22-Mec-B2 Environmental Control in Buildings · May 2013
Question 2 of 8: All-outdoor-air winter plant — preheat, adiabatic saturation and reheat (20 marks)
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional Engineers of Ontario / EGBC
annual examination, 07-Mec-B2 (now 22-Mec-B2) Environmental Control in
Buildings, May 2013 sitting. Three hours, open book.
Eight problems of 20 points each; the candidate is instructed to solve
five and to nominate which five are to be graded. Psychrometric
charts and a pressure–enthalpy diagram for ammonia (R-717) are appended to
the paper, and candidates are expected to bring an environmental-control text
and steam tables. Instruction 1 invites the candidate to state any
interpretation assumptions with the answer — that latitude is used
explicitly below where the printed data are redundant.
All eight problems are worked here. Every
psychrometric state has been recomputed from the ASHRAE formulation for
saturation vapour pressure rather than scaled off a chart, so the numbers are
tighter than a graphical solution would be; chart-quality agreement (about
±0.2 K and ±0.0002 kg/kg) is all that an examiner expects.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed., Butterworth-Heinemann — the standard reference for this examination code;
Ch. 2–3 (psychrometry), Ch. 6 (cooling loads), Ch. 10 (cooling towers),
Ch. 15 (duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist air), Ch. 8 (energy estimating and
degree-day methods), Ch. 12–13 (fluid flow and duct design).
ASHRAE Handbook – Fundamentals (2021) — Ch. 1 (psychrometrics), Ch. 21 (duct design),
Ch. 25–27 (heat, air and moisture transfer in the envelope).
Moran, Shapiro, Boettner & Bailey, Fundamentals of Engineering Thermodynamics, 9th ed., Wiley — Ch. 10 (vapour-compression and multistage
refrigeration).
ANSI/ASHRAE Standard 55, Thermal Environmental Conditions for Human
Occupancy, and ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable
Indoor Air Quality.
Canadian frame: National Building Code of Canada 2020, National Energy
Code of Canada for Buildings 2020, and Environment and Climate Change Canada
Canadian Climate Normals for degree-day data.
Psychrometric relations used throughout. At barometric
pressure $p$, with saturation vapour pressure $p_{ws}(t)$ from the ASHRAE
correlation,
in SI (kJ per kg of dry air), and in the inch-pound system
$h = 0.240\,t + W\,(1061 + 0.444\,t)$ Btu per lb of dry air. The
thermodynamic wet-bulb temperature is obtained from the adiabatic-saturation
equation, which is what a chart's constant-wet-bulb lines represent.
Given. A once-through (100% outdoor air) winter make-up air unit: preheat coil, adiabatic saturator, reheat coil, then the space.
Given data
Quantity
Value
Space sensible heat loss
200,000 Btu/h
Space latent load
negligible
Space design state
75 °F, 50% RH
Outdoor air
saturated at 20 °F
Ventilation air (100% outdoor)
7000 scfm
Adiabatic-saturator leaving dry bulb
60 °F
Find. the dry-bulb temperature of the air entering the space, the preheat and reheat coil duties in Btu/h, and the humidification water in US gpm.
System schematic. State 1 is outdoor air, 2 the preheat-coil outlet, 3 the adiabatic-saturator outlet held at 60 °F dry bulb, and 4 the supply air after reheat. All the air is exhausted from the space, so there is no return duct.
Approach. Because the space has no latent load, the supply air must carry the space moisture content, which fixes state 3; the adiabatic saturator follows a constant thermodynamic-wet-bulb line, so state 2 is the intersection of that line with the outdoor moisture content; the two coil duties and the water make-up then follow from mass and energy balances.
Moisture content the supply air must carry. With no latent load in the space, $W_4 = W_3 = W_{space}$. At 75 °F and 50% RH, $p_{ws} = 0.4300$ psia, so $$W_{space} = 0.6220\,\frac{0.50(0.4300)}{14.696 - 0.50(0.4300)} = \boxed{0.00924\ \text{lb/lb}}$$ The corresponding space wet bulb is 62.6 °F.
Outdoor air state 1. Saturated at 20 °F (over ice, $p_{ws} = 0.0505$ psia): $W_1 = 0.002144$ lb/lb and $$h_1 = 0.240(20) + 0.002144\,[1061 + 0.444(20)] = 7.09\ \text{Btu/lb}$$
State 3 leaving the adiabatic saturator. It is at 60 °F dry bulb and $W_3 = 0.00924$ lb/lb, which is 84% RH — a realistic outlet for a spray washer of about 85% saturating efficiency. Its enthalpy is $h_3 = 24.45$ Btu/lb and the adiabatic-saturation equation returns a thermodynamic wet bulb of $t^{*} = 57.1^\circ\text{F}$. This wet-bulb line is the humidification path.
State 2 leaving the preheat coil. Preheating is sensible, so $W_2 = W_1 = 0.002144$ lb/lb; state 2 is where the $t^{*} = 57.1^\circ\text{F}$ line meets that moisture content. Solving the adiabatic-saturation relation for dry bulb, $$t_2 = \frac{(1093 - 0.556\,t^{*})W^{*}_s + 0.240\,t^{*} - W_1(1093 - t^{*})}{0.240 + 0.444\,W_1} = \boxed{91.3^\circ\text{F}}$$ with $h_2 = 24.27$ Btu/lb. The preheat coil must therefore lift the outdoor air more than 70 F° before the washer can bring it to the required humidity.
Dry-air mass flow. Standard air is taken at 0.075 lb per cubic foot, so $$\dot{m}_a = 7000 \times 0.075 \times 60 = 31{,}500\ \text{lb of dry air per hour}$$
(i) Temperature of the air entering the space. The supply air must offset the sensible loss, with humid specific heat $c_p = 0.240 + 0.444(0.00924) = 0.2441$ Btu per lb per F°: $$\Delta t = \frac{200{,}000}{31{,}500 \times 0.2441} = 26.0\ \text{F}^\circ \;\Rightarrow\; t_4 = 75 + 26.0 = \boxed{101.0^\circ\text{F}}$$
(ii) Preheat coil duty. $$\dot{Q}_{pre} = \dot{m}_a\,(h_2 - h_1) = 31{,}500\,(24.267 - 7.094) = \boxed{541{,}000\ \text{Btu/h}}$$ or 158.5 kW — nearly three times the space heat loss, which is the price of 100% outdoor air at 20 °F.
(iii) Reheat coil duty. From 60 °F to 101.0 °F at constant moisture content, $$\dot{Q}_{re} = \dot{m}_a\,c_p\,(t_4 - t_3) = 31{,}500 \times 0.2441 \times (101.0 - 60) = \boxed{315{,}000\ \text{Btu/h}}$$ or 92.4 kW.
(iv) Humidification water. The washer must supply the moisture picked up between states 2 and 3: $$\dot{m}_w = \dot{m}_a\,(W_3 - W_1) = 31{,}500\,(0.00924 - 0.002144) = 223\ \text{lb/h}$$ and at 8.34 lb per US gallon, $$\dot{V}_w = \frac{223.4}{8.337 \times 60} = \boxed{0.447\ \text{gpm}}$$ About half a gallon a minute is the entire humidification demand; the recirculating spray pump handles many times that flow, and only the evaporated fraction is made up.
Operating cycle. Red 1→2: sensible preheat at constant humidity ratio. Green 2→3: adiabatic humidification along the 57.1 °F thermodynamic wet-bulb line. Red 3→4: sensible reheat to the 101.0 °F supply condition. Dashed gold 4→space: the space process, horizontal because the latent load is negligible.