NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · December 2013

Question 1 of 8: Natatorium — mixing, preheat and psychrometric cycle

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. Professional Engineers of Ontario / Engineers Canada annual examination 07-Mec-B2 Environmental Control in Buildings, December 2013 — 3 hours, open book, non-communicating calculator permitted. Eight problems of 20 points each; candidates answer any five. ASHRAE psychrometric charts (SI and I-P) and an R-134a pressure–enthalpy diagram are appended to the paper. All eight problems are solved below, because the set is intended as a study resource.

Reference texts. ASHRAE Handbook — Fundamentals (Ch. 1 Psychrometrics, Ch. 15 Fenestration, Ch. 16 Ventilation and Infiltration, Ch. 18 Nonresidential Cooling and Heating Load Calculations, Ch. 21 Duct Design); McQuiston, Parker & Spitler, Heating, Ventilating, and Air Conditioning: Analysis and Design, 6th ed.; Çengel & Boles, Thermodynamics: An Engineering Approach, 9th ed. (R-134a property tables); ANSI/ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy; ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Indoor Air Quality. Canadian practice: National Energy Code of Canada for Buildings (NECB) and CSA F280 where a Canadian code reference is required.

Check — table-derived coefficients. This is an open-book paper whose cover page instructs candidates to “submit a clear statement of the assumption(s)” made. Where a solution needs a value that is read from a handbook table or chart rather than given in the question — shading coefficients, air-space thermal resistances, curtain-wall leakage rates, surface-averaged wind pressure coefficients, window and door U-factors, CO2 generation rates — the value used is stated explicitly at the point of use with its source. The method, not the table entry, is what the marks follow; a different edition of the table shifts the arithmetic but not the answer structure.

Question 1: Natatorium — mixing, preheat and psychrometric cycle (20 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantitySymbolValue
Space sensible heat loss$q_s$130 kW
Space latent heat gain$q_l$160 kW
Outdoor design state$t_o,\ \phi_o$2 °C, 20% RH
Room state to be maintained$t_r,\ \phi_r$24 °C, 50% RH
Supply dry-bulb temperature$t_s$35 °C
Barometric pressure (sea level)$p$101.325 kPa
Moist-air specific heat$c_p$1.02 kJ/(kg·K)
Latent heat of vaporisation (0 °C datum)$h_{fg}$2501 kJ/kg

Find. The supply air mass (and volume) flow at 35 °C, the outdoor-to-recirculated air ratio, the preheat-coil duty and the heat exchanged in the mixing box — together with a system schematic and the four state points plotted on the psychrometric chart with their dry- and wet-bulb temperatures.

Outdoor2 deg C, 20% RHOMIXINGBOXMmixed air MPREHEAT COILfanS35 deg C supplyNATATORIUM (pool hall)24 deg C, 50% RHRrecirculated (return) air Rrelief / exhaust (balances the outdoor-air intake)
Figure 1.1 — System schematic. Outdoor air O mixes with recirculated room air R at M; the mixture is heated to the supply state S and delivered to the space, which returns to state R.
0713202733400481216100%50%mixing linepreheatroom processOMSRdry-bulb temperature (deg C)humidity ratio W (g/kg dry air)
Figure 1.2 — Operating cycle on the psychrometric chart. O–R is the adiabatic mixing line (M lies on it); M–S is sensible heating at constant humidity ratio; S–R is the room process, which gains moisture and loses sensible heat.

Approach. Fix the room and outdoor states from the given dry-bulb/RH pairs, size the supply air from the sensible balance at the stated 35 °C supply temperature, obtain the supply humidity ratio from the latent balance, then work backwards: the heater does not change humidity ratio, so the mixed-air humidity ratio equals the supply humidity ratio and fixes the outdoor-air fraction by a moisture balance on the mixing box.

  1. Fix the outdoor and room humidity ratios. With $p_{ws}$ from the ASHRAE saturation-pressure correlation and $W = 0.622\,p_w/(p - p_w)$: $$W_o = \frac{0.622\,(0.20)(0.7060)}{101.325 - 0.1412} = 0.00087\ \text{kg/kg da},\qquad W_r = \frac{0.622\,(0.50)(2.985)}{101.325 - 1.4925} = 0.00930\ \text{kg/kg da}$$ The corresponding specific enthalpies are $h_o = 4.19$ and $h_r = 47.81$ kJ/kg da.
  2. Size the supply air from the sensible balance. The room loses 130 kW of sensible heat, so the supply air must deliver it while cooling from 35 °C to the room 24 °C: $$\dot m_a = \frac{q_s}{c_p\,(t_s - t_r)} = \frac{130}{1.02\,(35 - 24)} = \boxed{11.59\ \text{kg/s dry air}}$$ At the supply state this is $\dot V_s = \dot m_a v_s = 11.59 \times 0.878 = 10.2\ \text{m}^3/\text{s}$ (about 21\,600 cfm) — the answer to part (a).
  3. Obtain the supply humidity ratio from the latent balance. The pool evaporates moisture into the space (a latent gain of 160 kW), so the supply air must arrive dry enough to absorb it: $$W_r - W_s = \frac{q_l}{\dot m_a\,h_{fg}} = \frac{160}{11.59 \times 2501} = 0.00552\ \text{kg/kg da}$$ $$W_s = 0.00930 - 0.00552 = 0.00378\ \text{kg/kg da}$$ State S is therefore 35 °C at $W = 0.00378$, i.e. only 10.9% RH — very dry air, which is exactly what a natatorium needs.
  4. Find the outdoor-air fraction from a moisture balance on the mixing box. Heating is a constant-humidity-ratio process, so $W_m = W_s$. Writing the mixing balance with $x$ the outdoor mass fraction, $$W_m = x W_o + (1 - x) W_r \;\Rightarrow\; x = \frac{W_r - W_m}{W_r - W_o} = \frac{0.00930 - 0.00378}{0.00930 - 0.00087} = 0.655$$ so 65.5% of the supply is outdoor air and 34.5% is recirculated: $$\frac{\dot m_o}{\dot m_r} = \frac{0.655}{0.345} = \boxed{1.90 : 1}$$ In absolute terms $\dot m_o = 7.59$ kg/s and $\dot m_r = 4.00$ kg/s — the answer to part (b). The high outdoor-air fraction is the direct consequence of the enormous latent gain: outdoor air at 2 °C is the cheapest available desiccant.
  5. Locate the mixed state M. An adiabatic mixing box conserves enthalpy as well as mass, so $$h_m = x h_o + (1 - x) h_r = 0.655(4.19) + 0.345(47.81) = 19.24\ \text{kJ/kg da}$$ Inverting $h = 1.006\,t + W(2501 + 1.86\,t)$ at $W_m = 0.00378$ gives $t_m = 9.7\ \text{°C}$ (50.9% RH). Point M lies on the straight line O–R, at the fraction 0.345 of the way from O to R — the graphical construction shown in Figure 1.2.
  6. Preheat-coil duty (part c). The coil raises the mixture from M to S at constant $W$: $$q_{\text{preheat}} = \dot m_a (h_s - h_m) = 11.59\,(44.90 - 19.24) = \boxed{297\ \text{kW}}$$ A useful cross-check: this must equal the space sensible loss plus the sensible energy needed to warm the outdoor air from 2 °C to room temperature, $q = 130 + 7.59(1.02)(24 - 2) = 300$ kW, which agrees to within the rounding of $c_p$.
  7. Heat transfer rate for the mixing process (part d). The mixing box exchanges no heat with its surroundings — it is adiabatic, so the external heat transfer rate is $$q_{\text{mixing, external}} = \boxed{0\ \text{kW}}$$ What the process does transfer is energy between the two streams: the warm return air heats the cold outdoor air. That internal exchange is $$q_{o\to m} = \dot m_o (h_m - h_o) = 7.59\,(19.24 - 4.19) = 114\ \text{kW} = \dot m_r (h_r - h_m) = 4.00\,(47.81 - 19.24)$$ Both forms agree, confirming the mixing balance. Quoting 114 kW as “the heat transfer rate for the mixing process” is the intended reading; the point worth stating in the answer book is that this is free recovered heat, not coil duty — without recirculation the preheat coil would have to supply $q = 297 + 114 = 411$ kW.

The four state points, with the wet-bulb temperatures requested by the question, are collected below. These are the values that would be annotated on the schematic and on the psychrometric chart.

State pointDry bulbWet bulbW (kg/kg da)RH
O — outdoor air2.0 °C−3.1 °C0.0008720.0%
M — mixed air9.7 °C5.3 °C0.0037850.9%
S — supply air35.0 °C16.2 °C0.0037810.9%
R — room air24.0 °C17.1 °C0.0093050.0%

Check — assumptions stated per cover-page instruction 1. Sea-level barometric pressure 101.325 kPa; moist-air $c_p = 1.02$ kJ/(kg·K) and $h_{fg} = 2501$ kJ/kg at the 0 °C datum; fan, pump and duct heat gains neglected as the question directs; the pool-water make-up and deck losses are already embedded in the stated 130 kW / 160 kW; and the relief air leaving the space is at room state R, so the exhaust exactly balances the 65.5% outdoor-air intake.

Final results
QuantityResult
(a) Supply air mass flow$\dot m_a = 11.59$ kg/s dry air
(a) Supply air volume flow at 35 °C$\dot V_s = 10.2\ \text{m}^3/\text{s}$ (≈ 21 600 cfm)
(b) Outdoor : recirculated air1.90 : 1 (65.5% OA / 34.5% RA)
(c) Preheat coil duty$q_{\text{preheat}} = 297$ kW
(d) Mixing process, external heat transfer0 kW (adiabatic)
(d) Energy exchanged between streams in the mixing box114 kW
Supply state S35.0 °C DB / 16.2 °C WB, $W = 0.00378$
Mixed state M9.7 °C DB / 5.3 °C WB, $W = 0.00378$
← Paper overview