22-Mec-B2 Environmental Control in Buildings · December 2019
Question 7 of 8: Dilution ventilation for an indoor NO x source; stack and wind pressures on a tall building
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, December 2019 — 16-Mec-B2 Environmental
Control in Buildings. Three hours, open book: only textbooks and reference books are permitted
(no notes and no solved problems), any non-communicating calculator is allowed, and candidates are
expected to bring both an environmental-control text and steam tables because the tables and graphs
in those books are needed. Eight problems are printed at 20 points each and only the first
five in the exam book are graded, so the printed paper totals 160 points and a graded script
totals 100. Psychrometric charts (IP and SI) and an R-134a pressure–enthalpy diagram are
attached as the last three pages. All eight problems are worked below.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — plant psychrometry, duct design, infiltration and the degree-day method.
Jones, Air Conditioning Engineering, 5th ed. — percentage saturation, cooling-tower
analysis, apparatus dew point and coil by-pass factor.
Çengel & Ghajar, Heat and Mass Transfer, 6th ed., Ch. 3 —
one-dimensional composite walls and thermal bridging; Table A-5 for building-material
conductivities.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour-compression
cycles and heat pumps; ASHRAE Refrigerant Tables for R-134a on the datum of the attached
chart (hf = sf = 0 at −40 °F).
Eastop & McConkey, Applied Thermodynamics for Engineering Technologists, 5th ed.
— the SI cooling-tower mass/energy balance in the form this paper uses.
Canadian context: ASHRAE Standard 170 Ventilation of Health Care
Facilities (adopted by CSA Z317.2 for Canadian hospitals); Health Canada
Residential Indoor Air Quality Guidelines; National Building Code of Canada 9.36 and the
National Energy Code of Canada for Buildings (NECB 2020); Environment and Climate Change Canada
Canadian Climate Normals for degree-day and design-temperature data.
Check — assumptions declared under cover-page instruction 1
Cover-page instruction 1 asks candidates to state any interpretive assumption with the answer.
Four are needed on this paper and each is flagged again where it is used: the operating-room
dry-bulb temperature in Problem 1 (not given — taken as
75 °F, the top of the ASHRAE 170 range, because it is the
only part of that range that also satisfies the 60 % relative-humidity ceiling); the
Winnipeg design conditions and degree-day base in Problem 6 (the paper says
“select the design conditions”); the indoor design temperature and neutral pressure
level in Problem 7(b); and the duct roughness and fitting allowance in
Problem 8. Everything else in the paper is fully determined by the data given.
Question 7: Dilution ventilation for an indoor NOx source; stack and wind pressures on a
tall building (20 marks: a — 5, b — 15)
Part (a) — outdoor airflow needed to dilute the NOx source (5 marks)
Given. Indoor generation rate
S = 115 µg/s; outdoor (supply) concentration
Co = 55 µg/m³; the room is perfectly mixed and at
steady state.
Find. The outdoor airflow rate that holds the indoor concentration at the
recommended guideline value.
Write the steady-state mass balance on the well-mixed space. Contaminant in with
the ventilation air plus contaminant generated equals contaminant out with the exhaust:
$$\dot V C_o + S = \dot V C_i \quad\Longrightarrow\quad
\dot V = \frac{S}{C_i - C_o}$$
The result is independent of the room volume, which is why none is given: at steady state the volume
sets only how quickly the concentration gets there, not where it settles.
Select the guideline concentration. Because these are Canadian examinations, the
governing value is Health Canada's Residential Indoor Air Quality Guideline for nitrogen
dioxide, 170 µg/m³ as a one-hour exposure (the long-term
value of 20 µg/m³ is below the stated outdoor concentration and therefore unreachable
by dilution — a point worth making explicitly rather than silently). Substituting,
$$\dot V = \frac{115}{170 - 55} = \frac{115}{115} = \boxed{1.00\ \text{m}^3\!/\text{s}}$$
that is 1 000 L/s, or about 2 120 cfm.
Report the alternative standard, because the answer is sensitive to it.
ASHRAE 62.1 Table 4-1 adopts the US national ambient standard for NO₂ of
100 µg/m³ as an annual mean, which gives
115/(100 − 55) = 2.56 m³/s (5 415 cfm), and the
World Health Organization's one-hour value of 200 µg/m³ gives
0.79 m³/s. The three answers span a factor of three, so the standard must be named with the
number.
Note what the arithmetic reveals about the design. The outdoor air is already at
one-third of the guideline, so only 115 µg/m³ of headroom is available for dilution.
Halving the outdoor concentration to 27 µg/m³ would cut the required airflow to
0.80 m³/s, whereas raising it to 100 µg/m³ would demand
1.64 m³/s — and at 170 µg/m³ outdoors no finite airflow would work at
all. That hyperbolic sensitivity is the practical argument for source control before dilution
ventilation: capturing the NOx at source with local exhaust, or replacing a
combustion appliance with an electric one, removes the problem instead of diluting it, and costs far
less to run than conditioning 1 m³/s of outdoor air through a Canadian winter.
Part (b) — stack and wind pressure differences on the first and tenth floors (15 marks)
Given.
Quantity
Symbol
Value
Storeys × floor height
—
10 × 10 ft = 100 ft overall
Plan dimensions
—
150 ft × 50 ft
Wind speed, normal to the 150 ft face
U
15 mph (22.0 ft/s)
Indoor − outdoor temperature difference
Δt
70 °F
Construction
—
fixed windows, conventional curtain wall
Assumed (declared under instruction 1)
Indoor / outdoor design temperature
ti / to
70 / 0 °F
Neutral pressure level
hNPL
50 ft (mid-height)
Pressure coefficients
Cp
+0.6 windward, −0.3 leeward, −0.5 sidewall
Find. The indoor-minus-outdoor pressure difference on the first and tenth floors,
separating the stack and wind contributions.
Figure 7.1 — the two driving forces. Stack
pressure varies linearly with height and reverses sign at the neutral pressure level; wind pressure is
uniform with height in this estimate and depends on which face is considered.
Approach. Compute the two mechanisms separately — the stack pressure from the
indoor-to-outdoor air density difference acting over the height above or below the neutral pressure
level, and the wind pressure from the free-stream velocity pressure scaled by a surface pressure
coefficient — then add them algebraically for each face and floor.
Fix the two air densities. Taking 70 °F indoors and 0 °F outdoors
to give the stated 70 °F difference, and treating the air as dry at sea level,
$$\rho = \frac{p}{R_a T}: \qquad
\rho_i = \frac{2\,116.2}{53.35 \times 529.67} = 0.07489\ \text{lb/ft}^3, \qquad
\rho_o = \frac{2\,116.2}{53.35 \times 459.67} = 0.08629\ \text{lb/ft}^3$$
$$\Delta\rho = \rho_o - \rho_i = 0.01140\ \text{lb/ft}^3$$
The cold outdoor air is 15 % heavier, and that density difference is the entire stack effect.
Locate the neutral pressure level. For a building with leakage distributed
uniformly over its height and no imbalance between mechanical supply and exhaust, the plane at which
indoor and outdoor pressures are equal sits at mid-height:
hNPL = 50 ft. This is an assumption, and a consequential one
— the grade-level vestibule doors named in the question are a large low-level opening that in
practice pushes the neutral level upward, worsening ground-floor infiltration. The sensitivity is given
in the callout below.
Compute the stack pressure at each floor. With the sign convention that positive
means the outdoor pressure exceeds the indoor (so air is driven in),
$$\Delta p_s = \Delta\rho\,g\,(h_{NPL} - h)$$
Evaluating at the mid-height of each storey — 5 ft for the first floor and 95 ft for the
tenth — both are 45 ft from the neutral level, so the magnitudes are equal and the signs
opposite:
$$\Delta p_{s,1} = 0.01140 \times 45 = 0.513\ \text{lbf/ft}^2
= \boxed{+0.099\ \text{in.\ wg}}$$
$$\Delta p_{s,10} = \boxed{-0.099\ \text{in.\ wg}}$$
using 1 in. wg = 5.202 lbf/ft². Air is driven into the
first floor and out of the tenth — the classic winter chimney behaviour of a tall
building.
Compute the free-stream velocity pressure. At 15 mph = 22.0 ft/s in the
cold outdoor air,
$$p_v = \frac{\rho_o U^2}{2g_c}
= \frac{0.08629 \times 22.0^2}{2 \times 32.174} = 0.6486\ \text{lbf/ft}^2
= 0.125\ \text{in.\ wg}$$
The tabulated shortcut pv = 0.000482 U² gives
0.108 in. wg because it is written for standard 0.075 lb/ft³ air; the
15 % denser winter air raises it by the same 15 %.
Apply the surface pressure coefficients. The wall pressure is
Δpw = Cppv, so for the standard
average coefficients on a rectangular building,
$$\Delta p_{w} = \begin{cases}
+0.6 \times 0.125 = +0.075\ \text{in.\ wg} & \text{windward (the 150 ft face)}\\
-0.3 \times 0.125 = -0.037\ \text{in.\ wg} & \text{leeward}\\
-0.5 \times 0.125 = -0.062\ \text{in.\ wg} & \text{sidewalls (the 50 ft faces)}
\end{cases}$$
Note that only the windward face is pushed inward; the other three are in the wake and are suctioned,
so wind assists exfiltration over three-quarters of the building's perimeter.
Add the two mechanisms for each floor and face. Since both are pressures acting on
the same envelope, they superpose:
Floor
Face
Stack (in. wg)
Wind (in. wg)
Net (in. wg)
Direction
1st (5 ft)
windward
+0.099
+0.075
+0.174
infiltration
leeward
+0.099
−0.037
+0.061
infiltration
sidewall
+0.099
−0.062
+0.036
infiltration
10th (95 ft)
windward
−0.099
+0.075
−0.024
slight exfiltration
leeward
−0.099
−0.037
−0.136
exfiltration
sidewall
−0.099
−0.062
−0.161
exfiltration
The two extremes are the ones a designer needs: +0.174 in. wg driving air into the
windward ground floor and −0.161 in. wg driving it out of the tenth-floor
sidewall. The whole first floor infiltrates on every face because stack dominates there, while
on the tenth floor the windward wall is nearly balanced — wind almost exactly cancels stack, and
a small change in either would reverse the flow through those windows.
Interpret the numbers as a design engineer would. A pressure difference of
0.17 in. wg across a swinging door is about 5 lbf of opening force on a
3 ft × 7 ft leaf, near the limit at which doors become difficult and start to
be held open — which is precisely why the question specifies double vestibule-type
doors: two door banks in series each see half the total difference. On the tenth floor the same
magnitude of difference acting outward is what drives moisture-laden indoor air into the curtain-wall
cavity, where it meets a cold surface; that, not heat loss, is the usual reason top-floor curtain walls
fail. The standard remedies are exactly the ones the question hints at: vestibules and revolving doors
at grade, compartmentation of shafts and stairwells to break the vertical connection, and a slight net
mechanical pressurisation of the building to shift the neutral level below the ground floor.
Check — two assumptions that matter, quantified
Neutral pressure level. Mid-height is the textbook default for uniform leakage. If
the grade-level doors move it down to 0.3 H = 30 ft, the first-floor stack term falls to
+0.055 and the tenth-floor term rises to −0.143 in. wg — the tenth floor gets
worse and the first better, so the assumption is not conservative in both directions and should be
stated wherever the answer is used.
Wind-speed profile. The 15 mph is treated as acting uniformly, which is what
“estimate” invites. Carrying the ASHRAE boundary-layer correction from a
33 ft open-terrain met station to a suburban site instead gives 7.1 mph at 5 ft and
13.6 mph at 95 ft, so the velocity pressure falls to 0.028 in. wg at the first
floor and 0.103 at the tenth. That would leave the first floor stack-dominated at
+0.116 in. wg and push the tenth-floor windward wall to −0.037 — a genuine
exfiltration rather than a near balance. The uniform-wind answer above is the more conservative one for
the ground-floor doors, which is the governing case.
Quantity
Symbol
Result
Outdoor airflow for NOx dilution (part a)
Ṁ
1.00 m³/s (1 000 L/s, 2 120 cfm) at the Health Canada 1-h value
— on ASHRAE 62.1 / NAAQS annual 100 µg/m³
—
2.56 m³/s (5 415 cfm)
Air densities, indoor / outdoor
ρi / ρo
0.0749 / 0.0863 lb/ft³
Stack pressure, 1st / 10th floor
Δps
+0.099 / −0.099 in. wg
Free-stream velocity pressure
pv
0.125 in. wg
Wind pressure, windward / leeward / sidewall
Δpw
+0.075 / −0.037 / −0.062 in. wg
Net on 1st floor (part b)
Δp
+0.174 windward, +0.061 leeward, +0.036 sidewall — all infiltration
Net on 10th floor (part b)
Δp
−0.024 windward, −0.136 leeward, −0.161 sidewall — all exfiltration