NivaarExam PrepOfficial exam papers ↗

22-Mec-B2 Environmental Control in Buildings · Undated paper

Question 6 of 8: Equal-friction duct sizing

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, May 2019 — 16-Mec-B2 Environmental Control in Buildings. Three hours, open book: any textbooks, references or notes may be used and any non-communicating calculator is permitted, but computers, internet and smart phones are prohibited. Candidates are told to bring both an environmental-control text and steam tables. Eight problems are printed — Problem 1 is 30 points, Problem 2 is 10 points and Problems 3 to 8 are 20 points each — and candidates solve five, indicating on the cover of the first workbook which five are to be graded. Psychrometric charts and the refrigerant pressure–enthalpy diagram are attached as the last three pages. Cover-page instruction 1 asks for a clear statement of the assumption(s) wherever the interpretation is open, and several problems below need one. All eight problems are worked here, because this set is a study resource rather than a three-hour sitting.

Reference texts for this subject.

Check: every psychrometric state below is computed from the ASHRAE Ch. 1 formulations rather than read off the attached chart, and every mixing state is obtained from the exact mass and energy balances (humidity ratio and enthalpy mass-weighted, dry bulb then derived). Chart readings will differ in the last displayed digit; the physics does not.

Problem 6: Equal-friction duct sizing (20 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. A five-section low-velocity system carrying 300 cfm total, with the three terminal losses printed on the figure and 0.14 in. wg of total pressure at the plenum.

SectionServesFlow (cfm)Length (ft)
A — plenum to J1everything30020
B1 — riser off J1diffuser 1 (0.05 in. wg)8012
B — J1 to J2outlets 2 and 32208
C — drop off J2diffuser 3 (0.036 in. wg)12015
D — run-out off J2grille 2 (0.04 in. wg)1008 + 15 = 23

Find. A round duct size for each of the five sections, and the balancing each run then needs.

Approach. Identify the run with the least pressure per foot available — the index run — set the design friction rate from it, size every section at that rate, round up to commercially available diameters, and finish by checking each path against the 0.14 in. wg budget.

  1. Find the index run. Each run must fit its duct friction plus its terminal loss inside 0.14 in. wg, so its allowable friction rate is $(0.14-\Delta p_{term})/L \times 100$: $$\text{run 1 (A+B1)}:\ \frac{0.14-0.050}{32}(100)=0.281\ \text{in. wg/100 ft}$$ $$\text{run 2 (A+B+D)}:\ \frac{0.14-0.040}{51}(100)=0.196\ \text{in. wg/100 ft}$$ $$\text{run 3 (A+B+C)}:\ \frac{0.14-0.036}{43}(100)=0.242\ \text{in. wg/100 ft}$$ The smallest governs, so run 2 — the 100 cfm grille, longest at 51 ft — is the index run and the design rate is $$\boxed{\Delta p/L = 0.196\ \text{in. wg per 100 ft}}$$
  2. Size at that rate. For each section the diameter is the one satisfying $$\frac{\Delta p}{L}=\frac{f}{D}\cdot\frac{\rho V^2}{2g_c},\qquad \frac{1}{\sqrt f}=-2\log_{10}\!\left(\frac{\varepsilon}{3.7D}+\frac{2.51}{Re\sqrt f}\right)$$ with standard air ($\rho = 0.075\ \text{lb/ft}^3$, $\nu = 1.57\times10^{-4}\ \text{ft}^2/\text{s}$) and galvanised roughness $\varepsilon = 0.0003$ ft — which is precisely what the ASHRAE friction chart plots. The calculated diameters are 7.57, 4.62, 6.74, 5.38 and 5.02 in.
  3. Round up to available sizes. Round duct is made in whole-inch increments, and rounding up keeps every section at or below the design rate: $$A \to 8\ \text{in},\quad B_1 \to 5\ \text{in},\quad B \to 7\ \text{in},\quad C \to 6\ \text{in},\quad D \to 6\ \text{in}$$ Velocities are then 859, 587, 823, 611 and 509 fpm — all comfortably inside the 1,000–1,200 fpm ceiling that keeps a low-pressure system quiet, so no size has to be increased for noise.
  4. Section losses at the selected sizes. Recomputing the friction rate at the rounded diameters: $$A:\ 0.150 \Rightarrow 0.0299,\quad B_1:\ 0.134 \Rightarrow 0.0161,\quad B:\ 0.163 \Rightarrow 0.0130$$ $$C:\ 0.115 \Rightarrow 0.0172,\quad D:\ 0.082 \Rightarrow 0.0190\ \ \text{in. wg}$$ (rate in in. wg/100 ft, then the section loss over its own length).
  5. Check each path against the budget. $$\text{run 1}:\ 0.0299+0.0161+0.050=0.096\ \text{in. wg}$$ $$\text{run 2}:\ 0.0299+0.0130+0.0190+0.040=0.102\ \text{in. wg}$$ $$\text{run 3}:\ 0.0299+0.0130+0.0172+0.036=0.096\ \text{in. wg}$$ Every path fits inside 0.14 in. wg, and the index run has the largest demand as it should.
  6. Balancing. Because each diameter was rounded up, all three runs finish with surplus pressure: 0.044, 0.038 and 0.044 in. wg respectively. The system is therefore self-balancing to within 0.006 in. wg — the runs are within 6 % of one another — and the practical instruction is to fit a balancing damper in each branch and set them to absorb the surplus, or, better, to reduce the plenum pressure to about 0.102 in. wg and save the fan energy. The near-equality of the three surpluses is the equal-friction method working as intended.
plenum0.14 in. wg availableA: 20 ft, 300 cfm, 8 inB: 8 ft, 220 cfm, 7 inB1: 12 ft, 80 cfm, 5 in80 cfmdiffuser 0.05 in. wgD: 8 + 15 ft100 cfm, 6 ingrille 0.04 in. wgC: 15 ft, 120 cfm, 6 in120 cfmdiffuser 0.036 in. wgJ1J2Problem 6 — duct network, selected round sizes at 0.196 in. wg / 100 ft
Problem 6 — the duct network with the selected round sizes. The index run is plenum → A → B → D → 100 cfm grille, 51 ft of duct against 0.100 in. wg of available friction.
SectionFlow (cfm)Length (ft)Calculated $D$ (in)Selected $D$ (in)Velocity (fpm)Loss (in. wg)
A300207.5788590.030
B180124.6255870.016
B22086.7478230.013
C120155.3866110.017
D100235.0265090.019
RunDuct + terminal loss (in. wg)Surplus to be dampered (in. wg)
1 — 80 cfm diffuser0.0960.044
2 — 100 cfm grille (index)0.1020.038
3 — 120 cfm diffuser0.0960.044
Check: as the question asks, the assumptions are stated. Standard air at 0.075 lb/ft³; galvanised round duct, $\varepsilon = 0.0003$ ft, so the Colebrook–White solution reproduces the ASHRAE friction chart to within reading accuracy. Dynamic losses at the two tees and the two elbows are neglected, which is the usual first-pass treatment of the equal-friction method; adding them as equivalent lengths (about 15 ft per branch take-off at these sizes) would consume most of the surplus found in step 6 and would move sections A and D up one size. The 8 ft rise on run D is counted as duct length. Duct sizes are restricted to whole inches, and diameters are rounded up rather than to nearest so that no section exceeds the design friction rate.