22-Mec-B2 Environmental Control in Buildings · December 2019
Question 1 of 8: All-outdoor-air operating-room plant — state points, air quantity, coil duty
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, December 2019 — 16-Mec-B2 Environmental
Control in Buildings. Three hours, open book: only textbooks and reference books are permitted
(no notes and no solved problems), any non-communicating calculator is allowed, and candidates are
expected to bring both an environmental-control text and steam tables because the tables and graphs
in those books are needed. Eight problems are printed at 20 points each and only the first
five in the exam book are graded, so the printed paper totals 160 points and a graded script
totals 100. Psychrometric charts (IP and SI) and an R-134a pressure–enthalpy diagram are
attached as the last three pages. All eight problems are worked below.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — plant psychrometry, duct design, infiltration and the degree-day method.
Jones, Air Conditioning Engineering, 5th ed. — percentage saturation, cooling-tower
analysis, apparatus dew point and coil by-pass factor.
Çengel & Ghajar, Heat and Mass Transfer, 6th ed., Ch. 3 —
one-dimensional composite walls and thermal bridging; Table A-5 for building-material
conductivities.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour-compression
cycles and heat pumps; ASHRAE Refrigerant Tables for R-134a on the datum of the attached
chart (hf = sf = 0 at −40 °F).
Eastop & McConkey, Applied Thermodynamics for Engineering Technologists, 5th ed.
— the SI cooling-tower mass/energy balance in the form this paper uses.
Canadian context: ASHRAE Standard 170 Ventilation of Health Care
Facilities (adopted by CSA Z317.2 for Canadian hospitals); Health Canada
Residential Indoor Air Quality Guidelines; National Building Code of Canada 9.36 and the
National Energy Code of Canada for Buildings (NECB 2020); Environment and Climate Change Canada
Canadian Climate Normals for degree-day and design-temperature data.
Check — assumptions declared under cover-page instruction 1
Cover-page instruction 1 asks candidates to state any interpretive assumption with the answer.
Four are needed on this paper and each is flagged again where it is used: the operating-room
dry-bulb temperature in Problem 1 (not given — taken as
75 °F, the top of the ASHRAE 170 range, because it is the
only part of that range that also satisfies the 60 % relative-humidity ceiling); the
Winnipeg design conditions and degree-day base in Problem 6 (the paper says
“select the design conditions”); the indoor design temperature and neutral pressure
level in Problem 7(b); and the duct roughness and fitting allowance in
Problem 8. Everything else in the paper is fully determined by the data given.
Question 1: All-outdoor-air operating-room plant — state points, air quantity, coil duty
(20 marks)
Find. The supply air rate in cfm, the total cooling-coil capacity in Btu/h, and the
relative humidity of the air leaving the operating room, with every significant state point labelled
by dry-bulb and wet-bulb temperature on both a system diagram and the psychrometric chart.
Figure 1.1 — part (a): the once-through
100 % outdoor-air plant. Because none of the room air returns, the coil face always sees the
outdoor state O, and the air leaving the room is exhausted at the room state R.
Check — the room dry-bulb temperature is not given
Parts (d)–(f) need a room dry-bulb temperature, and the paper does not state one; the loads
and the supply state fix only the direction of the room line, not the room point. Adopting
tR = 75 °F: ASHRAE Standard 170 (adopted in Canada through
CSA Z317.2) gives an operating-room design range of 68–75 °F with relative humidity
held between 20 % and 60 %. Step 6 below shows that the 60 % ceiling is only met
for tR ≥ 72.4 °F, so 75 °F is the
standards-compliant choice and it is also the least-airflow (least-energy) end of the range. A
sensitivity table at the end of the answer shows what the other end of the range would give.
Approach. Fix the supply state from saturation at 55 °F and the outdoor
state from its wet bulb, size the dry-air mass flow on the sensible balance between supply and
room, close the moisture balance to get the room humidity ratio, then take the coil duty as the whole
enthalpy drop from O to S because the system is once-through.
Part (a) — describe the plant and fix the notation. Outdoor air is filtered,
cooled and dehumidified in one coil, moved by the supply fan and delivered to the room; all of it is
exhausted. Three states matter: O outdoors, S leaving the coil (and,
because duct gain and fan rise are to be neglected, also entering the room), and R in
the room and in the exhaust. Figure 1.1 is the answer to part (a).
Fix the supply state S from saturation at 55 °F. With
φ = 100 % the vapour pressure equals the saturation pressure,
$$p_{ws}(55\,{}^{\circ}\text{F}) = 0.2141\ \text{psia}, \qquad
W = 0.621945\,\frac{p_w}{p - p_w}$$
so that
$$W_S = 0.621945 \times \frac{0.2141}{14.696 - 0.2141} = \boxed{0.009195\ \text{lb/lb da}}$$
The enthalpy and specific volume follow from the ASHRAE moist-air relations,
h = 0.240t + W(1061 + 0.444t) and
v = 0.370486 T(1 + 1.6079W)/p:
hS = 23.18 Btu/lb and
vS = 13.167 ft³/lb da. A saturated state is its own
wet bulb, so twb,S = 55.0 °F.
Fix the outdoor state O from its wet bulb. The adiabatic-saturation relation
inverted at t = 95 °F,
t* = 75 °F gives
$$W_O = \frac{h(t^{*}, W_{sat}(t^{*})) - 0.240\,t - W_{sat}(t^{*})\,h_f(t^{*})}{(1061 + 0.444\,t) - h_f(t^{*})}
= \boxed{0.014065\ \text{lb/lb da}}$$
whence hO = 38.32 Btu/lb and
φO = 39.8 % — a hot, only moderately humid design
day, which is what makes the outdoor air worth cooling in one pass.
Part (d) — size the dry-air flow on the sensible balance. The supply-to-room
sensible gain is taken at constant humidity ratio, so the exact moist-air specific heat at
WS applies:
$$q_s = \dot m_{da}\,(0.240 + 0.444\,W_S)\,(t_R - t_S)$$
$$\dot m_{da} = \frac{40\,000}{(0.240 + 0.444 \times 0.009195)(75 - 55)}
= \frac{40\,000}{4.8817} = \boxed{8\,194\ \text{lb da/h}}$$
Converting to volume at the supply state,
$$\dot V_S = \dot m_{da}\,\frac{v_S}{60} = 8\,194 \times \frac{13.167}{60}
= \boxed{1\,798\ \text{cfm}}$$
The familiar shortcut cfm = qs/(1.10 Δt) returns
1 818 cfm; the 1 % difference is the standard-density coefficient standing in for the
actual 13.167 ft³/lb of the cold supply air.
Close the moisture balance to reach the room state R. All the latent load is
picked up between S and R, so
$$W_R = W_S + \frac{q_l}{\dot m_{da}\,(1061 + 0.444\,t_R)}
= 0.009195 + \frac{10\,000}{8\,194 \times 1\,094.3} = \boxed{0.010311\ \text{lb/lb da}}$$
Two checks close on this: the total enthalpy rise
ṁda(hR − hS) =
8 194 × (29.283 − 23.180) = 50 000 Btu/h, exactly the stated total
load, and the room sensible-heat factor
SHF = 40 000/50 000 = 0.80, which is the slope of the S–R
line drawn on Figure 1.2.
Part (f) — the humidity of the air leaving the operating room. The air
leaving the room is at the room state, so its relative humidity follows from WR:
$$p_w = \frac{p\,W_R}{0.621945 + W_R} = \frac{14.696 \times 0.010311}{0.632256} = 0.2397\ \text{psia},
\qquad \phi_R = \frac{p_w}{p_{ws}(75\,{}^{\circ}\text{F})} = \frac{0.2397}{0.4300}$$
$$\phi_R = \boxed{55.7\ \%}$$
with a wet-bulb temperature of 64.2 °F. Repeating steps 4–6 across the
ASHRAE 170 band shows why the top of the band was chosen: at 68 °F the room would sit at
68.0 % RH, at 70 °F at 64.2 %, and the 60 % limit is not reached until
72.4 °F. A colder room needs more air, but the extra air removes proportionally less
moisture relative to its own saturation limit, so the room gets damper, not drier.
Part (e) — the coil capacity. Because the system is once-through, the coil
processes the whole supply flow all the way from the outdoor state:
$$\dot Q_{coil} = \dot m_{da}\,(h_O - h_S) = 8\,194 \times (38.316 - 23.180)
= \boxed{124\,000\ \text{Btu/h}} \;=\; 10.3\ \text{tons}$$
Splitting it the way a coil-selection sheet does, the sensible part is
ṁda[h(tO,WO) −
h(tS,WO)] = 80 700 Btu/h and the latent part
43 300 Btu/h, a coil sensible-heat factor of 0.651. The coil is therefore 2.5 times
the room load, and every bit of that multiplier is the price of the infection-control decision to
recirculate nothing.
Parts (b) and (c) — the cycle and its state points. On the chart the process
is a straight coil line O → S followed by the room line S → R at
SHF 0.80. The coil line terminates on the saturation curve, so the apparatus dew point
coincides with S and the coil by-pass factor is
$$\text{BF} = \frac{W_S - W_{adp}}{W_M - W_{adp}} = 0\ ,\qquad \text{ADP} = 55\,{}^{\circ}\text{F}$$
A real coil cannot achieve this — four- to six-row coils leave air at 90–95 %
saturation — so in practice the coil would be selected for an apparatus dew point of about
52 °F with a by-pass factor near 0.10, giving the stated 55 °F saturated condition
after a small amount of mixing. That refinement changes the duty by under 2 % and is noted rather
than carried.
Figure 1.2 — parts (b) and (c): the operating
cycle. O → S is the cooling and dehumidifying coil process, S → R is the
room line at SHF 0.80. Because S lies on the saturation curve it is also the apparatus dew
point.