22-Mec-B2 Environmental Control in Buildings · December 2017
Question 8 of 8: Seasonal gas consumption of an R-2000 house and the value of night setback
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. Engineers Canada national
examination 16-Mec-B2 Environmental Control in Buildings, December 2017,
three hours, open book. Eight problems of 20 points each;
candidates are required to solve five, and all questions carry the same value.
ASHRAE Psychrometric Chart No. 1 (SI and inch-pound) and a pressure–enthalpy
diagram for R-717 are appended to the paper as pages 6–8.
All eight problems are worked here. The paper mixes SI and inch-pound units deliberately:
Problems 1, 3 and 4 are SI, Problems 2, 6 and 7 are inch-pound, and Problem 8 is
SI with a Canadian climate. Each solution is worked in the units the question
uses, as the cover-page instructions require.
Reference texts for this subject.
W. P. Jones, Air Conditioning Engineering, 5th ed.,
Butterworth-Heinemann — the standard reference for this examination code;
Ch. 2–3 (psychrometry and the psychrometric chart), Ch. 6 (air-conditioning
plant cycles), Ch. 7 (the cooling coil, apparatus dew point and by-pass factor),
Ch. 9 (cooling towers), Ch. 15 (fans).
McQuiston, Parker & Spitler, Heating, Ventilating and Air
Conditioning: Analysis and Design, 6th ed., Wiley — Ch. 3 (moist air),
Ch. 5 (heat transmission in building structures), Ch. 8 (energy estimating and the
degree-day method), Ch. 12 (fans and duct design).
ASHRAE Handbook — Fundamentals — Ch. 1 (psychrometrics),
Ch. 14 (climatic design information), Ch. 21 (duct design), Ch. 25–27
(thermal and moisture performance of the building envelope), Ch. 30 (fenestration).
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed.,
McGraw-Hill — Ch. 10–12 (vapour-compression cycle, compressors,
condensers and evaporators); ASHRAE Handbook — Refrigeration for
ammonia plant practice.
National Building Code of Canada and the National Energy Code of Canada for
Buildings (NRC), Appendix C climatic data; CSA and Canada Green Building Council
material for Problem 5.
Property basis used throughout. Moist-air
properties are computed from the ASHRAE Fundamentals ideal-moist-air
relations, so every state quoted here can be read back off the psychrometric chart
supplied with the paper:
with $h$ in $\text{kJ/kg}$ of dry air for $t$ in $\,{}^{\circ}\text{C}$ and in
$\text{Btu/lb}$ of dry air for $t$ in $\,{}^{\circ}\text{F}$. Ammonia properties
are quoted on the same datum as the attached ASHRAE p–h diagram
($h_f=200\ \text{kJ/kg}$ and $s_f=1.0\ \text{kJ/(kg}\cdot\text{K)}$ for saturated
liquid at $0\,{}^{\circ}\text{C}$); only differences enter the answers, so any
consistent chart or table gives the same duties.
Question 8: Seasonal gas consumption of an R-2000 house and the value of night
setback (20 points)
$4500\ {}^{\circ}\text{C}\cdot\text{day}$ (NBC Appendix C)
Degree-day correction factor
$C_D$
$0.65$
Setback
$\Delta t_{sb}$, hours
$4\ \text{K}$ for $7\ \text{h}$ of every $24$
Find. The annual natural-gas consumption, and the saving that
results from a $4\ \text{K}$ night setback held for seven hours a day.
Approach. Convert the design heat loss into a building loss
coefficient, apply the modified degree-day method with Ottawa climatic data to get
the seasonal heat requirement, and divide by the furnace efficiency and the heating
value. For the setback, treat the seven setback hours as a season at a lower base
temperature and re-sum.
Building loss coefficient. The design heat loss is the
product of the coefficient and the design temperature difference, so
$$UA=\frac{\dot q_{design}}{t_i-t_o}=\frac{10}{22-(-25)}=\frac{10}{47}
=0.2128\ \text{kW/K}$$
This single number carries the whole envelope — transmission plus infiltration
— and it is all the degree-day method needs.
Climatic data. Appendix C of the National Building Code
gives Ottawa a January $2.5\%$ design temperature of $-25\,{}^{\circ}\text{C}$
— which is exactly the value the question uses, confirming the data set —
and $4500\ {}^{\circ}\text{C}\cdot\text{day}$ of heating degree-days below
$18\,{}^{\circ}\text{C}$.
Part (a) — seasonal heat requirement. The modified
degree-day method scales the design loss by the accumulated temperature deficit and
applies an empirical correction:
$$Q_{annual}=24\;UA\;\text{HDD}_{18}\;C_D
=24\times0.2128\times4500\times0.65$$
$$Q_{annual}=14{,}940\ \text{kWh}=53{,}770\ \text{MJ}$$
The factor $C_D$ — here taken as $0.65$ — corrects for the two effects the
raw degree-day sum ignores: internal gains from occupants, lighting and appliances,
which are relatively large in a well-sealed R-2000 house, and the fact that a furnace
runs less efficiently at part load than at its rated output. Values between $0.60$ and
$0.70$ are standard for a modern Canadian house.
Part (a) — gas volume. Dividing by the furnace
efficiency and the heating value:
$$V_{gas}=\frac{Q_{annual}}{\eta_f\,HV}=\frac{53{,}770}{0.85\times37}
=\boxed{1710\ \text{m}^3/\text{yr}}$$
about $4.7\ \text{m}^3$ a day averaged over the year, or $63\ \text{GJ}$ of purchased
gas. Sanity-check it as equivalent full-load hours:
$$\text{EFLH}=\frac{24\,\text{HDD}\,C_D}{t_i-t_o}
=\frac{24\times4500\times0.65}{47}=1494\ \text{h}$$
so the furnace runs the equivalent of about $1500$ hours a year at full output, which
is the right order for southern Ontario and confirms the arithmetic.
Part (b) — how a setback actually saves energy. The
saving is not simply the fraction of time multiplied by the fraction of
temperature difference. Lowering the thermostat by $4\ \text{K}$ lowers the balance
temperature of the house by the same $4\ \text{K}$, so during the setback hours the
house is losing heat against a base of $14\,{}^{\circ}\text{C}$ rather than
$18\,{}^{\circ}\text{C}$ — and a degree-day total measured to a lower base is
smaller, because the hours when the outdoor temperature lies between the two bases now
contribute nothing at all. The seasonal heat is therefore re-summed with the day split
between the two bases:
$$Q_{sb}=UA\,C_D\big[(24-7)\,\text{HDD}_{18}+7\,\text{HDD}_{14}\big]$$
Part (b) — the degree-days at the lower base. Near a
base of $18\,{}^{\circ}\text{C}$ the sensitivity of the degree-day total to the base
temperature is, by definition, the number of days a year colder than that base —
about $295\ {}^{\circ}\text{C}\cdot\text{day}$ per kelvin for Ottawa. Hence
$$\text{HDD}_{14}=4500-4\times295=3320\ {}^{\circ}\text{C}\cdot\text{day}$$
$$Q_{sb}=0.2128\times0.65\times\big[17(4500)+7(3320)\big]
=0.1383\times99{,}740=13{,}790\ \text{kWh}$$
Part (b) — the saving. Comparing with the
$14{,}940\ \text{kWh}$ of part (a):
$$\Delta Q=14{,}940-13{,}790=1150\ \text{kWh}\ \text{per year}$$
$$\text{saving}=\frac{1150}{14{,}940}=\boxed{7.6\%}$$
$$\Delta V_{gas}=\frac{1150\times3.6}{0.85\times37}
=\boxed{131\ \text{m}^3/\text{yr}}$$
leaving an annual consumption of about $1580\ \text{m}^3$. At a delivered gas price of
roughly $\$0.40$ per cubic metre this is on the order of $\$50$ a year — real,
but modest, and worth stating plainly to a client who has been promised more.
Why the saving is smaller than intuition suggests, and what limits
it. A naive calculation — $7/24$ of the time at $4/47$ less temperature
difference — gives only $2.5\%$, because it wrongly scales against the
design difference rather than the seasonal average. The correct degree-day
treatment gives $7.6\%$. Two practical qualifications cut into even that. First,
thermal mass: the house does not reach $18\,{}^{\circ}\text{C}$ the moment the
thermostat drops, so the effective setback period is shorter than seven hours —
in a heavy house perhaps four or five. Second, the recovery penalty: at the end of the
setback the furnace must supply the steady loss plus the energy to re-warm the
structure. The extra steady capacity needed is only
$UA\,\Delta t_{sb}=0.2128\times4=0.85\ \text{kW}$ against $9.15\ \text{kW}$ of spare
capacity at design conditions, so the furnace can recover even on the coldest night;
but the recovery is at full fire, and an over-aggressive setback in a house with an
undersized furnace will simply fail to recover by morning. The realistic expectation is
therefore $5$–$7\%$, and the setback should be ramped back an hour before
occupancy rather than stepped.
The setback schedule. Because the balance temperature falls with the thermostat, the seven setback hours must be summed against a 14 °C degree-day base and the remaining seventeen against 18 °C.
$\mathbf{7.6\%}$, i.e. $1150\ \text{kWh}$ or $\mathbf{131\ \text{m}^3}$ of gas a year
Consumption with setback
$1580\ \text{m}^3/\text{yr}$
Extra capacity needed for recovery
$0.85\ \text{kW}$ against $9.15\ \text{kW}$ spare
Check: assumptions declared under cover-page instruction 1.
The question supplies no climatic data, so two values must be brought in and stated.
(i) $\text{HDD}_{18}=4500\ {}^{\circ}\text{C}\cdot\text{day}$ for Ottawa, from
Appendix C of the National Building Code; the same table gives the
$-25\,{}^{\circ}\text{C}$ design temperature the question uses, which confirms the
source. Published Ottawa values range from about $4400$ to $4700$ depending on the
station and the normals period, so the gas figure carries roughly $\pm5\%$ on that
account alone. (ii) $C_D=0.65$; at $0.60$ the answer becomes $1580\ \text{m}^3$ and at
$0.70$ it becomes $1840\ \text{m}^3$, so this is the largest single uncertainty in
part (a) and the answer should be quoted as "about $1700\ \text{m}^3$". The
percentage saving in part (b) is far more robust, because $C_D$ and $UA$
cancel out of the ratio — only the degree-day sensitivity of
$295\ {}^{\circ}\text{C}\cdot\text{day}$ per kelvin affects it. (iii) Domestic hot
water is excluded throughout: the question asks for the gas required to heat the
house, and water heating would add roughly another $1000\ \text{m}^3$ a year to a
real bill.