NivaarExam PrepOfficial exam papers ↗

22-Elec-B7 Power Systems Engineering · December 2013

Question 6 of 7: Sequence Networks and Single Line-to-Ground Faults

Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)

Notes on this paper

Paper format. National Exams, December 2013 — 07-Elec-B7 Power Systems Engineering. Open-book, three hours, any non-communicating calculator permitted. Seven problems of equal value (20 points each); any five constitute a complete paper and only the first five appearing in the answer book are marked. All seven are solved here, because the set is a study resource.

Reference texts.

Problem 6: Sequence Networks and Single Line-to-Ground Faults (20 points)

Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.

Given. The Figure (4) system — G1 – T1 – bus 1 – L1 – bus 2 – L2 – bus 3 – T2 – G2 — with T1 delta on the machine side and grounded wye (through switch S) on the bus-1 side, and T2 grounded wye on the bus-3 side and delta on the machine side.

Table (2) — component reactances in per unit
SequenceGenerators $G_1$, $G_2$ Transformers $T_1$, $T_2$Lines $L_1$, $L_2$
Positive $X_+$0.2000.2750.225
Negative $X_-$0.1500.2750.225
Zero $X_0$0.0500.2750.225

Find. The three sequence networks, then the phase-A fault current for a single line-to-ground fault at bus 2 with S closed and with S open, and the current for a three-phase fault at bus 2.

positive-sequence network (internal emf 1.0 pu)ref1230.2250.225~E0.20.2750.2750.2~Efaultnegative-sequence network (no internal emf)ref1230.2250.2250.150.2750.2750.15faultzero-sequence network (switch S closed)ref1230.2250.2250.275T₁S0.275T₂G₁: open (Δ winding)G₂: open (Δ winding)fault
Parts (a) and (b): the three sequence networks with switch S closed. Positive and negative sequence have the same topology and differ only in the machine reactance (0.2 against 0.15) and in the absence of internal emf in the negative network. In the zero-sequence network both generators are cut off by the delta windings, so the only paths to the reference are through the two grounded-wye transformer neutrals.

Approach. Build each sequence network from the one-line diagram — the transformer winding connections alone decide the zero-sequence topology — reduce each to a single reactance at bus 2, then connect the three networks in series for the single line-to-ground fault and use the positive network alone for the three-phase fault.

  1. Part (a) — build the positive-sequence network. Every element appears in series along its path, and each generator drives its own internal emf of 1.0 pu behind its positive-sequence reactance. From bus 2, the two sides are identical chains: $$X_{+,\text{left}}=x_{G}+x_{T1}+x_{L1}=0.200+0.275+0.225=0.700\ \text{pu},$$ and the right-hand chain through $L_2$, $T_2$ and $G_2$ has the same three values. The two are in parallel at bus 2, so $$\boxed{X_1=\tfrac12(0.700)=0.350\ \text{pu}}$$
  2. Build the negative-sequence network the same way. The topology is identical; only the machine reactance changes, and there is no internal emf because a balanced generator produces only positive-sequence voltage: $$X_{-,\text{each side}}=0.150+0.275+0.225=0.650\ \text{pu},$$ $$\boxed{X_2=\tfrac12(0.650)=0.325\ \text{pu}}$$
  3. Part (b) — build the zero-sequence network from the winding connections. Zero-sequence current is in phase in all three conductors, so it needs a return path through earth. A delta winding provides a closed path for zero-sequence current to circulate but none for it to leave the winding, so it acts as an open circuit to the rest of the network; a grounded-wye winding connects to the reference bus through its neutral. Here both $T_1$ and $T_2$ have their delta on the machine side, so both generators are isolated from the zero-sequence network entirely, and the only connections to the reference are the two transformer neutrals — T1's through the switch S, T2's solidly.
  4. Reduce the zero-sequence network with S closed. From bus 2 the left path is line $L_1$ then $T_1$ to reference, and the right path is line $L_2$ then $T_2$ to reference: $$X_{0,\text{left}}=x_{L1,0}+x_{T1,0}=0.225+0.275=0.500\ \text{pu} = X_{0,\text{right}},$$ $$\boxed{X_0=\tfrac12(0.500)=0.250\ \text{pu (S closed)}}$$
  5. Part (c) — connect the three networks in series for the single line-to-ground fault. A bolted single line-to-ground fault on phase A imposes $I_b=I_c=0$ and $V_a=0$, which forces the three sequence currents to be equal and the three networks into series: $$I_{a1}=I_{a2}=I_{a0}=\frac{E}{j(X_1+X_2+X_0)}=\frac{1.0}{j(0.350+0.325+0.250)}=\frac{1.0}{j0.925}=1.0811\angle-90^\circ.$$
  6. Sum the sequence components to get the phase current. Since $I_a=I_{a1}+I_{a2}+I_{a0}=3I_{a1}$, $$\boxed{I_{a}=\frac{3(1.0)}{j0.925}=3.2432\angle-90^\circ\ \text{pu (S closed)}}$$
  7. Part (d) — open the switch and rebuild the zero-sequence network. With S open, T1's neutral no longer reaches the reference, so the entire left branch of the zero-sequence network is dead and the only path left is through $L_2$ and $T_2$: $$X_0'=0.225+0.275=0.500\ \text{pu},$$ $$\boxed{I_{a}'=\frac{3(1.0)}{j(0.350+0.325+0.500)}=\frac{3}{j1.175}=2.5532\angle-90^\circ\ \text{pu}}$$
  8. State the effect of the transformer grounding. Opening S raises the zero-sequence reactance from 0.250 to 0.500 pu and drops the ground-fault current from 3.243 to 2.553 pu, a reduction of 21.3 %. That is the general result and the general design trade-off: more grounded-wye neutrals means a stiffer zero-sequence source, hence higher ground-fault duty on the breakers but also a well-defined neutral, ground-fault current large enough for ground relays to see reliably, and neutral-to-earth voltage on the healthy phases held near normal. Fewer grounded neutrals reduces the fault duty but pushes the healthy-phase voltages towards $\sqrt3$ times normal during a ground fault and can leave the ground fault too small to detect. Canadian transmission practice is effectively grounded systems ($X_0/X_1\le3$, $R_0/X_1\le1$), obtained by grounding enough transformer neutrals; distribution feeders are multi-grounded on the same reasoning. Note also that a single line-to-ground fault here draws more current than a three-phase fault (step 9), which is the signature of a strongly grounded system with $X_0\lt X_1$.
  9. Part (e) — use the positive network alone for the three-phase fault. A balanced three-phase fault produces no negative- or zero-sequence current at all, so only $X_1$ appears: $$\boxed{I_F=\frac{1.0}{jX_1}=\frac{1.0}{j0.350}=2.8571\angle-90^\circ\ \text{pu}}$$ The switch position is irrelevant to this answer, because no zero-sequence current flows in a balanced fault.
QuantitySymbol Result
Positive-sequence reactance at bus 2$X_1$ 0.350 pu
Negative-sequence reactance at bus 2$X_2$ 0.325 pu
Zero-sequence reactance, S closed$X_0$0.250 pu
Zero-sequence reactance, S open$X_0'$0.500 pu
SLG fault current, S closed$I_a$ $3.2432\angle-90^\circ$ pu
SLG fault current, S open$I_a'$ $2.5532\angle-90^\circ$ pu
Reduction on opening S—21.3 %
Three-phase fault current$I_F$ $2.8571\angle-90^\circ$ pu
sequence networks in SERIES — single line-to-ground fault~1.0 puX₁ = 0.350positiveX₂ = 0.325negativeX₀ = 0.250zeroI₁ = I₂ = I₀ = 1.081 pu
Part (c): for a bolted single line-to-ground fault the three sequence networks connect in SERIES, which is what makes I₀ equal to I₁ and gives I⃉ = 3I₁. Opening switch S doubles the third element from 0.250 to 0.500 pu.