NivaarExam PrepOfficial exam papers ↗

22-Mec-B3 Energy Conversion and Power Generation · December 2019

Question 3 of 8: Condenser Performance

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Examinations, December 2019 — 16-Mec-B3 Energy Conversion and Power Generation. Three hours, closed book. Section A is calculative (Questions 1–5) and Section B descriptive (Questions 6–8); candidates answer four from Section A and two from Section B, six questions of ten marks each for a total of sixty. Reference data are bound in as pages 11–16 and reference formulae and constants as pages 17–20, with steam tables from Thermodynamics and Heat Power supplied. All eight questions are solved here, because the set is a study resource rather than a sitting.

Reference texts.

Check: steam and water properties below are taken from IAPWS-95 (the formulation the bound Granet & Bluestein tables tabulate); readings agree with those tables to better than 0.1 %, which is well inside the rounding the paper itself applies.

Question 3: Condenser Performance (10 marks)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. From the page-13 Koeberg data sheet, the design point of the condenser:

QuantitySymbolValue
Steam flow rate$\dot{m}_s$2996 t/h = 832.2 kg/s
Cooling water flow rate$\dot{m}_w$141 000 t/h = 39 167 kg/s
Cooling water inlet / outlet$T_{w1},\ T_{w2}$13 / 24 °C
Steam inlet temperature$T_s$30 °C
Steam inlet pressure$p$0.043 bar = 4.3 kPa
Terminal temperature difference$\mathrm{TTD}$6 °C
Cooling surface area$A$57 426 m²

Find. The design profile, and then for each of four changed conditions the new cooling-water rise ΔT, the new mean temperature difference θ, the new water outlet temperature and the new condensing temperature, each plotted against the design profile.

Approach. Two equations govern everything: the water-side sensible balance $\dot{Q} = \dot{m}_w c_p \Delta T$ and the surface rating $\dot{Q} = UA\theta$. Because $A$ never changes, each part alters exactly one factor, so ΔT and θ each scale by a single ratio and no iteration is needed. The condensing temperature is not an input — it floats to whatever value the surface requires, and the back pressure follows it.

  1. Establish the design point and confirm the data sheet is self-consistent. The cooling water rises $\Delta T = 24 - 13 = 11$ K, its mean temperature is 18.5 °C, so the mean temperature difference is $\theta = 30 - 18.5 = 11.5$ K and the terminal difference at the outlet end is $30 - 24 = 6$ K, exactly as the sheet prints. The duty follows from the water side, $\dot{Q} = 39\,167 \times 4.19 \times 11 = 1.805 \times 10^6$ kW, i.e. 1805 MW. Divided by the steam flow that is 2169 kJ/kg given up per kilogram of steam, which against $h_{fg} = 2429$ kJ/kg at 30 °C implies a turbine exhaust quality of 0.89 — entirely normal for the last stage of a saturated-steam nuclear turbine, so the sheet is internally consistent. The printed 0.043 bar is $p_{sat}$ at 30 °C, which closes the loop.
  2. Write the two scaling rules once. From $\dot{Q} = \dot{m}_w c_p \Delta T = UA\theta$ with $A$ fixed,$$\Delta T = \frac{\dot{Q}}{\dot{m}_w c_p} \propto \frac{\dot{Q}}{\dot{m}_w} \qquad \theta = \frac{\dot{Q}}{UA} \propto \frac{\dot{Q}}{U}$$ and the condensing temperature is then read off as $T_s = \tfrac{1}{2}(T_{w1} + T_{w2}) + \theta$. Every part below is one substitution into these three relations.
  3. Part (a) — cooling water inlet raised to 18 °C. Neither the duty, the water flow nor $U$ has changed, so $\Delta T$ and $\theta$ both hold at their design values. The whole profile simply translates upward by 5 K: the water leaves at $18 + 11 = 29$ °C, its mean is 23.5 °C, and $$T_s = 23.5 + 11.5 = \boxed{35\ {}^{\circ}\text{C}}$$ The back pressure rises from 4.3 to 5.6 kPa. This is the summer condition, and it costs output: 5 K of extra condensing temperature is worth roughly 1.5 % of turbine work.
  4. Part (b) — turbine load reduced to a quarter. The duty falls to a quarter with the load while the water flow and $U$ are held, so both $\Delta T$ and $\theta$ scale by 0.25: $\Delta T = 2.75$ K and $\theta = 2.875$ K. The water leaves at $13 + 2.75 = 15.75 \approx 16$ °C, its mean is 14.4 °C, and $$T_s = 14.375 + 2.875 = 17.25 \approx \boxed{17\ {}^{\circ}\text{C}}$$ at a back pressure of about 1.9 kPa. In practice a real plant would not be allowed to go this deep — below about 3 kPa the LP exhaust annulus chokes and air in-leakage dominates — so part load is normally run with fewer circulating-water pumps, which is case (c).
  5. Part (c) — cooling water flow halved and $U$ down to 70 %. The duty is unchanged (full load), so halving the flow doubles the rise, $\Delta T = 11/0.5 = 22$ K, and the degraded coefficient widens the mean difference to $\theta = 11.5/0.7 = 16.43$ K. The water now leaves at $13 + 22 = 35$ °C, its mean is 24 °C, and $$T_s = 24 + 16.43 = 40.4 \approx \boxed{40\ {}^{\circ}\text{C}}$$ The back pressure has risen to about 7.4 kPa, and the terminal difference has collapsed to 5 K. Note that the two effects compound: the flow reduction alone would give 35 °C and the $U$ reduction alone about 34 °C, but together they give 40 °C. This is why taking circulating-water pumps out of service at full load is normally interlocked.
  6. Part (d) — $U$ reduced 20 % by fouling. Full duty and full water flow, so $\Delta T$ stays at 11 K and the outlet stays at 24 °C; only the surface has got worse, so $\theta = 11.5/0.8 = 14.375$ K and $$T_s = 18.5 + 14.375 = 32.9 \approx \boxed{33\ {}^{\circ}\text{C}}$$ at about 5.0 kPa. The cooling-water profile is identical to the design one and only the steam line lifts — which is exactly the diagnostic signature of fouling, and the reason condenser performance is monitored by $\theta$ (or by the cleanliness factor $U/U_{design}$) rather than by back pressure alone.
102030inletoutletPosition along tubesTemperature (°C)Designsteam 30 °C1324ΔT=11.00θ=11.50reference10203040inletoutletPosition along tubesTemperature (°C)(a) inlet 18 °Csteam 35 °C1829ΔT=11.00θ=11.505.6 kPa102030inletoutletPosition along tubesTemperature (°C)(b) quarter loadsteam 17 °C1316ΔT=2.75θ=2.881.9 kPa10203040inletoutletPosition along tubesTemperature (°C)(c) half flow, U = 70 %steam 40 °C1335ΔT=22.00θ=16.437.4 kPa10203040inletoutletPosition along tubesTemperature (°C)(d) U down 20 %steam 33 °C1324ΔT=11.00θ=14.385.0 kPa
The page-14 profiles. Grey dotted lines are the design condition (water 13 → 24 °C, steam 30 °C) repeated on every axis; the solid blue line is the cooling water and the solid red line the condensing steam for each new case. Terminal temperatures are rounded to the nearest degree as the question directs, and the bracketed values are ΔT and θ before rounding.
ConditionΔT (K)θ (K)Water in / out (°C)Steam (°C)Back pressure (kPa)
Design11.011.513 / 24304.3
(a) inlet water at 18 °C11.011.518 / 29355.6
(b) quarter load2.752.87513 / 16171.9
(c) half flow, $U$ = 70 %22.016.4313 / 35407.4
(d) $U$ down 20 % (fouling)11.014.37513 / 24335.0