22-Mec-B2 Environmental Control in Buildings · December 2016
Question 4 of 8: R-22 vapour-compression heat pump
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Professional
Engineers of Ontario / Engineers Canada annual examination
07-Mec-B2 Environmental Control in Buildings, December 2016,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same
value. Psychrometric charts and an R-22 p-h diagram are appended to the
paper. All eight problems are solved here.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this
examination code; Ch. 2–3 (psychrometry), Ch. 5–6 (heating
and cooling loads), Ch. 15 (fans and duct design).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3
(moist air), Ch. 5 (heat transmission in building structures), Ch. 8
(energy estimating and the degree-day method), Ch. 12–13 (fluid
flow, fans and duct design).
ASHRAE Handbook — Fundamentals (2021) — Ch. 1
(psychrometrics), Ch. 14 (climatic design information), Ch. 18
(non-residential cooling and heating load calculations), Ch. 21 (duct
design), Ch. 26 (heat, air and moisture control), Ch. 30
(thermophysical properties of refrigerants).
Moran, Shapiro, Boettner & Bailey, Fundamentals of Engineering
Thermodynamics, 9th ed., Wiley — Ch. 10 (vapour-compression
refrigeration and heat pumps).
ANSI/ASHRAE Standard 62.1, Ventilation for Acceptable Indoor Air
Quality; ANSI/ASHRAE Standard 55, Thermal Environmental
Conditions for Human Occupancy.
Canadian frame: National Building Code of Canada 2020
and its Appendix C design temperatures; National Energy Code of Canada
for Buildings 2020; Environment and Climate Change Canada degree-day
normals for Toronto and Ottawa; CSA B52 Mechanical Refrigeration
Code; Canada Green Building Council LEED Canada and the CaGBC Zero
Carbon Building Standard for Problem 5.
Check: assumptions carried through this
paper. Cover-page instruction 1 invites a clear statement of any
assumption. Standard barometric pressure of 101.325 kPa is used throughout;
moist-air properties follow the ASHRAE Handbook — Fundamentals Ch. 1
formulation (Hyland–Wexler saturation pressure, so results agree with
the appended chart to chart-reading accuracy rather than being read off it);
R-22 properties are on the IIR datum and agree with the appended p-h diagram. Problem-specific assumptions — the coil bypass factor, climate and
degree-day data, fuel prices and equipment efficiencies, duct roughness, and
the CLTD / SCL / CLF table entries — are stated where they are first
used.
Given. An air-source heat pump delivering 16 kW to a house at 20 °C from outdoor air at 4 °C, with R-22 leaving the evaporator as saturated vapour and the condenser as saturated liquid.
Given data and selected saturation states, Problem 4
Quantity
Symbol
Value
Heating duty
ṁH
16 kW
Indoor / outdoor temperature
ti, to
20 °C / 4 °C
Evaporating temperature (selected)
te
−6 °C
Condensing temperature (selected)
tc
40 °C
State 1, saturated vapour at te
h1
402.77 kJ/kg
State 2, isentropic discharge at pc
h2
436.02 kJ/kg
State 3, saturated liquid at tc
h3
249.65 kJ/kg
Find. Suitable evaporator and condenser pressures, then the refrigerant mass flow in kg/min, the compressor power and the coefficient of performance.
Approach. Choose saturation temperatures that give the heat exchangers a workable temperature difference against the two air streams, read the corresponding pressures and the four cycle enthalpies, and then apply steady-flow energy balances to each component.
Select the saturation temperatures, and hence the pressures. The evaporator must draw heat out of 4 °C air and the condenser must reject it into a 20 °C house, so each coil needs a temperature difference to work against. Taking about 10 K on the source side and 20 K on the sink side — ordinary values for finned-tube air coils — gives $t_{e}=-6.0\ ^\circ\text{C}$ and $t_{c}=40.0\ ^\circ\text{C}$, and the R-22 saturation line then fixes$$\boxed{\ p_{e}=407.7\ \text{kPa},\qquad p_{c}=1,533.6\ \text{kPa}\ }$$a pressure ratio of 3.76, comfortably inside the single-stage range for a reciprocating or scroll machine.
Fix the four cycle states. State 1 is saturated vapour at $p_{e}$, so $h_{1}=402.77$ kJ/kg. Compression is taken as isentropic to $p_{c}$, giving $h_{2}=436.02$ kJ/kg at about 61 °C discharge. State 3 is saturated liquid at $p_{c}$, $h_{3}=249.65$ kJ/kg, and the expansion valve is a throttle, so$$h_{4}=h_{3}=249.65\ \text{kJ/kg}$$The specific duties follow immediately: $q_{\text{cond}}=h_{2}-h_{3}=186.37$ kJ/kg, $w=h_{2}-h_{1}=33.25$ kJ/kg and $q_{\text{evap}}=h_{1}-h_{4}=153.12$ kJ/kg, which satisfy $q_{\text{cond}}=q_{\text{evap}}+w$ exactly.
Mass flow, part (a). The condenser is the useful output, so it sets the flow:$$\dot{m}=\frac{\dot{Q}_{H}}{h_{2}-h_{3}}=\frac{16}{186.37}=0.08585\ \text{kg/s}$$$$\boxed{\ \dot{m}=5.1510\ \text{kg/min}\ }$$
Compressor power, part (b).$$\dot{W}=\dot{m}\,(h_{2}-h_{1})=0.08585\times33.25$$$$\boxed{\ \dot{W}=2.855\ \text{kW}\ }$$The evaporator therefore lifts 13.15 kW out of the outdoor air, and 13.15 + 2.855 returns the 16 kW delivered indoors, as it must.
Coefficient of performance, part (c).$$\mathrm{COP}_{\text{hp}}=\frac{\dot{Q}_{H}}{\dot{W}}=\frac{h_{2}-h_{3}}{h_{2}-h_{1}}=\frac{186.37}{33.25}$$$$\boxed{\ \mathrm{COP}=5.605\ }$$Against the reversible limit for the two air temperatures, $\mathrm{COP}_{\text{Carnot}}=T_{i}/(T_{i}-T_{o})=293.15/16=18.32$, the cycle achieves a second-law efficiency of 0.306. Almost all of that shortfall is the 30 K of heat-exchanger temperature difference deliberately chosen in step 1, not compressor irreversibility — which is why oversizing the coils is the cheapest way to raise seasonal performance.
[Figure not reproduced: The cycle on the R-22 p–h diagram appended to the examination paper. The condensing and evaporating pressures are the two horizontal legs; the throttle 3–4 is vertical because it is isenthalpic. See the official exam paper.]
Two design remarks belong with the numbers. First, R-22 is an HCFC and is no longer available for new equipment in Canada — the Ozone-depleting Substances and Halocarbon Alternatives Regulations (SOR/2016-137) ended imports for new systems — so a machine of this kind would today be built on R-410A or R-454B; the analysis is unchanged, only the property table moves. Second, the 16 kW duty at 4 °C says nothing about the design day: at the NBCC Appendix C 2.5 % winter temperature the same house would need substantially more heat while the machine would deliver substantially less, so supplementary heat and a balance-point analysis are part of any real selection.