NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · December 2016

Question 1 of 8: Summer air-conditioning plant for a department store

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. Professional Engineers of Ontario / Engineers Canada annual examination 07-Mec-B2 Environmental Control in Buildings, December 2016, three hours, open book. Eight problems of 20 points each; candidates are required to solve five, and all questions carry the same value. Psychrometric charts and an R-22 p-h diagram are appended to the paper. All eight problems are solved here.

Reference texts for this subject.

Check: assumptions carried through this paper. Cover-page instruction 1 invites a clear statement of any assumption. Standard barometric pressure of 101.325 kPa is used throughout; moist-air properties follow the ASHRAE Handbook — Fundamentals Ch. 1 formulation (Hyland–Wexler saturation pressure, so results agree with the appended chart to chart-reading accuracy rather than being read off it); R-22 properties are on the IIR datum and agree with the appended p-h diagram. Problem-specific assumptions — the coil bypass factor, climate and degree-day data, fuel prices and equipment efficiencies, duct roughness, and the CLTD / SCL / CLF table entries — are stated where they are first used.

Question 1: Summer air-conditioning plant for a department store (20 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A single-zone mixed-air plant serves a store held at 75 °F dry bulb and 50 % relative humidity against the design cooling load below, with ventilation air fixed at 30 % of the supply air by mass.

Given data, Problem 1
QuantitySymbolValue
Room dry bulb / relative humiditytR, φR75 °F, 50 %
Room sensible heat gainRSH450,000 Btu/h
Room latent heat gainRLH120,000 Btu/h
Outdoor dry bulb / relative humiditytO, φO90 °F, 60 %
Outdoor-air fraction of supply, by massx0.30
Barometric pressurep101.325 kPa (sea level)
Duct gain and fan temperature rise—neglected

Find. The system diagram and the cycle on the chart, the dry- and wet-bulb temperature of every significant state, the supply air rate, the coil capacity in kilowatts, the apparatus dew point and the coil bypass factor.

Conditioned space R 75 °F dB, 50 % RH RSH 450,000 Btu/h RLH 120,000 Btu/h Mix M Filter Fan Cooling coil outdoor air O 30 % by mass S return air (70 % by mass), state R relief to outdoors Once through the coil: all supply air is filtered, fanned and cooled together
Part (a) — plant arrangement. Return air is split: part is relieved to atmosphere and the remainder is mixed with 30 % outdoor air by mass at M, then filtered, fanned and cooled to the supply state S.

Approach. Fix the two known states from the ASHRAE moist-air relations, mix them in the stated mass ratio to get the coil entering state, close the one remaining degree of freedom with an assumed coil bypass factor, use the Carrier effective-sensible-heat-factor line to locate the apparatus dew point, and then read the air quantity, the supply state and the coil duty straight off the balances.

  1. Fix the room and outdoor states. The humidity ratio follows from the saturation pressure and the relative humidity, and the enthalpy from the standard inch-pound moist-air relation:$$W=0.622\,\frac{\phi\,p_{ws}}{p-\phi\,p_{ws}},\qquad h=0.240\,t+W\,(1061+0.444\,t)$$At 75 °F and 50 %, $W_{R}=0.009236\ \text{lb/lb}$ (64.6 grains per pound) and $h_{R}=28.11\ \text{Btu/lb}$; at 90 °F and 60 %, $W_{O}=0.018268\ \text{lb/lb}$ and $h_{O}=41.71\ \text{Btu/lb}$. The corresponding thermodynamic wet bulbs are 62.56 °F and 78.35 °F.
  2. Mix 30 % outdoor air with 70 % return air. Adiabatic mixing conserves moisture and enthalpy exactly, so both are mass-weighted and the dry bulb is recovered from them — never weighted directly, because the $W\,t$ cross term in the enthalpy relation would then leave $h(t_{M},W_{M})$ disagreeing with the mixed enthalpy:$$W_{M}=x\,W_{O}+(1-x)\,W_{R}=0.011945\ \text{lb/lb},\qquad h_{M}=x\,h_{O}+(1-x)\,h_{R}=32.19\ \text{Btu/lb}$$$$t_{M}=\frac{h_{M}-1061\,W_{M}}{0.240+0.444\,W_{M}}=79.55\ ^\circ\text{F}$$State M therefore sits at 79.55 °F dry bulb, 67.92 °F wet bulb — the air the coil actually sees.
  3. Recognise the missing degree of freedom, and close it. The room sensible heat factor is $\mathrm{RSHF}=450{,}000/570{,}000=0.7895$, which fixes the direction of the supply-to-room line but not how far down it the supply state lies. The paper gives no supply temperature, so one assumption is unavoidable; cover-page instruction 1 invites it. Assuming a coil bypass factor of 0.10, typical of a five- or six-row chilled-water coil at 500 fpm face velocity, is the better choice than assuming a supply temperature difference, because the bypass factor then reappears as an independent output in step 6 and verifies the whole construction.
  4. Form the effective heat factor and locate the apparatus dew point. The bypassed fraction of the outdoor air reaches the room unprocessed, so it is charged to the room rather than to the coil:$$\mathrm{ERSH}=\mathrm{RSH}+\mathrm{BF}\cdot\mathrm{OASH},\qquad \mathrm{ERLH}=\mathrm{RLH}+\mathrm{BF}\cdot\mathrm{OALH}$$with $\mathrm{OASH}=1.10\,Q_{O}(t_{O}-t_{R})=88,903$ Btu/h and $\mathrm{OALH}=4840\,Q_{O}(W_{O}-W_{R})=235,541$ Btu/h on the 5,388 cfm of outdoor air found below. That gives $\mathrm{ERSH}=458,890$ Btu/h, $\mathrm{ERLH}=143,554$ Btu/h and $\mathrm{ESHF}=0.7617$. Dropping a line of that slope from the room state until it meets the saturation curve gives$$\boxed{\ \mathrm{ADP}=49.19\ ^\circ\text{F}\ }$$The line must be drawn from R, not from M: the room-ratio line to saturation would give the room apparatus dew point, several degrees adrift of the coil's.
  5. Size the air supply rate. Only the $(1-\mathrm{BF})$ share of the air is brought all the way to the apparatus dew point, so the effective room sensible heat is carried by$$Q=\frac{\mathrm{ERSH}}{1.10\,(1-\mathrm{BF})\,(t_{R}-\mathrm{ADP})}=\frac{458,890}{1.10\times0.90\times(75-49.19)}$$$$\boxed{\ Q=17,960\ \text{cfm}\ }$$That is 8.48 m³/s, or about 82,463 lb of dry air per hour, of which 5,388 cfm is outdoor air — the 30 % the ventilation requirement calls for.
  6. Recover the supply state and check the bypass factor. The room balances give the supply condition directly:$$t_{S}=t_{R}-\frac{\mathrm{RSH}}{1.10\,Q}=52.22\ ^\circ\text{F},\qquad W_{S}=W_{R}-\frac{\mathrm{RLH}}{4840\,Q}=0.007855\ \text{lb/lb}$$so the supply air leaves the coil at 52.22 °F dry bulb and 51.40 °F wet bulb, a supply differential of about 23 F°. The bypass factor now follows from the finished state points, independently of the value assumed in step 3:$$\mathrm{BF}=\frac{t_{S}-\mathrm{ADP}}{t_{M}-\mathrm{ADP}}=\frac{52.22-49.19}{79.55-49.19}$$$$\boxed{\ \mathrm{BF}=0.100\ }$$It reproduces the assumed 0.10 to within a quarter of one per cent, which is what turns the assumption into a verified result.
  7. Compute the coil capacity. The coil takes the whole supply stream from M down to S, so its grand total heat is$$\mathrm{GTH}=4.5\,Q\,(h_{M}-h_{S})=4.5\times17,960\times(32.19-21.05)=900,213\ \text{Btu/h}$$$$\boxed{\ \dot{Q}_{\text{coil}}=263.8\ \text{kW}\ (75.0\ \text{tons})\ }$$As an independent check the same duty must equal the room load plus the whole outdoor-air load: $570{,}000+4.5\times5,388\times(41.71-28.11)=899,883$ Btu/h, agreeing to better than 0.1 %. Note how much of the plant the ventilation air costs: the room asks for 570,000 Btu/h and the coil has to be a third larger again.
40 50 60 70 80 90 100 .000 .004 .008 .012 .016 .020 .024 dry-bulb temperature, °F humidity ratio lb/lb dry air saturation 80% 60% 40% 20% O R M S ADP Department-store cycle, sea level (ASHRAE chart no. 1) coil line M → S extended to the saturation curve gives the apparatus dew point
Parts (b) and (c) — the cycle on the ASHRAE sea-level chart. Outdoor air O mixes with return air R at M, the coil brings the air along M–S toward the apparatus dew point, and the room process S–R closes the cycle along the room heat-factor line.

Part (c) asks for each significant point to be identified with its dry- and wet-bulb temperature, which the table below collects.

Part (c) — the significant state points
PointDescriptionDry bulb, °FWet bulb, °FW, lb/lbh, Btu/lb
Ooutdoor / ventilation air90.0078.350.01826841.71
Rroom and return air75.0062.560.00923628.11
Mmixed air, coil entry79.5567.920.01194532.19
Ssupply air, coil leaving52.2251.400.00785521.05
ADPapparatus dew point (saturated)49.1949.190.00780920.55
Problem 1 — results
QuantityValue
(d) Air supply rate17,960 cfm (8.48 m³/s)
   of which outdoor air5,388 cfm (30 % by mass)
(e) Coil capacity, grand total heat263.8 kW = 900,213 Btu/h = 75.0 tons
(f) Apparatus dew point49.19 °F
(g) Coil bypass factor0.100
Supply air condition52.22 °F dB, 51.40 °F wB
Mixed-air condition at the coil face79.55 °F dB, 67.92 °F wB
← Paper overview