22-Mec-B2 Environmental Control in Buildings · December 2017
Question 4 of 8: Ammonia cold-storage plant for a milk chilling duty
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Engineers Canada national
examination 16-Mec-B2 Environmental Control in Buildings, December 2017,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same value.
ASHRAE Psychrometric Chart No. 1 (SI and inch-pound) and a pressure–enthalpy
diagram for R-717 are appended to the paper as pages 6–8.
All eight problems are worked here. The paper mixes SI and inch-pound units deliberately:
Problems 1, 3 and 4 are SI, Problems 2, 6 and 7 are inch-pound, and Problem 8 is
SI with a Canadian climate. Each solution is worked in the units the question
uses, as the cover-page instructions require.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this examination code;
Ch. 2–3 (psychrometry and the psychrometric chart), Ch. 6 (air-conditioning
plant cycles), Ch. 7 (the cooling coil, apparatus dew point and by-pass factor),
Ch. 9 (cooling towers), Ch. 15 (fans).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist air),
Ch. 5 (heat transmission in building structures), Ch. 8 (energy estimating and the
degree-day method), Ch. 12 (fans and duct design).
ASHRAE Handbook — Fundamentals — Ch. 1 (psychrometrics),
Ch. 14 (climatic design information), Ch. 21 (duct design), Ch. 25–27
(thermal and moisture performance of the building envelope), Ch. 30 (fenestration).
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed.,
McGraw-Hill — Ch. 10–12 (vapour-compression cycle, compressors,
condensers and evaporators); ASHRAE Handbook — Refrigeration for
ammonia plant practice.
National Building Code of Canada and the National Energy Code of Canada for
Buildings (NRC), Appendix C climatic data; CSA and Canada Green Building Council
material for Problem 5.
Property basis used throughout. Moist-air
properties are computed from the ASHRAE Fundamentals ideal-moist-air
relations, so every state quoted here can be read back off the psychrometric chart
supplied with the paper:
with $h$ in $\text{kJ/kg}$ of dry air for $t$ in $\,{}^{\circ}\text{C}$ and in
$\text{Btu/lb}$ of dry air for $t$ in $\,{}^{\circ}\text{F}$. Ammonia properties
are quoted on the same datum as the attached ASHRAE p–h diagram
($h_f=200\ \text{kJ/kg}$ and $s_f=1.0\ \text{kJ/(kg}\cdot\text{K)}$ for saturated
liquid at $0\,{}^{\circ}\text{C}$); only differences enter the answers, so any
consistent chart or table gives the same duties.
Question 4: Ammonia cold-storage plant for a milk chilling duty
(20 points)
Find. The plant sketch and the cycle on the attached R-717
p–h diagram, then the compressor shaft power, the swept volume of each
cylinder, and the volumetric rate of brine circulation.
Part (a) — the plant. Ammonia circulates 1→2→3→4 between the evaporator and the condenser; a secondary brine circuit carries the duty from the evaporator to the milk coolers, its temperature rise limited to 3 K.
Approach. Add the two components of the evaporator duty, fix the
four cycle states from the ammonia tables, take the refrigerating effect per unit
mass to get the refrigerant flow, and then take the compressor work, the induced
volume and the brine flow in turn.
Evaporator duty. The milk mass flow follows from the
volumetric throughput and density:
$$\dot m_m=\frac{9000}{1000}\times\frac{1030}{3600}=2.575\ \text{kg/s}$$
$$\dot Q_{milk}=\dot m_m\,c_{p,m}\,\Delta t=2.575\times3.77\times(27-4)
=223.28\ \text{kW}$$
Adding the plant heat gain of $3600/60=60\ \text{kW}$,
$$\dot Q_e=223.28+60=\boxed{283.28\ \text{kW}}$$
which is $80.6$ tons of refrigeration — a substantial industrial plant, and
consistent with a slow-speed reciprocating ammonia machine.
Part (b) — fix the four cycle states. State 1 is dry
saturated vapour at $-6\,{}^{\circ}\text{C}$; state 2 is the isentropic end point at
the delivery pressure; state 3 is liquid undercooled to $24\,{}^{\circ}\text{C}$ at
that same pressure; and state 4 follows from throttling at constant enthalpy.
Point
Description
$p$ (bar)
$t$ (°C)
$h$ (kJ/kg)
$s$ (kJ/kg·K)
$v$ (m³/kg)
1
dry saturated vapour, compressor suction
3.41
−6.0
1455.1
5.700
0.3597
2
after isentropic compression
10.34
71.0
1609.6
5.700
—
3
undercooled liquid leaving the condenser
10.34
24.0
312.7
—
—
4
after throttling, wet vapour
3.41
−6.0
312.7
—
—
At $10.34\ \text{bar}$ ammonia condenses at $26.0\,{}^{\circ}\text{C}$, so the
stated $24\,{}^{\circ}\text{C}$ liquid represents $2\ \text{K}$ of undercooling
— a modest and entirely realistic figure. Compression ends at
$71\,{}^{\circ}\text{C}$, well within the $150\,{}^{\circ}\text{C}$ limit that
governs ammonia discharge temperatures.
Refrigerating effect and refrigerant mass flow. The
evaporator takes the fluid from state 4 to state 1, so
$$q_e=h_1-h_4=1455.1-312.7=1142.3\ \text{kJ/kg}$$
$$\dot m_r=\frac{\dot Q_e}{q_e}=\frac{283.28}{1142.3}
=\boxed{0.2480\ \text{kg/s}}\quad(893\ \text{kg/h})$$
The undercooling is worth having: without it the liquid would enter the throttle at
$26\,{}^{\circ}\text{C}$ and the refrigerating effect would fall by roughly
$10\ \text{kJ/kg}$, requiring about $1\%$ more refrigerant for the same duty.
Part (c)(i) — compressor power. Isentropic compression
work per unit mass, then the indicated power, then the shaft power through the
mechanical efficiency:
$$w=h_2-h_1=1609.6-1455.1=154.6\ \text{kJ/kg}$$
$$\dot W_{ind}=\dot m_r\,w=0.2480\times154.6=38.33\ \text{kW}$$
$$\dot W_{shaft}=\frac{\dot W_{ind}}{\eta_m}=\frac{38.33}{0.90}
=\boxed{42.59\ \text{kW}}$$
The plant coefficient of performance on shaft power is
$\text{COP}=283.28/42.59=6.65$ (ideal, on indicated power, $7.39$), which is what
one expects of ammonia working across only $32\ \text{K}$ of temperature lift. The
condenser must reject $\dot m_r(h_2-h_3)=321.6\ \text{kW}$.
Part (c)(ii) — swept volume per cylinder. The volume
the compressor actually induces is the mass flow times the suction specific volume;
the swept volume is larger by the reciprocal of the volumetric efficiency, which
accounts for re-expansion of the clearance gas:
$$\dot V_{ind}=\dot m_r\,v_1=0.2480\times0.3597=0.08921\ \text{m}^3/\text{s}$$
$$\dot V_{swept}=\frac{\dot V_{ind}}{\eta_v}=\frac{0.08921}{0.85}
=0.10495\ \text{m}^3/\text{s}$$
Single acting means one induction stroke per revolution per cylinder, so at
$200\ \text{rpm}$ with two cylinders the machine completes
$2\times200/60=6.667$ induction strokes per second:
$$V_{cyl}=\frac{0.10495}{6.667}=\boxed{0.01574\ \text{m}^3=15.74\ \text{litres}}$$
For a square engine ($\text{bore}=\text{stroke}$) that is a bore of
$272\ \text{mm}$ — a large, slow, industrial ammonia compressor, exactly the
machine the stated $200\ \text{rpm}$ implies.
Part (c)(iii) — brine circulation rate. The brine
carries the whole evaporator duty from the chiller to the milk coolers, and its
temperature rise is limited to $3\ \text{K}$:
$$\dot m_b=\frac{\dot Q_e}{c_{p,b}\,\Delta t_b}=\frac{283.28}{2.93\times3}
=32.23\ \text{kg/s}$$
$$\dot V_b=\frac{\dot m_b}{\rho_b}=\frac{32.23}{1190}\times1000
=\boxed{27.08\ \text{L/s}}$$
which is $97.5\ \text{m}^3/\text{h}$. The narrow $3\ \text{K}$ rise is what makes
the flow so large; it is specified to keep the brine temperature nearly uniform
through the milk coolers, and it is the price paid for using a secondary refrigerant
rather than expanding ammonia directly in a food-contact heat exchanger.
Part (b) — the cycle on the attached R-717 pressure–enthalpy diagram. 1→2 isentropic compression, 2→3 desuperheating, condensation and 2 K of undercooling, 3→4 throttling at constant enthalpy, 4→1 evaporation to dry saturated vapour.
Final results.
Quantity
Result
Milk cooling load
$223.28\ \text{kW}$
Evaporator duty (with heat gain)
$283.28\ \text{kW}$ ($80.6\ \text{TR}$)
Refrigerating effect
$1142.3\ \text{kJ/kg}$
Refrigerant mass flow
$0.2480\ \text{kg/s}$ ($893\ \text{kg/h}$)
Isentropic work
$154.6\ \text{kJ/kg}$; indicated power $38.33\ \text{kW}$
Check: assumptions declared under cover-page instruction 1.
(i) Ammonia properties are quoted on the datum of the attached ASHRAE p–h
diagram ($h_f=200\ \text{kJ/kg}$ at $0\,{}^{\circ}\text{C}$); only the differences
$h_1-h_4$ and $h_2-h_1$ enter the answers, so any consistent set of tables gives the
same duties. (ii) The stated plant heat gain of $3600\ \text{kJ/min}$ is taken as an
additional load on the evaporator, which is where a cold-store cabinet gain must
appear. (iii) Pressure drops in the suction and discharge lines are neglected, so the
suction state is the saturated state at $-6\,{}^{\circ}\text{C}$ as stated. (iv)
"Single acting" is read literally — one induction stroke per revolution per
cylinder; a double-acting machine of the same duty would need half this swept volume.
(v) The two densities printed at the foot of the question are matched to the fluids
by physical sense: $1030\ \text{kg/m}^3$ is whole milk and $1190\ \text{kg/m}^3$ a
calcium-chloride brine.