22-Mec-B2 Environmental Control in Buildings · Undated paper
Question 1 of 8: Summer plant — mixing box, cooling coil, apparatus dew point
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, May 2019 — 16-Mec-B2 Environmental
Control in Buildings. Three hours, open book: any textbooks, references or notes may be used and
any non-communicating calculator is permitted, but computers, internet and smart phones are
prohibited. Candidates are told to bring both an environmental-control text and steam tables.
Eight problems are printed — Problem 1 is 30 points, Problem 2 is 10 points and
Problems 3 to 8 are 20 points each — and candidates solve five, indicating on the
cover of the first workbook which five are to be graded. Psychrometric charts and the refrigerant
pressure–enthalpy diagram are attached as the last three pages. Cover-page instruction 1 asks
for a clear statement of the assumption(s) wherever the interpretation is open, and several
problems below need one. All eight problems are worked here, because this set is a
study resource rather than a three-hour sitting.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — plant psychrometry, infiltration, duct design, solar heat gain and the
degree-day method.
Jones, Air Conditioning Engineering, 5th ed. — apparatus dew point, coil by-pass
factor, humidification.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour-
compression cycle analysis and compressor volumetric efficiency.
Çengel & Boles, Thermodynamics: An Engineering Approach, 9th ed. —
R-134a property tables and steam tables.
Environment and Climate Change Canada, Canadian Climate Normals — Ottawa
heating degree-days; National Energy Code of Canada for Buildings (NECB) 2020 for the net-zero
discussion.
Check: every psychrometric state below is computed from the ASHRAE Ch. 1
formulations rather than read off the attached chart, and every mixing state is obtained from the
exact mass and energy balances (humidity ratio and enthalpy mass-weighted, dry bulb then
derived). Chart readings will differ in the last displayed digit; the physics does not.
Problem 1: Summer plant — mixing box, cooling coil, apparatus dew point (30 points)
Given. A once-mixed, single-coil constant-volume plant at sea level
($p = 14.696$ psia), with no fan or friction gain.
Quantity
Symbol
Value
Room sensible cooling load
$Q_{RS}$
195,500 Btu/h
Room latent cooling load
$Q_{RL}$
34,500 Btu/h
Room state
$R$
78 °F db, 67 °F wb
Outdoor state
$O$
90 °F db, 70 % RH
Ventilation (outdoor) air
$\dot V_O$
3,000 cfm
Return air recirculated
$\dot V_R$
11,000 cfm
Find. The supply-air condition and quantity, the room and grand sensible heat
factors, the refrigeration duty at the coil, and the coil apparatus dew point with its by-pass
factor.
Part (a) — plant arrangement. Outdoor air
O joins return air R in the mixing box, the mixture M passes over the chilled-water coil to state S,
and S is supplied to the room; 3,000 cfm is relieved to balance the ventilation air.
Approach. Fix the room and outdoor states from ASHRAE Ch. 1, convert the two
stated volume flows to dry-air mass flows at their own states, mix them exactly, close the
room sensible and latent balances to get the supply state, and then read the coil line
$M \to S$ down to the saturation curve for the apparatus dew
point.
Part (b) — fix the room state R. With a 78 °F dry bulb and 67 °F wet
bulb, the ASHRAE wet-bulb relation
$$W_R=\frac{(1093-0.556\,t^{*})W_s(t^{*})-0.240\,(t-t^{*})}{1093+0.444\,t-t^{*}}$$
with $t=78\,{}^{\circ}\text{F}$ and $t^{*}=67\,{}^{\circ}\text{F}$ gives
$\boxed{W_R = 0.01163\ \text{lb}_w/\text{lb}_{da}}$, from which $h_R = 0.240t + W(1061+0.444t) =
31.46\ \text{Btu/lb}_{da}$, $v_R = 13.808\ \text{ft}^3/\text{lb}_{da}$, dew point 61.4 °F and
relative humidity 56.8 %.
Fix the outdoor state O. At 90 °F the saturation pressure is 0.6989 psia, so
$p_w = 0.70(0.6989) = 0.4892$ psia and
$$W_O=\frac{0.621945\,p_w}{p-p_w}=0.02142\ \text{lb}_w/\text{lb}_{da},$$
giving $h_O = 45.18\ \text{Btu/lb}_{da}$, $v_O = 14.334\ \text{ft}^3/\text{lb}_{da}$, wet bulb
81.5 °F and dew point 78.9 °F. The outdoor air is both hotter and far wetter than the
room, which is why the coil ends up latent-heavy.
Convert the two volume flows to dry-air mass flows. Each stream must be divided
by the specific volume of that stream, not by a standard 13.5:
$$\dot m_O=\frac{3000}{14.334}=209.3\ \frac{\text{lb}_{da}}{\text{min}},\qquad
\dot m_R=\frac{11000}{13.808}=796.6\ \frac{\text{lb}_{da}}{\text{min}}$$
so $\dot m_S = 1{,}005.9\ \text{lb}_{da}/\text{min}$ and the outdoor-air mass fraction is
$x = 209.3/1005.9 = 0.2081$ — slightly below the 3/14 = 0.214 volumetric fraction because the
outdoor air is less dense.
Mix exactly to state M. Adiabatic mixing is exact in moisture and in enthalpy,
so both are mass-weighted and the dry bulb is derived afterwards:
$$W_M=xW_O+(1-x)W_R=0.01367,\qquad h_M=xh_O+(1-x)h_R=34.32\ \text{Btu/lb}_{da}$$
$$t_M=\frac{h_M-1061\,W_M}{0.240+0.444\,W_M}=80.53\,{}^{\circ}\text{F}$$
Weighting the dry bulb directly would be about 0.1 °F adrift because of the $W\!\cdot\!t$ cross
term in the enthalpy relation. State M has a 70.5 °F wet bulb and a 66.0 °F dew point.
Part (d) — close the room latent balance for $W_S$. The room moisture gain
must be absorbed by the supply air:
$$Q_{RL}=\dot m_S\,(W_R-W_S)\,(1061+0.444\,t_R)
\;\Rightarrow\; W_S=W_R-\frac{34{,}500}{60(1005.9)(1095.6)}=0.01111$$
$$\boxed{W_S = 0.01111\ \text{lb}_w/\text{lb}_{da}}$$
Close the room sensible balance for $t_S$. With the moist-air specific heat
$c_p = 0.240+0.444W_S = 0.2449\ \text{Btu/lb}\cdot{}^{\circ}\text{F}$,
$$t_S=t_R-\frac{Q_{RS}}{\dot m_S c_p}=78-\frac{195{,}500}{60(1005.9)(0.2449)}
=\boxed{64.8\,{}^{\circ}\text{F db}}$$
The supply state is therefore 64.8 °F db, 61.8 °F wb, 85.0 % RH, $h_S = 27.65$ Btu/lb and
$v_S = 13.457\ \text{ft}^3/\text{lb}_{da}$, i.e. $1005.9 \times 13.457 = 13{,}537$ cfm delivered at the
supply state. As a check, $\dot m_S(h_R-h_S) = 230{,}000$ Btu/h exactly, which is the stated total
room load.
Part (c) — the two sensible heat factors. The room factor is a pure ratio of
the given loads,
$$\text{RSHF}=\frac{Q_{RS}}{Q_{RS}+Q_{RL}}=\frac{195{,}500}{230{,}000}=\boxed{0.850}$$
The grand factor belongs to the coil, whose entering state is M and leaving state is S. Splitting the
coil enthalpy drop at constant $W_S$,
$$Q_{GS}=\dot m_S\big[h(t_M,W_S)-h(t_S,W_S)\big]=232{,}900\ \text{Btu/h},\qquad
Q_{GT}=\dot m_S(h_M-h_S)=402{,}200\ \text{Btu/h}$$
$$\text{GSHF}=\frac{232{,}900}{402{,}200}=\boxed{0.579}$$
The grand factor is far below the room factor because the 3,000 cfm of 78.9 °F dew-point outdoor
air is almost entirely a latent burden.
Part (e) — total energy input at the coil.
$$Q_{GT}=\dot m_S\,(h_M-h_S)=60(1005.9)(34.32-27.65)=\boxed{402{,}200\ \text{Btu/h}=33.5\ \text{tons}}$$
This closes independently against the load-plus-ventilation route: the outdoor-air load is
$\dot m_O(h_O-h_R)=60(209.3)(45.18-31.46)=172{,}200$ Btu/h, and $230{,}000+172{,}200 = 402{,}200$
Btu/h to within 40 Btu/h. Of the total, 232,900 Btu/h is sensible and 169,300 Btu/h latent.
Part (f) — apparatus dew point and by-pass factor. The apparatus dew point
is the point where the straight coil line through M and S meets the saturation curve. Parameterising
that line and solving $W(t)=W_s(t)$ gives
$$\boxed{\text{ADP}=56.7\,{}^{\circ}\text{F}}$$
and the by-pass factor is the fraction of the entering air that leaves at the entering state,
$$\text{BF}=\frac{t_S-\text{ADP}}{t_M-\text{ADP}}=\frac{64.8-56.7}{80.5-56.7}=\boxed{0.34}$$
A by-pass factor of 0.34 is high for a chilled-water coil — typical four- to six-row selections
sit at 0.05 to 0.15 — which says the plant as specified needs a deeper coil or a lower face
velocity than the stated flows imply. That observation is part of the answer, not a defect in
it.
Part (b) — operating cycle on the
psychrometric chart. O + R mix along the dashed tie-line to M; the coil process M→S extends
(dashed) to the apparatus dew point on the saturation curve; the room process S→R runs back at
RSHF = 0.85.
Point
db (°F)
wb (°F)
$h$ (Btu/lb)
dew point (°F)
$v$ (ft³/lb)
O outdoor
90.0
81.5
45.18
78.9
14.334
R room
78.0
67.0
31.46
61.4
13.808
M mixed
80.5
70.5
34.32
66.0
13.918
S supply
64.8
61.8
27.65
60.2
13.457
ADP
56.7
56.7
24.29
56.7
13.246
Result
Value
(c) Room sensible heat factor, RSHF
0.850
(c) Grand sensible heat factor, GSHF
0.579
(d) Supply-air condition
64.8 °F db / 61.8 °F wb, $W$ = 0.01111, 85 % RH
(d) Supply-air quantity
1,006 lbₕₐ/min = 13,540 cfm at the supply state (14,000 cfm mixed)