NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · December 2019

Question 1 of 8: All-outdoor-air operating-room plant — state points, air quantity, coil duty

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, December 2019 — 16-Mec-B2 Environmental Control in Buildings. Three hours, open book: only textbooks and reference books are permitted (no notes and no solved problems), any non-communicating calculator is allowed, and candidates are expected to bring both an environmental-control text and steam tables because the tables and graphs in those books are needed. Eight problems are printed at 20 points each and only the first five in the exam book are graded, so the printed paper totals 160 points and a graded script totals 100. Psychrometric charts (IP and SI) and an R-134a pressure–enthalpy diagram are attached as the last three pages. All eight problems are worked below.

Reference texts for this subject.

Check — assumptions declared under cover-page instruction 1

Cover-page instruction 1 asks candidates to state any interpretive assumption with the answer. Four are needed on this paper and each is flagged again where it is used: the operating-room dry-bulb temperature in Problem 1 (not given — taken as 75 °F, the top of the ASHRAE 170 range, because it is the only part of that range that also satisfies the 60 % relative-humidity ceiling); the Winnipeg design conditions and degree-day base in Problem 6 (the paper says “select the design conditions”); the indoor design temperature and neutral pressure level in Problem 7(b); and the duct roughness and fitting allowance in Problem 8. Everything else in the paper is fully determined by the data given.

Question 1: All-outdoor-air operating-room plant — state points, air quantity, coil duty (20 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given.

QuantitySymbolValue
Outdoor design statetO / twb,O95 / 75 °F
Supply (coil-leaving) statetS / φS55 °F / 100 %
Room sensible loadqs40 000 Btu/h
Room latent loadql10 000 Btu/h
Barometric pressure (sea level)p14.696 psia
Outdoor-air fraction—100 % (once-through)

Find. The supply air rate in cfm, the total cooling-coil capacity in Btu/h, and the relative humidity of the air leaving the operating room, with every significant state point labelled by dry-bulb and wet-bulb temperature on both a system diagram and the psychrometric chart.

100 % outdoor-air (once-through) operating-room plantFilterspre + HEPACoolingcoilFanOperatingroom RO95 °F DB75 °F WBS1 798 cfm55 °F sat.R100 % exhaust(no recirculation)75 °F DB, 55.7 % RHQ̇coil = 124 000 Btu/h40 000 Btu/h sensible10 000 Btu/h latentAir passes once, so the coil always sees the outdoor state on its face.
Figure 1.1 — part (a): the once-through 100 % outdoor-air plant. Because none of the room air returns, the coil face always sees the outdoor state O, and the air leaving the room is exhausted at the room state R.
Check — the room dry-bulb temperature is not given

Parts (d)–(f) need a room dry-bulb temperature, and the paper does not state one; the loads and the supply state fix only the direction of the room line, not the room point. Adopting tR = 75 °F: ASHRAE Standard 170 (adopted in Canada through CSA Z317.2) gives an operating-room design range of 68–75 °F with relative humidity held between 20 % and 60 %. Step 6 below shows that the 60 % ceiling is only met for tR ≥ 72.4 °F, so 75 °F is the standards-compliant choice and it is also the least-airflow (least-energy) end of the range. A sensitivity table at the end of the answer shows what the other end of the range would give.

Approach. Fix the supply state from saturation at 55 °F and the outdoor state from its wet bulb, size the dry-air mass flow on the sensible balance between supply and room, close the moisture balance to get the room humidity ratio, then take the coil duty as the whole enthalpy drop from O to S because the system is once-through.

  1. Part (a) — describe the plant and fix the notation. Outdoor air is filtered, cooled and dehumidified in one coil, moved by the supply fan and delivered to the room; all of it is exhausted. Three states matter: O outdoors, S leaving the coil (and, because duct gain and fan rise are to be neglected, also entering the room), and R in the room and in the exhaust. Figure 1.1 is the answer to part (a).
  2. Fix the supply state S from saturation at 55 °F. With φ = 100 % the vapour pressure equals the saturation pressure, $$p_{ws}(55\,{}^{\circ}\text{F}) = 0.2141\ \text{psia}, \qquad W = 0.621945\,\frac{p_w}{p - p_w}$$ so that $$W_S = 0.621945 \times \frac{0.2141}{14.696 - 0.2141} = \boxed{0.009195\ \text{lb/lb da}}$$ The enthalpy and specific volume follow from the ASHRAE moist-air relations, h = 0.240t + W(1061 + 0.444t) and v = 0.370486 T(1 + 1.6079W)/p: hS = 23.18 Btu/lb and vS = 13.167 ft³/lb da. A saturated state is its own wet bulb, so twb,S = 55.0 °F.
  3. Fix the outdoor state O from its wet bulb. The adiabatic-saturation relation inverted at t = 95 °F, t* = 75 °F gives $$W_O = \frac{h(t^{*}, W_{sat}(t^{*})) - 0.240\,t - W_{sat}(t^{*})\,h_f(t^{*})}{(1061 + 0.444\,t) - h_f(t^{*})} = \boxed{0.014065\ \text{lb/lb da}}$$ whence hO = 38.32 Btu/lb and φO = 39.8 % — a hot, only moderately humid design day, which is what makes the outdoor air worth cooling in one pass.
  4. Part (d) — size the dry-air flow on the sensible balance. The supply-to-room sensible gain is taken at constant humidity ratio, so the exact moist-air specific heat at WS applies: $$q_s = \dot m_{da}\,(0.240 + 0.444\,W_S)\,(t_R - t_S)$$ $$\dot m_{da} = \frac{40\,000}{(0.240 + 0.444 \times 0.009195)(75 - 55)} = \frac{40\,000}{4.8817} = \boxed{8\,194\ \text{lb da/h}}$$ Converting to volume at the supply state, $$\dot V_S = \dot m_{da}\,\frac{v_S}{60} = 8\,194 \times \frac{13.167}{60} = \boxed{1\,798\ \text{cfm}}$$ The familiar shortcut cfm = qs/(1.10 Δt) returns 1 818 cfm; the 1 % difference is the standard-density coefficient standing in for the actual 13.167 ft³/lb of the cold supply air.
  5. Close the moisture balance to reach the room state R. All the latent load is picked up between S and R, so $$W_R = W_S + \frac{q_l}{\dot m_{da}\,(1061 + 0.444\,t_R)} = 0.009195 + \frac{10\,000}{8\,194 \times 1\,094.3} = \boxed{0.010311\ \text{lb/lb da}}$$ Two checks close on this: the total enthalpy rise ṁda(hR − hS) = 8 194 × (29.283 − 23.180) = 50 000 Btu/h, exactly the stated total load, and the room sensible-heat factor SHF = 40 000/50 000 = 0.80, which is the slope of the S–R line drawn on Figure 1.2.
  6. Part (f) — the humidity of the air leaving the operating room. The air leaving the room is at the room state, so its relative humidity follows from WR: $$p_w = \frac{p\,W_R}{0.621945 + W_R} = \frac{14.696 \times 0.010311}{0.632256} = 0.2397\ \text{psia}, \qquad \phi_R = \frac{p_w}{p_{ws}(75\,{}^{\circ}\text{F})} = \frac{0.2397}{0.4300}$$ $$\phi_R = \boxed{55.7\ \%}$$ with a wet-bulb temperature of 64.2 °F. Repeating steps 4–6 across the ASHRAE 170 band shows why the top of the band was chosen: at 68 °F the room would sit at 68.0 % RH, at 70 °F at 64.2 %, and the 60 % limit is not reached until 72.4 °F. A colder room needs more air, but the extra air removes proportionally less moisture relative to its own saturation limit, so the room gets damper, not drier.
  7. Part (e) — the coil capacity. Because the system is once-through, the coil processes the whole supply flow all the way from the outdoor state: $$\dot Q_{coil} = \dot m_{da}\,(h_O - h_S) = 8\,194 \times (38.316 - 23.180) = \boxed{124\,000\ \text{Btu/h}} \;=\; 10.3\ \text{tons}$$ Splitting it the way a coil-selection sheet does, the sensible part is ṁda[h(tO,WO) − h(tS,WO)] = 80 700 Btu/h and the latent part 43 300 Btu/h, a coil sensible-heat factor of 0.651. The coil is therefore 2.5 times the room load, and every bit of that multiplier is the price of the infection-control decision to recirculate nothing.
  8. Parts (b) and (c) — the cycle and its state points. On the chart the process is a straight coil line O → S followed by the room line S → R at SHF 0.80. The coil line terminates on the saturation curve, so the apparatus dew point coincides with S and the coil by-pass factor is $$\text{BF} = \frac{W_S - W_{adp}}{W_M - W_{adp}} = 0\ ,\qquad \text{ADP} = 55\,{}^{\circ}\text{F}$$ A real coil cannot achieve this — four- to six-row coils leave air at 90–95 % saturation — so in practice the coil would be selected for an apparatus dew point of about 52 °F with a by-pass factor near 0.10, giving the stated 55 °F saturated condition after a small amount of mixing. That refinement changes the duty by under 2 % and is noted rather than carried.
Psychrometric processes — outdoor O, coil discharge S, room R0.0040.0080.0120.0160.0200.024Dry-bulb temperature (°F)Humidity ratio W (lb/lb da)4550556065707580859095100saturation (100 % RH)50 % RHOS = ADPRcoil processroom line (SHF = 0.80)
Figure 1.2 — parts (b) and (c): the operating cycle. O → S is the cooling and dehumidifying coil process, S → R is the room line at SHF 0.80. Because S lies on the saturation curve it is also the apparatus dew point.
QuantitySymbolResult
Supply state (part c)tS / twb,S / WS55.0 / 55.0 °F, 0.009195 lb/lb da
Outdoor state (part c)tO / twb,O / WO95.0 / 75.0 °F, 0.014065 lb/lb da
Room state (part c)tR / twb,R / WR75.0 / 64.2 °F, 0.010311 lb/lb da
Dry-air mass flowṁda8 194 lb da/h
Supply air rate (part d)ṀS1 798 cfm
Cooling-coil capacity (part e)ṁ̇coil124 000 Btu/h (10.3 tons)
— sensible / latent split—80 700 / 43 300 Btu/h (coil SHF 0.651)
Humidity leaving the room (part f)φR55.7 % RH
Apparatus dew point and by-pass factorADP / BF55.0 °F, BF = 0
← Paper overview