22-Mec-B2 Environmental Control in Buildings · May 2013
Question 1 of 8: Mixed-air plant with reheat — cycle, loads and plant energy (20 marks)
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of Ontario / EGBC
annual examination, 07-Mec-B2 (now 22-Mec-B2) Environmental Control in
Buildings, May 2013 sitting. Three hours, open book.
Eight problems of 20 points each; the candidate is instructed to solve
five and to nominate which five are to be graded. Psychrometric
charts and a pressure–enthalpy diagram for ammonia (R-717) are appended to
the paper, and candidates are expected to bring an environmental-control text
and steam tables. Instruction 1 invites the candidate to state any
interpretation assumptions with the answer — that latitude is used
explicitly below where the printed data are redundant.
All eight problems are worked here. Every
psychrometric state has been recomputed from the ASHRAE formulation for
saturation vapour pressure rather than scaled off a chart, so the numbers are
tighter than a graphical solution would be; chart-quality agreement (about
±0.2 K and ±0.0002 kg/kg) is all that an examiner expects.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed., Butterworth-Heinemann — the standard reference for this examination code;
Ch. 2–3 (psychrometry), Ch. 6 (cooling loads), Ch. 10 (cooling towers),
Ch. 15 (duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist air), Ch. 8 (energy estimating and
degree-day methods), Ch. 12–13 (fluid flow and duct design).
ASHRAE Handbook – Fundamentals (2021) — Ch. 1 (psychrometrics), Ch. 21 (duct design),
Ch. 25–27 (heat, air and moisture transfer in the envelope).
Moran, Shapiro, Boettner & Bailey, Fundamentals of Engineering Thermodynamics, 9th ed., Wiley — Ch. 10 (vapour-compression and multistage
refrigeration).
ANSI/ASHRAE Standard 55, Thermal Environmental Conditions for Human
Occupancy, and ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable
Indoor Air Quality.
Canadian frame: National Building Code of Canada 2020, National Energy
Code of Canada for Buildings 2020, and Environment and Climate Change Canada
Canadian Climate Normals for degree-day data.
Psychrometric relations used throughout. At barometric
pressure $p$, with saturation vapour pressure $p_{ws}(t)$ from the ASHRAE
correlation,
in SI (kJ per kg of dry air), and in the inch-pound system
$h = 0.240\,t + W\,(1061 + 0.444\,t)$ Btu per lb of dry air. The
thermodynamic wet-bulb temperature is obtained from the adiabatic-saturation
equation, which is what a chart's constant-wet-bulb lines represent.
Question 1: Mixed-air plant with reheat — cycle, loads and plant energy (20 marks)
Given. A single-zone plant handling a mixture of return and outdoor air through a chilled-water cooling coil and a reheat coil, at sea level ($p = 101.325$ kPa).
Given data
Quantity
Symbol
Value
Zone sensible load
$\dot{Q}_s$
20.5 kW
Zone latent load
$\dot{Q}_l$
8.8 kW
Zone (room) state
R
25 °C, 50% RH
Supply air state and flow
S
14 °C, 60% RH, 1.8 kg/s
Outdoor design state
O
27 °C, 70% RH
Re-circulated : fresh air (by mass)
—
3 : 1
Cooling-coil apparatus dew point
ADP
5 °C
Refrigeration plant coefficient of performance
COP
2
Find. (a) the plant schematic, (b) the cycle plotted on the psychrometric chart, (c) a table of dry- and wet-bulb temperatures at every significant point, (d) the total air-conditioning load imposed by the room, (e) the total energy input to the plant, and (f) the energy input when the reheat coil is served by condenser heat recovery.
(a) Plant schematic. Outdoor air O mixes with re-circulated room air R in the ratio 1 : 3 to give state M; the chilled-water coil cools and dehumidifies M to W; the heating coil reheats W to the supply state S; the fan delivers S to the zone, which returns air at state R.
Approach. Fix R, S and O from the ASHRAE moisture-content relation, mix R and O by mass fraction to get M, locate the coil off-state W on the straight line from M to the apparatus dew point at the supply moisture content (the reheat process is sensible, so the coil must do all of the dehumidification), then close energy balances on the coil, the reheater and the refrigeration plant.
Moisture content of the three specified states. With $p_{ws}(25) = 3.170$ kPa, $p_{ws}(14) = 1.599$ kPa and $p_{ws}(27) = 3.568$ kPa, $$W = 0.6220\,\frac{\phi\,p_{ws}}{p - \phi\,p_{ws}}\;\Rightarrow\; W_R = 0.009881,\; W_S = 0.005944,\;W_O = 0.015715 \ \text{kg/kg}$$ The room dew point is therefore 13.9 °C and the supply dew point 6.4 °C, so the coil must leave the air no warmer than about 6.4 °C saturated — consistent with the 5 °C apparatus dew point specified.
Specific enthalpies of those states. $h = 1.006\,t + W(2501 + 1.86\,t)$ gives $h_R = 50.32$, $h_S = 29.10$ and $h_O = 67.25$ kJ/kg of dry air.
Mixed state M leaving the mixing chamber. A 3 : 1 re-circulation ratio means mass fractions of 0.75 room air and 0.25 outdoor air, and both temperature and moisture content mix linearly: $$t_M = 0.75(25) + 0.25(27) = 25.5^\circ\text{C},\qquad W_M = 0.75(0.009881) + 0.25(0.015715) = 0.011340\ \text{kg/kg}$$ Consistency check on enthalpy: $h_M = 0.75(50.32) + 0.25(67.25) = 54.55$ kJ/kg, the same value the property relation returns for 25.5 °C and 0.011340 kg/kg.
Coil off-state W. The heating coil is a sensible process, so the moisture content leaving the cooling coil already equals the supply value, $W_W = W_S = 0.005944$ kg/kg. The coil process is the straight line from M to the apparatus dew point (5 °C saturated, $W_{ADP} = 0.005402$ kg/kg), whose slope is $$\frac{W_M - W_{ADP}}{t_M - t_{ADP}} = \frac{0.011340 - 0.005402}{25.5 - 5} = 2.897\times10^{-4}\ \text{kg/kg per K}$$ so $t_W = 5 + (0.005944 - 0.005402)/2.897\times10^{-4} = \boxed{6.87^\circ\text{C}}$ and $h_W = 21.85$ kJ/kg. The implied coil contact factor is $(25.5 - 6.87)/(25.5 - 5) = 0.909$, a realistic four- to six-row chilled-water coil.
(d) Total air-conditioning load on the room. The room load is the sum of the two components the question supplies: $$\dot{Q}_{room} = \dot{Q}_s + \dot{Q}_l = 20.5 + 8.8 = \boxed{29.3\ \text{kW}}$$ with a room sensible heat ratio of $20.5/29.3 = 0.70$.
Cooling-coil duty. The coil sees the mixed air, not the room air, so it must also remove the fresh-air load: $$\dot{Q}_{cc} = \dot{m}_a\,(h_M - h_W) = 1.8\,(54.55 - 21.85) = \boxed{58.9\ \text{kW}}$$
Reheat duty. Raising the coil off-state to the supply condition at constant moisture content costs $$\dot{Q}_{rh} = \dot{m}_a\,(h_S - h_W) = 1.8\,(29.10 - 21.85) = \boxed{13.1\ \text{kW}}$$
(e) Total energy input. The refrigeration plant delivers the coil duty at an overall COP of 2, and the reheat energy is bought separately: $$\dot{W}_{ref} = \frac{58.85}{2} = 29.4\ \text{kW},\qquad \dot{E}_{total} = 29.4 + 13.1 = \boxed{42.5\ \text{kW}}$$
(f) Energy input with condenser heat recovery. The condenser rejects everything the plant absorbs plus the work put in, $$\dot{Q}_{cond} = \dot{Q}_{cc} + \dot{W}_{ref} = 58.85 + 29.43 = 88.3\ \text{kW}$$ which is 6.8 times the 13.1 kW the reheat coil needs. The condenser cooling water can therefore carry the whole reheat duty and the purchased input collapses to the compressor power alone: $$\dot{E}_{recovered} = \boxed{29.4\ \text{kW}}$$ a saving of 13.1 kW, or 30.7% of the original input.
(c) Significant points on the diagram and the chart
Point
Description
Dry bulb (°C)
Wet bulb (°C)
$W$ (kg/kg)
$h$ (kJ/kg)
O
Outdoor fresh air
27.0
22.8
0.015715
67.25
R
Room / return air
25.0
17.9
0.009881
50.32
M
Mixing-chamber outlet
25.5
19.2
0.011340
54.55
W
Cooling-coil outlet
6.87
6.6
0.005944
21.85
S
Supply air after reheat
14.0
10.0
0.005944
29.10
ADP
Coil apparatus dew point
5.0
5.0
0.005402
18.59
(b) The operating cycle. Grey dashed lines: adiabatic mixing of R and O to M. Blue: the cooling and dehumidifying process M→W, aimed at the 5 °C apparatus dew point. Red: sensible reheat W→S. Gold: the room process S→R along the room ratio line.
Check: the printed data are redundant and slightly inconsistent. Taking the room and supply states literally, 1.8 kg/s from S to R would offset $1.8(50.32 - 29.10) = 38.2$ kW at a sensible heat ratio of 0.53, not the 29.3 kW at 0.70 that the stated loads give. The two data sets cannot both be exact. Part (d) is answered from the loads the question states, because that is what “the total air conditioning load for the room” asks for, and parts (e) and (f) are answered from the specified states, mixing ratio and apparatus dew point, none of which depends on the load split. Per instruction 1 on the cover page, this reading is stated as an assumption; a candidate who instead scaled the supply flow to 1.38 kg/s to satisfy the stated loads would reach the same method with proportionally smaller duties.