NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · Undated paper

Question 1 of 8: Summer plant — mixing box, cooling coil, apparatus dew point

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, May 2019 — 16-Mec-B2 Environmental Control in Buildings. Three hours, open book: any textbooks, references or notes may be used and any non-communicating calculator is permitted, but computers, internet and smart phones are prohibited. Candidates are told to bring both an environmental-control text and steam tables. Eight problems are printed — Problem 1 is 30 points, Problem 2 is 10 points and Problems 3 to 8 are 20 points each — and candidates solve five, indicating on the cover of the first workbook which five are to be graded. Psychrometric charts and the refrigerant pressure–enthalpy diagram are attached as the last three pages. Cover-page instruction 1 asks for a clear statement of the assumption(s) wherever the interpretation is open, and several problems below need one. All eight problems are worked here, because this set is a study resource rather than a three-hour sitting.

Reference texts for this subject.

Check: every psychrometric state below is computed from the ASHRAE Ch. 1 formulations rather than read off the attached chart, and every mixing state is obtained from the exact mass and energy balances (humidity ratio and enthalpy mass-weighted, dry bulb then derived). Chart readings will differ in the last displayed digit; the physics does not.

Problem 1: Summer plant — mixing box, cooling coil, apparatus dew point (30 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A once-mixed, single-coil constant-volume plant at sea level ($p = 14.696$ psia), with no fan or friction gain.

QuantitySymbolValue
Room sensible cooling load$Q_{RS}$195,500 Btu/h
Room latent cooling load$Q_{RL}$34,500 Btu/h
Room state$R$78 °F db, 67 °F wb
Outdoor state$O$90 °F db, 70 % RH
Ventilation (outdoor) air$\dot V_O$3,000 cfm
Return air recirculated$\dot V_R$11,000 cfm

Find. The supply-air condition and quantity, the room and grand sensible heat factors, the refrigeration duty at the coil, and the coil apparatus dew point with its by-pass factor.

Mixing boxCooling coilSupply fanOffice78 F db / 67 F wbO outdoor air3,000 cfm 90 F / 70%M 80.5 FS 64.8 FsupplyR return 11,000 cfmexhaust 3,000 cfm
Part (a) — plant arrangement. Outdoor air O joins return air R in the mixing box, the mixture M passes over the chilled-water coil to state S, and S is supplied to the room; 3,000 cfm is relieved to balance the ventilation air.

Approach. Fix the room and outdoor states from ASHRAE Ch. 1, convert the two stated volume flows to dry-air mass flows at their own states, mix them exactly, close the room sensible and latent balances to get the supply state, and then read the coil line $M \to S$ down to the saturation curve for the apparatus dew point.

  1. Part (b) — fix the room state R. With a 78 °F dry bulb and 67 °F wet bulb, the ASHRAE wet-bulb relation $$W_R=\frac{(1093-0.556\,t^{*})W_s(t^{*})-0.240\,(t-t^{*})}{1093+0.444\,t-t^{*}}$$ with $t=78\,{}^{\circ}\text{F}$ and $t^{*}=67\,{}^{\circ}\text{F}$ gives $\boxed{W_R = 0.01163\ \text{lb}_w/\text{lb}_{da}}$, from which $h_R = 0.240t + W(1061+0.444t) = 31.46\ \text{Btu/lb}_{da}$, $v_R = 13.808\ \text{ft}^3/\text{lb}_{da}$, dew point 61.4 °F and relative humidity 56.8 %.
  2. Fix the outdoor state O. At 90 °F the saturation pressure is 0.6989 psia, so $p_w = 0.70(0.6989) = 0.4892$ psia and $$W_O=\frac{0.621945\,p_w}{p-p_w}=0.02142\ \text{lb}_w/\text{lb}_{da},$$ giving $h_O = 45.18\ \text{Btu/lb}_{da}$, $v_O = 14.334\ \text{ft}^3/\text{lb}_{da}$, wet bulb 81.5 °F and dew point 78.9 °F. The outdoor air is both hotter and far wetter than the room, which is why the coil ends up latent-heavy.
  3. Convert the two volume flows to dry-air mass flows. Each stream must be divided by the specific volume of that stream, not by a standard 13.5: $$\dot m_O=\frac{3000}{14.334}=209.3\ \frac{\text{lb}_{da}}{\text{min}},\qquad \dot m_R=\frac{11000}{13.808}=796.6\ \frac{\text{lb}_{da}}{\text{min}}$$ so $\dot m_S = 1{,}005.9\ \text{lb}_{da}/\text{min}$ and the outdoor-air mass fraction is $x = 209.3/1005.9 = 0.2081$ — slightly below the 3/14 = 0.214 volumetric fraction because the outdoor air is less dense.
  4. Mix exactly to state M. Adiabatic mixing is exact in moisture and in enthalpy, so both are mass-weighted and the dry bulb is derived afterwards: $$W_M=xW_O+(1-x)W_R=0.01367,\qquad h_M=xh_O+(1-x)h_R=34.32\ \text{Btu/lb}_{da}$$ $$t_M=\frac{h_M-1061\,W_M}{0.240+0.444\,W_M}=80.53\,{}^{\circ}\text{F}$$ Weighting the dry bulb directly would be about 0.1 °F adrift because of the $W\!\cdot\!t$ cross term in the enthalpy relation. State M has a 70.5 °F wet bulb and a 66.0 °F dew point.
  5. Part (d) — close the room latent balance for $W_S$. The room moisture gain must be absorbed by the supply air: $$Q_{RL}=\dot m_S\,(W_R-W_S)\,(1061+0.444\,t_R) \;\Rightarrow\; W_S=W_R-\frac{34{,}500}{60(1005.9)(1095.6)}=0.01111$$ $$\boxed{W_S = 0.01111\ \text{lb}_w/\text{lb}_{da}}$$
  6. Close the room sensible balance for $t_S$. With the moist-air specific heat $c_p = 0.240+0.444W_S = 0.2449\ \text{Btu/lb}\cdot{}^{\circ}\text{F}$, $$t_S=t_R-\frac{Q_{RS}}{\dot m_S c_p}=78-\frac{195{,}500}{60(1005.9)(0.2449)} =\boxed{64.8\,{}^{\circ}\text{F db}}$$ The supply state is therefore 64.8 °F db, 61.8 °F wb, 85.0 % RH, $h_S = 27.65$ Btu/lb and $v_S = 13.457\ \text{ft}^3/\text{lb}_{da}$, i.e. $1005.9 \times 13.457 = 13{,}537$ cfm delivered at the supply state. As a check, $\dot m_S(h_R-h_S) = 230{,}000$ Btu/h exactly, which is the stated total room load.
  7. Part (c) — the two sensible heat factors. The room factor is a pure ratio of the given loads, $$\text{RSHF}=\frac{Q_{RS}}{Q_{RS}+Q_{RL}}=\frac{195{,}500}{230{,}000}=\boxed{0.850}$$ The grand factor belongs to the coil, whose entering state is M and leaving state is S. Splitting the coil enthalpy drop at constant $W_S$, $$Q_{GS}=\dot m_S\big[h(t_M,W_S)-h(t_S,W_S)\big]=232{,}900\ \text{Btu/h},\qquad Q_{GT}=\dot m_S(h_M-h_S)=402{,}200\ \text{Btu/h}$$ $$\text{GSHF}=\frac{232{,}900}{402{,}200}=\boxed{0.579}$$ The grand factor is far below the room factor because the 3,000 cfm of 78.9 °F dew-point outdoor air is almost entirely a latent burden.
  8. Part (e) — total energy input at the coil. $$Q_{GT}=\dot m_S\,(h_M-h_S)=60(1005.9)(34.32-27.65)=\boxed{402{,}200\ \text{Btu/h}=33.5\ \text{tons}}$$ This closes independently against the load-plus-ventilation route: the outdoor-air load is $\dot m_O(h_O-h_R)=60(209.3)(45.18-31.46)=172{,}200$ Btu/h, and $230{,}000+172{,}200 = 402{,}200$ Btu/h to within 40 Btu/h. Of the total, 232,900 Btu/h is sensible and 169,300 Btu/h latent.
  9. Part (f) — apparatus dew point and by-pass factor. The apparatus dew point is the point where the straight coil line through M and S meets the saturation curve. Parameterising that line and solving $W(t)=W_s(t)$ gives $$\boxed{\text{ADP}=56.7\,{}^{\circ}\text{F}}$$ and the by-pass factor is the fraction of the entering air that leaves at the entering state, $$\text{BF}=\frac{t_S-\text{ADP}}{t_M-\text{ADP}}=\frac{64.8-56.7}{80.5-56.7}=\boxed{0.34}$$ A by-pass factor of 0.34 is high for a chilled-water coil — typical four- to six-row selections sit at 0.05 to 0.15 — which says the plant as specified needs a deeper coil or a lower face velocity than the stated flows imply. That observation is part of the answer, not a defect in it.
5056626975818894100051014192420%40%60%80%Dry-bulb temperature (°F)W (lb/1000 lb da)Problem 1 — mix O+R → M, coil M→S, room S→ROMRSADP
Part (b) — operating cycle on the psychrometric chart. O + R mix along the dashed tie-line to M; the coil process M→S extends (dashed) to the apparatus dew point on the saturation curve; the room process S→R runs back at RSHF = 0.85.
Pointdb (°F)wb (°F)$h$ (Btu/lb)dew point (°F)$v$ (ft³/lb)
O outdoor90.081.545.1878.914.334
R room78.067.031.4661.413.808
M mixed80.570.534.3266.013.918
S supply64.861.827.6560.213.457
ADP56.756.724.2956.713.246
ResultValue
(c) Room sensible heat factor, RSHF0.850
(c) Grand sensible heat factor, GSHF0.579
(d) Supply-air condition64.8 °F db / 61.8 °F wb, $W$ = 0.01111, 85 % RH
(d) Supply-air quantity1,006 lbₕₐ/min = 13,540 cfm at the supply state (14,000 cfm mixed)
(e) Total energy input (coil duty)402,200 Btu/h = 33.5 tons refrigeration
(f) Coil apparatus dew point56.7 °F
(f) Coil by-pass factor0.34
← Paper overview