the sequence-network fault reduction of Problem 6 and the equal-area criterion of Problem 7. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed. (ch. 4–5 transmission-line parameters, ch. 6 power flow, ch. 7–9 symmetrical components and faults, ch. 11 transient stability); J. J. Grainger and W. D. Stevenson, Power System Analysis; and S. J. Chapman, Electric Machinery Fundamentals, 5th ed., for the synchronous-machine and transformer chapters. Canadian practice references where protection and grounding are discussed: CSA C22.1 Canadian Electrical Code, Part I, CSA C22.3 for overhead systems, and IEEE C37 (protective relaying) and IEEE 142 Green Book (grounding).
Check: four judgement calls carried through the solutions, recorded here rather than hedged inside the answers.
(i) Problem 1 states neither a frequency nor a line length. Parts (a)–(c) need neither. Part (d) needs both, so 60 Hz is used (Canadian national exam) and the ABCD constants are given as closed-form functions of length, evaluated at a representative 400 km with a sensitivity table at 200 km and 600 km. The characteristic impedance and the surge-impedance loading do not depend on either quantity.
(ii) Problem 1 gives “bundle separation S” for a bundle whose figure shows eight sub-conductors on a circle. S is read as the distance between adjacent sub-conductors, so the bundle radius is $A = S/[2\sin(\pi/N)] = 0.6533\ \text{m}$ — the standard El-Hawary reading. If a marker instead reads S as the bundle diameter, every mean radius scales by the same factor and the method is unchanged.
(iii) Problem 5 says “the voltage at both sources is 1 p.u.” above a figure that draws three generators. All three are taken at 1.0 pu, which is the only reading that closes the network; the three internal e.m.f.s then merge into one node.
(iv) Problem 6: the zero-sequence source reactance is printed as $X_{0S}=j0.04$, possibly followed by a fifth digit. The value $j0.04$ is used. Reading it as $j0.045$ moves the zero-sequence Thévenin reactance from 0.19978 to 0.20051 pu and the fault current by 0.1 % — below the resolution of any answer here.
Problem 6: Single Line-to-Ground Fault on a Sequence-Network Representation (25 points)
Find. The total current delivered to a bolted single line-to-ground fault at the mid-point of line G–H, and the three phase voltages at each of buses G and H while that fault is on.
[Figure not reproduced: Figure 6 — The two sequence networks of Figure (5) redrawn with the fault node F at the mid-point of line G–H. In the positive-sequence network the tertiary arm Z L is open, so the branch from H to the source is simply X HM + X 1S ; in the zero-sequence network all three arms of the thre. See the official exam paper.]
Approach. Reduce each sequence network to its Thévenin reactance seen from F, connect the three in series (the standard single line-to-ground connection), obtain the symmetrical components of the fault current, then propagate those component currents back through each network to get the sequence voltages at G and H and finally transform to phase quantities.
Part 1 — reduce the positive-sequence network. With the tertiary arm open, bus G is reached from the source through $X_d^{\prime\prime}+X_{TG}=0.20+0.1375=0.3375$ pu and bus H through $X_{1S}+X_{HM}=0.03+0.03667=0.06667$ pu. The fault at the mid-point splits the line into $0.18148/2=0.09074$ pu on each side, so the two paths from the source node to F are$$0.3375+0.09074=0.42824\ \text{pu}\qquad\text{and}\qquad 0.06667+0.09074=0.15741\ \text{pu},$$in parallel:$$X_1=\frac{(0.42824)(0.15741)}{0.42824+0.15741}=\frac{0.067409}{0.58565}=0.115102\ \text{pu}.$$The negative-sequence network is identical in this representation, so $X_2=X_1=j0.115102$ pu.
Reduce the zero-sequence network. Here the picture changes: the generator is barred by the delta of its transformer and does not appear, but the three-winding unit at bus H is fully present. Its high arm and the system source are in series, $Z_H+X_{0S}=0.0450+0.0400=0.0850$ pu, and that is in parallel with the low (tertiary) arm $Z_L=0.1950$ pu:$$\frac{(0.0850)(0.1950)}{0.0850+0.1950}=0.059196\ \text{pu},$$to which the medium arm adds its negative value: $0.059196-0.0083=0.050896$ pu from bus H to the reference.
Complete the zero-sequence reduction. The zero-sequence line is much larger than the positive-sequence line — $0.620$ pu, giving $0.310$ pu per half — so the two paths to F are $0.1375+0.310=0.4475$ pu through bus G and $0.050896+0.310=0.360896$ pu through bus H, and$$X_0=\frac{(0.4475)(0.360896)}{0.4475+0.360896}=\frac{0.161501}{0.808396}=0.199780\ \text{pu}.$$Because $X_0$ exceeds $X_1$, the single line-to-ground current will be smaller than the three-phase current at the same point — the standard signature of a network whose zero-sequence path is the weaker one.
Connect the three networks in series. A bolted single line-to-ground fault on phase a forces $I_{a1}=I_{a2}=I_{a0}$ and $V_{a1}+V_{a2}+V_{a0}=0$, which is the series connection of the three Thévenin networks:$$I_{a1}=\frac{E}{X_1+X_2+X_0}=\frac{1.0\angle0^\circ}{j(0.115102+0.115102+0.199780)}=\frac{1.0}{j0.429983},$$giving $I_{a1}=I_{a2}=I_{a0}=2.32567\angle-90^\circ$ pu.
Figure 7 — The single line-to-ground connection: the three sequence Thévenin networks in series across the prefault voltage. The same current flows in all three, which is what makes Ia = 3 Ia1.
Report the fault current. The faulted-phase current is the sum of the three equal components,$$\boxed{I_f=I_a=3I_{a1}=6.9770\angle-90^\circ\ \text{pu},}$$the other two phases carrying zero. On a 100 MVA base this is 697.7 MVA of single-phase fault duty. For comparison, a three-phase fault at the same point would draw $1/X_1=8.6880$ pu, so the ground fault is 80 per cent of the three-phase value — consistent with $X_0 > X_1$, and the check that the zero-sequence network has been built correctly.
Part 2 — sequence voltages at bus G. Each network is now driven by its known component current. In the positive-sequence network the current divides between the two paths; the share flowing in from the G side is $I_{a1}(0.15741/0.58565)=0.62508$ pu, and bus G sits that current’s drop above F on the G-side half-line while also being pulled down from the source. Solving the network gives$$V_{G1}=0.789032,\qquad V_{G2}=-0.210968,\qquad V_{G0}=-0.142761\ \text{pu},$$all real because every impedance is a pure reactance and the driving voltage is real.
Sequence voltages at bus H. The same construction on the H side, where the source is electrically much closer, gives$$V_{H1}=0.886622,\qquad V_{H2}=-0.113378,\qquad V_{H0}=-0.065525\ \text{pu}.$$Bus H holds up better than bus G in every sequence, which is expected: its path to the source is $0.06667$ pu against $0.3375$ pu at bus G.
Transform to phase voltages at bus G. With $a=1\angle120^\circ$ and the standard synthesis $V_a=V_0+V_1+V_2$, $V_b=V_0+a^{2}V_1+aV_2$, $V_c=V_0+aV_1+a^{2}V_2$,$$\boxed{\begin{aligned}V_{aG}&=0.4353\angle0^\circ,\\ V_{bG}&=0.9677\angle-116.50^\circ,\\ V_{cG}&=0.9677\angle+116.50^\circ\ \text{pu}.\end{aligned}}$$
Transform to phase voltages at bus H. The same transformation on the bus-H components gives$$\boxed{\begin{aligned}V_{aH}&=0.7077\angle0^\circ,\\ V_{bH}&=0.9770\angle-117.57^\circ,\\ V_{cH}&=0.9770\angle+117.57^\circ\ \text{pu}.\end{aligned}}$$The faulted phase is depressed at both buses — heavily at G, which is on the weak side of the fault — while the two healthy phases stay near unity but swing apart in angle, the familiar unbalanced signature of an earth fault on an effectively-grounded system.
Check the result at the fault point itself. At F the three sequence voltages must sum to zero, and they do: $V_{F1}=0.732311$, $V_{F2}=-0.267689$ and $V_{F0}=-0.464622$ pu, summing to $0.000000$. Equivalently, $V_{F1}=E-jX_1I_{a1}$ with the same numbers. A second check is the coefficient of grounding: the healthy-phase voltages reach 0.977 pu, well below the 1.4 pu that would flag an ineffectively-grounded system, which is consistent with $X_0/X_1=1.74$ and $R_0/X_1=0$.