22-Mec-B2 Environmental Control in Buildings · December 2017
Question 1 of 8: Summer air-conditioning plant — cycle, load and energy input
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Engineers Canada national
examination 16-Mec-B2 Environmental Control in Buildings, December 2017,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same value.
ASHRAE Psychrometric Chart No. 1 (SI and inch-pound) and a pressure–enthalpy
diagram for R-717 are appended to the paper as pages 6–8.
All eight problems are worked here. The paper mixes SI and inch-pound units deliberately:
Problems 1, 3 and 4 are SI, Problems 2, 6 and 7 are inch-pound, and Problem 8 is
SI with a Canadian climate. Each solution is worked in the units the question
uses, as the cover-page instructions require.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this examination code;
Ch. 2–3 (psychrometry and the psychrometric chart), Ch. 6 (air-conditioning
plant cycles), Ch. 7 (the cooling coil, apparatus dew point and by-pass factor),
Ch. 9 (cooling towers), Ch. 15 (fans).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist air),
Ch. 5 (heat transmission in building structures), Ch. 8 (energy estimating and the
degree-day method), Ch. 12 (fans and duct design).
ASHRAE Handbook — Fundamentals — Ch. 1 (psychrometrics),
Ch. 14 (climatic design information), Ch. 21 (duct design), Ch. 25–27
(thermal and moisture performance of the building envelope), Ch. 30 (fenestration).
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed.,
McGraw-Hill — Ch. 10–12 (vapour-compression cycle, compressors,
condensers and evaporators); ASHRAE Handbook — Refrigeration for
ammonia plant practice.
National Building Code of Canada and the National Energy Code of Canada for
Buildings (NRC), Appendix C climatic data; CSA and Canada Green Building Council
material for Problem 5.
Property basis used throughout. Moist-air
properties are computed from the ASHRAE Fundamentals ideal-moist-air
relations, so every state quoted here can be read back off the psychrometric chart
supplied with the paper:
with $h$ in $\text{kJ/kg}$ of dry air for $t$ in $\,{}^{\circ}\text{C}$ and in
$\text{Btu/lb}$ of dry air for $t$ in $\,{}^{\circ}\text{F}$. Ammonia properties
are quoted on the same datum as the attached ASHRAE p–h diagram
($h_f=200\ \text{kJ/kg}$ and $s_f=1.0\ \text{kJ/(kg}\cdot\text{K)}$ for saturated
liquid at $0\,{}^{\circ}\text{C}$); only differences enter the answers, so any
consistent chart or table gives the same duties.
Question 1: Summer air-conditioning plant — cycle, load and energy input
(20 points)
Find. The complete plant diagram and psychrometric cycle with
every state point characterised, the total room air-conditioning load, the total
energy input to the plant, and the energy input when the heating coil is served by
condenser heat recovery instead of a separate heat source.
Part (a) — the plant: outdoor air mixes with three parts of recirculated air at M, is cooled and dehumidified to C, sensibly reheated to S, and delivered to the room. The dashed lines show the chilled-water and condenser-water connections.
Approach. Fix the three given states from the chart, take the
room load directly as the enthalpy the supply air absorbs, close the adiabatic
mixing balance for M, place the off-coil state C on the line from M to the
apparatus dew point at the supply humidity ratio, and then split the plant duty
between the refrigeration machine and the heater.
Part (c) — fix the three given state points. With
$p=101.325\ \text{kPa}$ and $p_{ws}$ from steam tables, $W=0.621945\,p_w/(p-p_w)$
and $h=1.006\,t+W(2501+1.86\,t)$:
Point
Description
$t$ (°C db)
$W$ (g/kg)
$h$ (kJ/kg)
$\phi$ (%)
$t_{wb}$ (°C)
$v$ (m³/kg)
O
outdoor air
27.00
15.72
67.26
70.0
22.78
0.8718
R
room / return
20.00
7.26
38.56
50.0
13.78
0.8402
S
supply to room
14.00
5.95
29.11
60.0
9.95
0.8212
Part (d) — the room load is the enthalpy the supply air picks
up. The supply air enters at S and leaves at the room state R, so
$$\dot Q_{\text{room}}=\dot m\,(h_R-h_S)=1.8\times(38.56-29.11)
=\boxed{17.01\ \text{kW}}$$
Splitting it, the latent part is carried by the moisture the air picks up and the
sensible part is the remainder:
$$\dot Q_L=\dot m\,h_{fg}\,(W_R-W_S)=1.8\times2501\times(0.007263-0.005945)
=5.93\ \text{kW}$$
$$\dot Q_S=\dot Q_{\text{total}}-\dot Q_L=17.01-5.93=11.07\ \text{kW},
\qquad \text{SHR}=\frac{11.07}{17.01}=0.651$$
Mix the outdoor and recirculated streams at M. A
recirculated-to-fresh ratio of 3 means the outdoor-air fraction is
$x=1/(1+3)=0.25$, i.e. $0.45\ \text{kg/s}$ of outdoor air and
$1.35\ \text{kg/s}$ of return air. Adiabatic mixing is exact in moisture
and in enthalpy, so both are mass-weighted:
$$W_M=x\,W_O+(1-x)\,W_R=0.25(15.72)+0.75(7.26)=9.377\ \text{g/kg}$$
$$h_M=x\,h_O+(1-x)\,h_R=0.25(67.26)+0.75(38.56)=45.73\ \text{kJ/kg}$$
The dry bulb then follows from the enthalpy relation rather than from weighting
$t$ directly:
$$t_M=\frac{h_M-2501\,W_M}{1.006+1.86\,W_M}
=\frac{45.73-2501(0.009377)}{1.006+1.86(0.009377)}=21.77\,{}^{\circ}\text{C}$$
so M is $21.77\,{}^{\circ}\text{C}$ db, $57.7\%$ RH.
Locate the off-coil state C. The cooling coil drives the
air along the straight line from M toward its apparatus dew point —
saturated air at $5\,{}^{\circ}\text{C}$, for which
$W_{adp}=5.403\ \text{g/kg}$ and $h_{adp}=18.59\ \text{kJ/kg}$. The heating coil
downstream is sensible only, so it cannot change the humidity ratio; the air must
therefore leave the cooling coil already at the supply humidity ratio,
$W_C=W_S=5.945\ \text{g/kg}$. The position along the coil line is the contact
factor
$$\lambda=\frac{W_S-W_M}{W_{adp}-W_M}=\frac{5.945-9.377}{5.403-9.377}=0.8635,
\qquad \text{BF}=1-\lambda=0.137$$
$$t_C=t_M+\lambda\,(t_{adp}-t_M)=21.77+0.8635\,(5-21.77)
=7.29\,{}^{\circ}\text{C}$$
which is $93.9\%$ RH — a realistic leaving condition for a four-row
chilled-water coil, and the by-pass factor of $0.137$ confirms it. Then
$h_C=22.28\ \text{kJ/kg}$.
Coil and heater duties. Both follow from the same mass
flow across their own enthalpy differences:
$$\dot Q_{cc}=\dot m\,(h_M-h_C)=1.8\,(45.73-22.28)=\boxed{42.21\ \text{kW}}$$
$$\dot Q_{hc}=\dot m\,(h_S-h_C)=1.8\,(29.11-22.28)=\boxed{12.28\ \text{kW}}$$
Check the whole plant: what the coil removes, less what the heater puts back, must
equal the room load plus the load the outdoor air imposes,
$\dot m x (h_O-h_R)=0.45(67.26-38.56)=12.92\ \text{kW}$. Indeed
$42.21-12.28=29.93=17.01+12.92\ \text{kW}$ — the balance closes exactly.
Part (e) — total energy input. The refrigeration
machine has an overall COP of 2, so it needs
$$\dot W_{\text{ref}}=\frac{\dot Q_{cc}}{\text{COP}}=\frac{42.21}{2}
=21.11\ \text{kW}$$
and the heating coil draws its $12.28\ \text{kW}$ from a separate source, giving
$$\dot E_{\text{total}}=21.11+12.28=\boxed{33.39\ \text{kW}}$$
Part (f) — heating from condenser heat recovery.
The condenser must reject everything the evaporator absorbed plus the work put in:
$$\dot Q_{\text{cond}}=\dot Q_{cc}+\dot W_{\text{ref}}=42.21+21.11
=63.32\ \text{kW}$$
That is more than five times the $12.28\ \text{kW}$ the heating coil needs, and
the condenser water leaves at roughly $35\,{}^{\circ}\text{C}$ — far above
the $14\,{}^{\circ}\text{C}$ the reheat coil has to reach — so the reheat is
available at no extra energy cost. The purchased input is then the compressor
alone:
$$\dot E_{\text{total}}=\dot W_{\text{ref}}=\boxed{21.11\ \text{kW}}$$
a saving of $12.28\ \text{kW}$, or $36.8\%$ of the energy input of part (e).
Part (b) — the cycle on ASHRAE Chart No. 1. M lies one quarter of the way along R→O, the coil line M→C aims at the 5 °C apparatus dew point (dashed extension), C→S is the sensible reheat, and S→R is the room load line at SHR = 0.651.
Check: assumptions declared under cover-page instruction 1.
(i) The plant order is mix → cooling coil → heating coil → fan, which
is the order the question lists and the only order in which a coil with a
$5\,{}^{\circ}\text{C}$ apparatus dew point can produce a $14\,{}^{\circ}\text{C}$
supply at $60\%$ RH. (ii) The heating coil is taken as purely sensible, which fixes
$W_C=W_S$ and hence the off-coil state; without it the split between coil and heater
is indeterminate. (iii) Fan and pump work and duct gains are neglected as
instructed, so the state leaving the fan is the state entering the room. (iv) In
part (f) the recovered heat is treated as free because the condenser must reject it
anyway; in practice a desuperheater or a double-bundle condenser is needed, and the
condenser water circuit then does slightly more pump work.