NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · December 2013

Question 2 of 8: Summer air conditioner — apparatus dew point and coil capacity

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. Professional Engineers of Ontario / Engineers Canada annual examination 07-Mec-B2 Environmental Control in Buildings, December 2013 — 3 hours, open book, non-communicating calculator permitted. Eight problems of 20 points each; candidates answer any five. ASHRAE psychrometric charts (SI and I-P) and an R-134a pressure–enthalpy diagram are appended to the paper. All eight problems are solved below, because the set is intended as a study resource.

Reference texts. ASHRAE Handbook — Fundamentals (Ch. 1 Psychrometrics, Ch. 15 Fenestration, Ch. 16 Ventilation and Infiltration, Ch. 18 Nonresidential Cooling and Heating Load Calculations, Ch. 21 Duct Design); McQuiston, Parker & Spitler, Heating, Ventilating, and Air Conditioning: Analysis and Design, 6th ed.; Çengel & Boles, Thermodynamics: An Engineering Approach, 9th ed. (R-134a property tables); ANSI/ASHRAE Standard 55 Thermal Environmental Conditions for Human Occupancy; ANSI/ASHRAE Standard 62.1 Ventilation for Acceptable Indoor Air Quality. Canadian practice: National Energy Code of Canada for Buildings (NECB) and CSA F280 where a Canadian code reference is required.

Check — table-derived coefficients. This is an open-book paper whose cover page instructs candidates to “submit a clear statement of the assumption(s)” made. Where a solution needs a value that is read from a handbook table or chart rather than given in the question — shading coefficients, air-space thermal resistances, curtain-wall leakage rates, surface-averaged wind pressure coefficients, window and door U-factors, CO2 generation rates — the value used is stated explicitly at the point of use with its source. The method, not the table entry, is what the marks follow; a different edition of the table shifts the arithmetic but not the answer structure.

Question 2: Summer air conditioner — apparatus dew point and coil capacity (20 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantitySymbolValue
Outdoor air volume flow$\dot V_o$2000 cfm at 90 °F DB / 73 °F WB
Return air volume flow$\dot V_r$6000 cfm at 75 °F DB, 50% RH
Off-coil condition—90% saturation (degree of saturation $\mu = 0.90$)
Room sensible heat factor$\text{RSHF}$0.68
Barometric pressure$p$14.696 psia (sea level)

Find. The apparatus dew point, the dew-point temperature of the air leaving the coil and the off-coil dry-bulb temperature; the total coil capacity in Btu/hr; and the split of that capacity into sensible and latent components — with the system diagram and the cycle drawn on the I-P chart.

Outdoor90 deg F DB / 73 deg F WBOMIXINGBOXMmixed air MCOOLING COILfanSoff-coil supply SCONDITIONED SPACE75 deg F DB, 50% RHRrecirculated (return) air Rrelief / exhaust (balances the outdoor-air intake)
Figure 2.1 — System schematic. 2000 cfm outdoor air and 6000 cfm return air mix at M, pass over the cooling coil to S, and are delivered to the space which returns at R.
4050607080901000.0000.0050.0100.0150.020100%50%mixingcoilRSHF 0.68OMRSADPdry-bulb temperature (deg F)humidity ratio W (lb/lb dry air)
Figure 2.2 — Operating cycle. O–R is the mixing line carrying M; S–R is the room line of slope RSHF = 0.68, extended to the saturation curve at the apparatus dew point ADP; M–S is the coil process, which passes through ADP.

Approach. Convert both entering streams to mass flows through their specific volumes and mix them to fix state M. Draw the room sensible-heat-factor line through the room state R; where it meets the saturation curve is the apparatus dew point, and where it meets the 90%-saturation curve is the off-coil state S. The coil load is then the enthalpy drop from M to S on the total mass flow.

  1. Fix the two entering states. From the 90 °F DB / 73 °F WB pair the adiabatic-saturation relation gives $W_o = 0.01352$ lb/lb da, $h_o = 36.48$ Btu/lb da and $v_o = 14.16\ \text{ft}^3/\text{lb}$. For the return air at 75 °F, 50% RH, $W_r = 0.00924$ lb/lb da, $h_r = 28.11$ Btu/lb da, $v_r = 13.68\ \text{ft}^3/\text{lb}$ (room dew point 55.1 °F).
  2. Convert to mass flows and mix. Working in mass rather than volume avoids the small error the “cfm-weighted” shortcut introduces when the two streams have different densities: $$\dot m_o = \frac{2000 \times 60}{14.16} = 8476\ \text{lb/h},\qquad \dot m_r = \frac{6000 \times 60}{13.68} = 26\,317\ \text{lb/h}$$ $$\dot m_t = 34\,793\ \text{lb/h},\qquad W_m = \frac{8476(0.01352) + 26\,317(0.00924)}{34\,793} = 0.01028\ \text{lb/lb da}$$ $$h_m = \frac{8476(36.48) + 26\,317(28.11)}{34\,793} = 30.15\ \text{Btu/lb da} \;\Rightarrow\; t_m = 78.7\ \text{°F DB},\ 65.3\ \text{°F WB}$$
  3. Construct the room sensible-heat-factor line. Along a line of constant SHF through the room state, sensible and latent enthalpy changes keep the ratio 0.68, so $$\frac{\Delta W}{\Delta t} = \frac{c_{pa}\,(1 - \text{SHF})}{\text{SHF}\;h_g} = \frac{0.240\,(1 - 0.68)}{0.68 \times 1061} = 1.065 \times 10^{-4}\ \text{lb/lb per °F}$$ Every point on the supply line satisfies $W = W_r - 1.065\times10^{-4}(75 - t)$. (This is the line the protractor on the chart draws for SHF = 0.68.)
  4. Apparatus dew point (part a). The ADP is where that line, extended, meets the saturation curve, i.e. where $W_{\text{sat}}(t) = W_r - 1.065\times10^{-4}(75 - t)$. Solving, $$t_{\text{ADP}} = \boxed{42.9\ \text{°F}}$$ This is the effective surface temperature the coil must reach for the room to be held at 75 °F, 50% RH with a sensible heat factor of 0.68.
  5. Off-coil state (part a). Air leaving at 90% saturation lies on the same room line where $W = 0.90\,W_{\text{sat}}(t)$: $$t_s = \boxed{48.0\ \text{°F DB}},\qquad W_s = 0.00636\ \text{lb/lb da},\qquad h_s = 18.39\ \text{Btu/lb da}$$ Its dew point — the “air dew point” asked for — follows from $W_s$: $$t_{dp,s} = \boxed{45.2\ \text{°F}}$$ (the wet bulb is 46.5 °F). As expected the three temperatures nest, $t_{\text{ADP}} < t_{dp,s} < t_s$. The corresponding coil bypass factor is $$\text{BF} = \frac{t_s - t_{\text{ADP}}}{t_m - t_{\text{ADP}}} = \frac{48.0 - 42.9}{78.7 - 42.9} = 0.14$$ a realistic value for a four- to six-row coil.
  6. Cooling coil capacity (part b). The coil must take the whole mixture from M to S: $$q_t = \dot m_t (h_m - h_s) = 34\,793\,(30.15 - 18.39) = \boxed{409\,000\ \text{Btu/hr}} \;(34.1\ \text{tons})$$ Checking by parts: the room load is $\dot m_t(h_r - h_s) = 338\,000$ Btu/hr and the outdoor-air load is $\dot m_o(h_o - h_r) = 71\,000$ Btu/hr, summing to 409 000 Btu/hr.
  7. Sensible and latent split (part c). Splitting the same enthalpy drop into its dry-air and moisture parts, $$q_s = \dot m_t\,(c_{pa} + c_{pv}W_s)(t_m - t_s) = 34\,793\,(0.2428)(78.7 - 48.0) = \boxed{259\,000\ \text{Btu/hr}}$$ $$q_l = \dot m_t\,(W_m - W_s)(h_g) = 34\,793\,(0.01028 - 0.00636)(1096) = \boxed{150\,000\ \text{Btu/hr}}$$ so the coil is 63.4% sensible and 36.6% latent. Its own sensible heat factor, 0.634, is lower than the room value of 0.68 because the 2000 cfm of humid outdoor air adds mostly latent load.

Check — reading of part (a). The phrase “the apparatus dew point (ADP) the air dew point and the air of coil dry bulb temperature” is read as three quantities: the ADP, the dew point of the air leaving the coil, and the off-coil dry-bulb temperature. The room dew point (55.1 °F) is also reported in case the second item was intended to mean the room air.

Final results
QuantityResult
(a) Apparatus dew point$t_{\text{ADP}} = 42.9$ °F
(a) Dew point of air leaving the coil$t_{dp,s} = 45.2$ °F (room dew point 55.1 °F)
(a) Off-coil dry-bulb temperature$t_s = 48.0$ °F DB (46.5 °F WB, $W_s = 0.00636$)
Mixed-air state M78.7 °F DB / 65.3 °F WB, $W_m = 0.01028$
Coil bypass factorBF = 0.14
(b) Cooling coil capacity$q_t = 409\,000$ Btu/hr (34.1 tons)
(c) Sensible portion$q_s = 259\,000$ Btu/hr (63.4%)
(c) Latent portion$q_l = 150\,000$ Btu/hr (36.6%)