22-Mec-B2 Environmental Control in Buildings · December 2016
Question 3 of 8: Annual energy and running cost by the degree-day method
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional
Engineers of Ontario / Engineers Canada annual examination
07-Mec-B2 Environmental Control in Buildings, December 2016,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same
value. Psychrometric charts and an R-22 p-h diagram are appended to the
paper. All eight problems are solved here.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this
examination code; Ch. 2–3 (psychrometry), Ch. 5–6 (heating
and cooling loads), Ch. 15 (fans and duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3
(moist air), Ch. 5 (heat transmission in building structures), Ch. 8
(energy estimating and the degree-day method), Ch. 12–13 (fluid
flow, fans and duct design).
ASHRAE Handbook — Fundamentals (2021) — Ch. 1
(psychrometrics), Ch. 14 (climatic design information), Ch. 18
(non-residential cooling and heating load calculations), Ch. 21 (duct
design), Ch. 26 (heat, air and moisture control), Ch. 30
(thermophysical properties of refrigerants).
Moran, Shapiro, Boettner & Bailey, Fundamentals of Engineering
Thermodynamics, 9th ed., Wiley — Ch. 10 (vapour-compression
refrigeration and heat pumps).
ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air
Quality; ANSI/ASHRAE Standard 55, Thermal Environmental
Conditions for Human Occupancy.
Canadian frame: National Building Code of Canada 2020
and its Appendix C design temperatures; National Energy Code of Canada
for Buildings 2020; Environment and Climate Change Canada degree-day
normals for Toronto and Ottawa; CSA B52 Mechanical Refrigeration
Code; Canada Green Building Council LEED Canada and the CaGBC Zero
Carbon Building Standard for Problem 5.
Check: assumptions carried through this
paper. Cover-page instruction 1 invites a clear statement of any
assumption. Standard barometric pressure of 101.325 kPa is used throughout;
moist-air properties follow the ASHRAE Handbook — Fundamentals Ch. 1
formulation (Hyland–Wexler saturation pressure, so results agree with
the appended chart to chart-reading accuracy rather than being read off it);
R-22 properties are on the IIR datum and agree with the appended p-h diagram. Problem-specific assumptions — the coil bypass factor, climate and
degree-day data, fuel prices and equipment efficiencies, duct roughness, and
the CLTD / SCL / CLF table entries — are stated where they are first
used.
Question 3: Annual energy and running cost by the degree-day method (20 points)
Given. A 5,000 ft² downtown Toronto office with the design loads and design conditions below, plus a steady winter internal gain.
Given data, Problem 3
Quantity
Symbol
Value
Floor area
A
50 ft × 100 ft = 5,000 ft²
Design heating load
qh
280,000 Btu/h at 75 / −5 °F
Design cooling load
qc
125,000 Btu/h at 78 / 91 °F
Average winter internal gain
qint
8 kW = 27,297 Btu/h
Natural gas price
—
$4.00 per thousand ft³
Electricity price
—
$0.10 per kWh
Toronto heating degree-days, base 65 °F
HDD65
7,002 °F·day (assumed)
Toronto cooling degree-days, base 65 °F
CDD65
707 °F·day (assumed)
Find. The annual heating and cooling energy requirements by the degree-day method, the annual energy cost of each of the two proposed systems, and recommendations for reducing them.
Check: climate and equipment assumptions. The paper supplies no degree-day data, so Toronto Pearson normals are used: HDD65 = 7,002 and CDD65 = 707 °F·day (Environment and Climate Change Canada / ASHRAE Fundamentals Ch. 14, converted from 3,890 and 393 °C·day at base 18.3 °C). The variable-base sensitivity is taken as 245 °F·day per °F of base near 65 °F, which is simply the number of days a year colder than that base. Equipment: electric resistance at COP 1.0, gas furnace at 80 % seasonal efficiency, natural gas at 1,000 Btu/ft³ higher heating value (so one MCF equals one MMBtu), and a "high efficiency" air conditioner at SEER 16.
Approach. Convert each design load into a building conductance, use the internal gain to move the heating balance point away from the nominal 65 °F base, integrate the demand with degree-days to that balance point, and then divide by each system's seasonal efficiency and multiply by its fuel price.
Turn the design loads into conductances. The degree-day method needs a heat-loss rate per degree, not a peak load:$$(UA)_{h}=\frac{q_{h}}{t_{i}-t_{o}}=\frac{280{,}000}{75-(-5)}=3,500\ \text{Btu/h}\cdot{}^\circ\text{F}^{-1}$$$$(UA)_{c}=\frac{q_{c}}{t_{o}-t_{i}}=\frac{125{,}000}{91-78}=9,615\ \text{Btu/h}\cdot{}^\circ\text{F}^{-1}$$The summer figure is much the larger because the design cooling load is mostly solar and internal gain rather than conduction — a warning that the cooling estimate will be the weaker of the two.
Find the heating balance point. The office does not need heat until the loss exceeds the internal gain:$$\Delta t_{\text{bal}}=\frac{q_{\text{int}}}{(UA)_{h}}=\frac{27,297}{3,500}=7.80\ \text{F}^\circ,\qquad t_{\text{bal}}=75-7.80=67.20\ ^\circ\text{F}$$This is the step the 8 kW datum exists for. Note that the balance point lands above the conventional 65 °F base, because the office is held at 75 °F rather than the 70 °F that the base-65 convention assumes; using HDD65 unadjusted would therefore understate the heating requirement.
Correct the degree-days to the balance point. At 245 °F·day per °F of base,$$\mathrm{HDD}_{t_{\text{bal}}}=7{,}002+245\times(67.20-65)=7,541\ ^\circ\text{F}\cdot\text{day}$$which corresponds to $\mathrm{EFLH}=24\,\mathrm{HDD}/(t_{i}-t_{o})=2,262$ equivalent full-load hours — a thoroughly plausible figure for southern Ontario and a useful sanity check on the whole calculation.
Annual heating energy delivered.$$Q_{h}=24\,(UA)_{h}\,\mathrm{HDD}_{t_{\text{bal}}}=24\times3,500\times7,541$$$$\boxed{\ Q_{h}=633.5\ \text{MMBtu/yr}\ }$$The internal gain is worth 160.5 MMBtu/yr of that: without it the balance point would be the room temperature itself and the demand would rise to $24\times3,500\times9,452/10^{6}$ MMBtu. At 126.7 kBtu/ft²·yr for heating alone this is a very leaky building by modern standards, which is the first clue for the recommendations.
Annual cooling energy removed. Applying the same method on the summer side, with the nominal base of 65 °F:$$Q_{c}=24\,(UA)_{c}\,\mathrm{CDD}_{65}=24\times9,615\times707$$$$\boxed{\ Q_{c}=163.2\ \text{MMBtu/yr}\ }$$This is the least trustworthy number in the problem: it implies 1,305 equivalent full-load cooling hours, roughly twice what a southern-Ontario office actually runs, because the small 13 F° design difference makes $(UA)_{c}$ absorb solar and internal gains that do not in fact scale with outdoor temperature. It is reported as the degree-day answer the question asks for, with the caveat attached.
Cost the two systems. Electric resistance delivers one kilowatt-hour of heat per kilowatt-hour bought, whereas the gas furnace burns 633.5/0.80 MMBtu of gas:$$\text{baseboard: }\frac{633.5\times10^{6}}{3412}\times\text{\$}0.10=\text{\$}18,565\ \text{per year}$$$$\text{furnace: }\frac{633.5}{0.80}\times\text{\$}4.00=791.8\ \text{MCF}\times\text{\$}4.00=\text{\$}3,167\ \text{per year}$$The air conditioner is common to both: $163.2\times10^{6}/16=10,197$ kWh, or $1,020 a year. Unit heat costs make the gap plain — $29.31 per MMBtu delivered by resistance against $5.00 per MMBtu delivered by an 80 % furnace.
Total annual energy cost.$$\boxed{\ \text{(a) baseboard + AC}=\text{\$}19,585\ \text{per year}\ }$$$$\boxed{\ \text{(b) gas furnace + AC}=\text{\$}4,187\ \text{per year}\ }$$Option (b) saves about $15,398 a year, and the heating bill alone falls by a factor of 5.86.
The balance-point construction on the left and the annual running costs on the right. The internal gain shifts the point at which heating is needed down from the room temperature to 67.20 °F; the cost bars show how completely the heating fuel choice dominates the annual bill.
Recommendations. The gas furnace is the obvious choice on running cost, but the more useful advice concerns the building rather than the fuel. A conductance of 3,500 Btu/h·°F over 5,000 ft² is 56 Btu/h·ft² at design, two to three times what NECB 2020 or the Toronto Green Standard would allow for new construction, so envelope work — air sealing first, then glazing and insulation — attacks the largest term directly and cuts both bills at once. A condensing furnace at 95 % AFUE would bring the gas cost down to about $2,667 a year for a modest premium. A heat-recovery ventilator recovers 60–80 % of the ventilation heat, which in Toronto is a large share of the seasonal total. Night and weekend setback exploits the fact that an office is unoccupied about two-thirds of the hours in the heating season. On the cooling side, exterior or interpane shading and daylight-linked lighting control cut the gain before it has to be removed, and an economiser gives free cooling through the long Toronto shoulder seasons. Finally, a cold-climate air-source heat pump in a dual-fuel arrangement with the gas furnace is now worth costing: at Ontario electricity prices it competes with gas above roughly −10 °C and, on Ontario's largely non-emitting grid, it reduces emissions substantially even where it does not reduce the bill.