22-Elec-B7 Power Systems Engineering · December 2013
Question 3 of 7: Three-Winding Transformer — Star Equivalent, Powers and Efficiency
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams,
December 2013 — 07-Elec-B7 Power Systems Engineering. Open-book,
three hours, any non-communicating calculator permitted. Seven problems of equal
value (20 points each); any five constitute a complete paper and only the first
five appearing in the answer book are marked. All seven are solved here,
because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the notation this paper uses throughout
(the ABCD two-port, the salient-pole power-angle expressions, the sequence
networks and the equal-area criterion).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the exact
long line (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — three-winding transformers, sequence networks and the
bus-impedance method.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformers (Ch. 2) and synchronous machines
(Ch. 4–5).
Canadian practice: CSA C22.3 No. 1 Overhead Systems, CAN/CSA-C88
and CSA C50 (power transformers and insulating oil), and IEEE C37.91 as adopted
by Canadian utilities for transformer protection.
Problem 3: Three-Winding Transformer — Star Equivalent, Powers and Efficiency (20 points)
Part (a) — five transformer types used in the electric
power system.
Generator step-up (GSU) transformers — large
two-winding units, typically delta on the generator side and grounded wye on the
HV side, that lift generator terminal voltage (13.8–25 kV) to
transmission voltage. The delta winding also isolates the machine from
zero-sequence current.
Autotransformers — used to interconnect two
transmission voltages of comparable magnitude (500/230 kV, 230/115 kV). Because
part of the winding is common, the rating for a given throughput is much smaller
than an equivalent two-winding unit; they nearly always carry a buried delta
tertiary to stabilise the neutral and supply station service.
Distribution transformers — pole-mounted or
pad-mounted units stepping the primary feeder (25 kV, 14.4 kV) down to utilisation
voltage (600/347 V, 240/120 V), designed for very low no-load loss because they
are energised continuously at light load.
Instrument transformers — current transformers (CTs)
and voltage/potential transformers (VTs, CVTs) that scale primary quantities
down to the 5 A / 120 V metering and relaying range while isolating the
secondary circuits from system voltage.
Regulating and phase-shifting transformers —
on-load tap changers for voltage magnitude control, and quadrature-boost
(phase-angle regulating) transformers that inject a series voltage in quadrature
to control real power flow on parallel paths.
Other legitimate answers include grounding (zig-zag) transformers, which
create a zero-sequence source on an ungrounded system, and
converter/rectifier duty transformers for HVDC terminals and industrial
loads.
Given. The star equivalent circuit of a
three-winding transformer, all impedances already referred to the primary side,
with the secondary voltage taken as the reference phasor.
Given data
Quantity
Symbol
Value
Primary branch impedance
$Z_p$
$0.01+j0.08\ \Omega$
Secondary branch impedance
$Z_s$
$0.01+j0.08\ \Omega$
Tertiary branch impedance
$Z_t$
$0.01+j0.08\ \Omega$
Secondary voltage (reference)
$V_2$
$440\angle0^\circ$ V
Secondary current
$I_2$
$100\angle-25^\circ$ A
Tertiary current
$I_3$
$80\angle-35^\circ$ A
Find. The star-point voltage $V_0$, the primary current and
voltage, the tertiary voltage, the apparent power and power factor at all three
terminals, and the efficiency.
[Figure not reproduced: The three-winding transformer of Figure (1) redrawn as its star equivalent. All three branch impedances meet at the internal node V₀; the leakage drops are taken along each leg in turn. See the official exam paper.]
Approach. Walk the star circuit from the known
secondary terminal inwards to the star point, apply Kirchhoff's current law at
that node to get the primary current, then walk outwards along the primary and
tertiary legs; the powers follow from $S=VI^{*}$ at each terminal.
Convert the two known currents to rectangular form.
Every subsequent step is an addition of complex numbers, so this is done once:
$$I_2=100\angle-25^\circ=90.6308-j42.2618\ \text{A},\ I_3=80\angle-35^\circ=65.5322-j45.8861\ \text{A}.$$
Part (a) — walk from the secondary terminal to the star
point. The secondary current leaves the node through $Z_s$, so the
node voltage is the terminal voltage plus that leakage drop:
$$V_0=V_2+I_2Z_s = 440+(90.6308-j42.2618)(0.01+j0.08),$$
$$I_2Z_s = 4.2873+j6.8278\ \text{V},$$
$$\boxed{V_0=444.2873+j6.8278 = 444.34\angle0.880^\circ\ \text{V}}$$
Part (b) — apply KCL at the star point. The primary
current supplies both loaded windings, so
$$I_1=I_2+I_3=(90.6308+65.5322)-j(42.2618+45.8861),$$
$$\boxed{I_1=156.1629-j88.1479 = 179.32\angle-29.443^\circ\ \text{A}}$$
Note the magnitudes do not add: 100 A and 80 A give 179.3 A, not 180 A, because
the two load currents are 10° apart.
Complete part (b) by adding the primary leakage drop.
The primary current flows into the star point through $Z_p$, so the
primary terminal must stand above the node by that drop:
$$V_1=V_0+I_1Z_p,\ I_1Z_p=(156.1629-j88.1479)(0.01+j0.08)=8.6135+j11.6116,$$
$$\boxed{V_1=452.901+j18.439 = 453.28\angle2.331^\circ\ \text{V}}$$
Part (c) — walk outwards along the tertiary leg.
The tertiary current leaves the node, so the tertiary terminal sits
below the star point by its own leakage drop (everything here is
already referred to the primary, which is what the question means by
“referred to the primary side”):
$$V_3=V_0-I_3Z_t,\ I_3Z_t=(65.5322-j45.8861)(0.01+j0.08)=4.3262+j4.7837,$$
$$\boxed{V_3=439.961+j2.044 = 439.97\angle0.266^\circ\ \text{V}}$$
Part (d) — form the complex power at each terminal.
Using $S=VI^{*}$ with the terminal voltage and the terminal current at each
port:
$$S_1=V_1I_1^{*}=81\,283\angle31.775^\circ = 69\,100.9+j42\,801.8\ \text{VA},$$
$$S_2=V_2I_2^{*}=44\,000\angle25.000^\circ = 39\,877.5+j18\,595.2\ \text{VA},$$
$$S_3=V_3I_3^{*}=35\,197\angle35.266^\circ = 28\,737.8+j20\,322.1\ \text{VA}.$$
Read the power factors off the angles of those three
phasors. The power factor is the cosine of the angle of $S$, and all
three are lagging because every angle is positive:
$$\boxed{\cos\varphi_1=0.8501,\ \cos\varphi_2=0.9063,\ \cos\varphi_3=0.8165\ \text{(all lagging)}}$$
The primary power factor is not the average of the other two: it is the power
factor of the phasor sum of the two loads plus the reactive power
consumed inside the three leakage reactances.
Part (e) — take the ratio of output to input real
power. Only the real parts matter:
$$\eta=\frac{P_2+P_3}{P_1}=\frac{39\,877.5+28\,737.8}{69\,100.9}=\frac{68\,615.3}{69\,100.9},$$
$$\boxed{\eta=0.99297 = 99.30\ \text{per cent}}$$
Check the loss balance independently. The 485.6 W deficit
must be exactly the $I^{2}R$ dissipation in the three branch resistances, and it
is:
$$P_{\text{loss}}=(|I_1|^{2}+|I_2|^{2}+|I_3|^{2})(0.01)=(32\,156.9+10\,000+6\,400)(0.01)=485.57\ \text{W}.$$
The agreement to the last figure confirms every current magnitude. Note that
this is a copper-loss-only efficiency: the star model carries no
magnetising branch, so core loss is excluded and a real unit would test a little
below 99.3 %.