22-Mec-B2 Environmental Control in Buildings · Undated paper
Question 3 of 8: Winter plant — preheat, mix, heating coil and steam humidifier
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Examinations, May 2019 — 16-Mec-B2 Environmental
Control in Buildings. Three hours, open book: any textbooks, references or notes may be used and
any non-communicating calculator is permitted, but computers, internet and smart phones are
prohibited. Candidates are told to bring both an environmental-control text and steam tables.
Eight problems are printed — Problem 1 is 30 points, Problem 2 is 10 points and
Problems 3 to 8 are 20 points each — and candidates solve five, indicating on the
cover of the first workbook which five are to be graded. Psychrometric charts and the refrigerant
pressure–enthalpy diagram are attached as the last three pages. Cover-page instruction 1 asks
for a clear statement of the assumption(s) wherever the interpretation is open, and several
problems below need one. All eight problems are worked here, because this set is a
study resource rather than a three-hour sitting.
McQuiston, Parker & Spitler, Heating, Ventilating and Air Conditioning: Analysis and
Design, 6th ed. — plant psychrometry, infiltration, duct design, solar heat gain and the
degree-day method.
Jones, Air Conditioning Engineering, 5th ed. — apparatus dew point, coil by-pass
factor, humidification.
Stoecker & Jones, Refrigeration and Air Conditioning, 2nd ed. — vapour-
compression cycle analysis and compressor volumetric efficiency.
Çengel & Boles, Thermodynamics: An Engineering Approach, 9th ed. —
R-134a property tables and steam tables.
Environment and Climate Change Canada, Canadian Climate Normals — Ottawa
heating degree-days; National Energy Code of Canada for Buildings (NECB) 2020 for the net-zero
discussion.
Check: every psychrometric state below is computed from the ASHRAE Ch. 1
formulations rather than read off the attached chart, and every mixing state is obtained from the
exact mass and energy balances (humidity ratio and enthalpy mass-weighted, dry bulb then
derived). Chart readings will differ in the last displayed digit; the physics does not.
Problem 3: Winter plant — preheat, mix, heating coil and steam humidifier (20 points)
Given. A winter plant with an outdoor-air preheater, a mixing box, a main heating
coil and a steam humidifier, all at 101.325 kPa.
Quantity
Symbol
Value
Total heating load of the building
$Q$
155 kW
Space design condition
$R$
21 °C, 30 % RH
Outdoor design condition
$O$
−15 °C, ~0 % RH
Preheat coil exit
state 1
16 °C
Supply condition
$S$
40 °C, 30 % RH
Humidifying steam
—
saturated vapour, 1.13 bar absolute
Ventilation air
—
1/3 of the supply air, by volume
Find. The supply air quantity, the temperature rise across the heating coil, the
steam quantity, and the duties of the heating coil and preheater.
Part (a) — plant sketch. Outdoor air is
preheated from −15 °C to 16 °C, mixed with return air, heated at constant humidity
ratio to state 4, then humidified with saturated steam to the supply state S.
Approach. Fix R and S from the psychrometric relations, size the supply air on the
total enthalpy rise the question specifies, take one third of that volume as ventilation air
at the mixing-box entry, mix exactly, then work backwards from S through the steam-injection line to
find the heating-coil exit and the two duties.
Fix the space and supply states. At 21 °C, $p_{ws} = 2.487$ kPa, so
$p_w = 0.746$ kPa and $W_R = 0.004615\ \text{kg/kg}$, $h_R = 32.85\ \text{kJ/kg}_{da}$. At 40 °C,
$p_{ws} = 7.384$ kPa, so $W_S = 0.01390\ \text{kg/kg}$, $h_S = 76.04\ \text{kJ/kg}_{da}$ and
$v_S = 0.9069\ \text{m}^3/\text{kg}_{da}$.
Part (b) — size the supply air on the stated total load. The supply
air must deliver the whole 155 kW between its own state and the space state:
$$\dot m_{da}=\frac{Q}{h_S-h_R}=\frac{155}{76.04-32.85}=\boxed{3.59\ \text{kg}_{da}/\text{s}}$$
which is $\dot V_S = 3.59 \times 0.9069 = 3.26\ \text{m}^3/\text{s}$ (11,700 m³/h) at the supply
condition. Of that, 70.4 kW arrives as sensible heat and 84.6 kW as the moisture the humidifier put
in — a humidification-dominated load, which is what a space held at 30 % RH against
−15 °C dry outdoor air actually looks like.
Ventilation air, by volume. One third of the supply volume is
$\dot V_{OA} = 3.26/3 = 1.085\ \text{m}^3/\text{s}$. It enters the mixing box at the preheat exit,
16 °C and $W=0$, where $v = 0.8191\ \text{m}^3/\text{kg}$:
$$\dot m_{OA}=\frac{1.085}{0.8191}=1.32\ \text{kg}_{da}/\text{s}\quad\Rightarrow\quad x=\frac{1.32}{3.59}=0.369$$
The mass fraction (36.9 %) exceeds the volumetric third because the ventilation air is cooler and
drier, hence denser, than the supply air it is measured against.
Mix exactly to state M. With $h_1 = 1.006(16) = 16.10\ \text{kJ/kg}$ and
$W_1 = 0$,
$$W_M=0.369(0)+0.631(0.004615)=0.002912,\qquad h_M=0.369(16.10)+0.631(32.85)=26.67\ \text{kJ/kg}$$
$$t_M=\frac{h_M-2501W_M}{1.006+1.86W_M}=19.16\,{}^{\circ}\text{C}\ \ (21.3\ \%\ \text{RH})$$
Part (e) — the steam quantity. The heating coil cannot change $W$, so all the
moisture is added by the humidifier between $W_M$ and $W_S$:
$$\dot m_w=\dot m_{da}(W_S-W_M)=3.59(0.01390-0.002912)=0.0394\ \frac{\text{kg}}{\text{s}}
=\boxed{142\ \text{kg/h}}$$
Part (c) — work back through the steam line to state 4. Saturated vapour at
1.13 bar absolute is at 103.1 °C with $h_g = 2{,}680\ \text{kJ/kg}$. Steam injection is not
adiabatic — it carries its own enthalpy in — so
$$h_4=h_S-(W_S-W_M)h_g = 76.04-0.010988(2680)=46.59\ \text{kJ/kg}$$
and at the unchanged $W_M$,
$$t_4=\frac{46.59-2501(0.002912)}{1.006+1.86(0.002912)}=38.86\,{}^{\circ}\text{C}$$
so the heating coil raises the air from 19.16 °C to 38.86 °C, a rise of
$$\boxed{\Delta t = 19.7\ \text{K}}$$
Note that the steam contributes only 1.1 K of dry-bulb rise on top of its 11 g/kg of moisture; treating
the humidifier as a constant-temperature process would put state 4 at 40 °C and overstate the coil
duty by about 4 kW.
Part (f) — heating-coil capacity.
$$Q_{hc}=\dot m_{da}(h_4-h_M)=3.59(46.59-26.67)=\boxed{71.5\ \text{kW}}$$
Part (f) — preheater capacity. The preheater sees only the outdoor-air
branch, from −15 °C ($h_O = -15.09\ \text{kJ/kg}$) to 16 °C:
$$Q_{ph}=\dot m_{OA}(h_1-h_O)=1.32(16.10+15.09)=\boxed{41.3\ \text{kW}}$$
Its practical job is freeze protection as much as capacity — it is what keeps the mixing box and
the downstream coil above freezing on a design night.
Close the whole plant. Everything entering must equal everything leaving:
$$\dot m_{da}h_S \;\overset{?}{=}\; \dot m_{OA}h_O+(\dot m_{da}-\dot m_{OA})h_R+Q_{ph}+Q_{hc}+\dot m_w h_g$$
$$272.9 = -19.99+74.38+41.3+71.5+105.7 = 272.9\ \text{kW}\ \checkmark$$
The balance closes to nine figures, which validates the two duties, the steam rate and the mixed state
together.
Part (d) — the process on the psychrometric
chart. O→1 preheat at constant $W$; 1 mixes with R to give M; M→4 sensible heating; 4→S
steam injection along a near-vertical line of slope $h_g$; S→R is the space process.
Result
Value
(b) Supply air, dry-air mass flow
3.59 kgₕₐ/s
(b) Supply air, volume flow at 40 °C / 30 % RH
3.26 m³/s (11,700 m³/h)
Ventilation air
1.085 m³/s = 1.32 kgₕₐ/s (36.9 % by mass)
Mixed state M
19.16 °C, $W$ = 0.00291 kg/kg, 21.3 % RH
(c) Heating-coil temperature rise (19.16 → 38.86 °C)
19.7 K
(e) Water vapour (steam) required
0.0394 kg/s = 142 kg/h
(f) Heating-coil capacity
71.5 kW
(f) Preheater capacity
41.3 kW
Check: the paper is over-specified, and cover-page instruction 1 requires the
choice to be declared. It states the space state, the supply state and a 155 kW
“total heating load”. Read as a total-enthalpy duty, the supply air is 3.59 kg/s (used
above). Read as a sensible duty it would be $155/[(1.006+1.86W_S)(40-21)] = 7.91$ kg/s, more
than twice as much, and the humidifier would then have to inject 313 kg/h. The word
“total” is taken at face value here, and it is also the only reading under which both
stated states are used; the sensible reading is quoted so a marker can see the alternative. Two
further assumptions: the ventilation third is measured at the mixing-box entry (16 °C) —
measuring it instead at the raw outdoor state would give 1.42 kg/s and move the coil duty by about
3 kW — and the outdoor air is taken as exactly dry, as the paper's “essentially 0 %
relative humidity” states.