22-Elec-B7 Power Systems Engineering · December 2013
Question 5 of 7: Short-Circuit Consequences, Transformer Protection, and a Mid-Line Three-Phase Fault
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams,
December 2013 — 07-Elec-B7 Power Systems Engineering. Open-book,
three hours, any non-communicating calculator permitted. Seven problems of equal
value (20 points each); any five constitute a complete paper and only the first
five appearing in the answer book are marked. All seven are solved here,
because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the notation this paper uses throughout
(the ABCD two-port, the salient-pole power-angle expressions, the sequence
networks and the equal-area criterion).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the exact
long line (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — three-winding transformers, sequence networks and the
bus-impedance method.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformers (Ch. 2) and synchronous machines
(Ch. 4–5).
Canadian practice: CSA C22.3 No. 1 Overhead Systems, CAN/CSA-C88
and CSA C50 (power transformers and insulating oil), and IEEE C37.91 as adopted
by Canadian utilities for transformer protection.
Problem 5: Short-Circuit Consequences, Transformer Protection, and a Mid-Line Three-Phase Fault (20 points)
Part (a) — consequences of short-circuit faults.
A short circuit replaces the load impedance with something close to zero, so the
current rises to a value limited only by the source and network reactances
— typically ten to fifty times rated. The damage that follows falls into
four groups.
Thermal and mechanical damage to plant. Fault current heats
conductors adiabatically ($I^{2}t$), so cable insulation, busbar joints and
transformer windings can be destroyed in a fraction of a second. The
simultaneous electromagnetic forces vary as the square of the current and act to
throw parallel conductors apart; transformer windings distort or telescope, and
switchgear bracing fails, if the fault is not cleared inside the equipment's
rated withstand time. At the arc itself the energy release is an arc-flash
hazard governed in Canada by CSA Z462.
Voltage collapse over a wide area. During the fault the
voltage at and near the fault point falls to nearly zero and depresses voltage
across a large region — part (d) below shows buses two and three network
elements away held at only 0.36 to 0.49 pu. Motors stall or trip on undervoltage,
electronic and drive loads drop out, and induction generation disconnects; the
economic loss to industrial customers from a voltage sag is often far larger
than the utility's repair cost.
Loss of synchronism and system instability. With the
terminal voltage depressed, the electrical power a generator can export
collapses while the mechanical input is unchanged, so the rotor accelerates.
If the fault is not cleared before the critical clearing angle is reached the
machine pulls out of step — which is exactly the calculation of Problem 7.
Unbalanced faults additionally inject negative-sequence current, whose
double-frequency rotor currents heat the rotor body and damper windings very
quickly, and zero-sequence current, which raises earth-potential rise and
induces voltage into parallel telecommunication and pipeline plant.
Protection and equipment-rating consequences. The fault
level dictates the interrupting rating of every breaker and the withstand rating
of every bus in the station, and it changes as generation is added, so a
short-circuit study is repeated for every system change. Faults also cause
protection to operate, and an incorrect or slow operation cascades: an
overreaching zone-2 element or a stuck breaker turns a single line fault into a
multiple-element outage.
Part (b) — three transformer protective schemes.
Percentage differential protection (ANSI 87T). Currents are
measured at every winding, referred to a common base by ratio and phase-shift
compensation, and summed. In the healthy transformer the compensated sum is
essentially zero; an internal fault destroys that balance and the relay trips.
The percentage restraint characteristic makes the pickup proportional
to the through current so that CT saturation and tap-changer travel do not cause
false trips, and second-harmonic (inrush) and fifth-harmonic (overexcitation)
restraint prevent operation on energisation and on overfluxing. It is the
primary unit protection of any transformer above a few MVA.
Overcurrent and restricted-earth-fault backup (ANSI 50/51,
51G, 64REF). Time-graded phase and ground overcurrent relays on each
winding provide backup for the differential and cover faults beyond the
transformer. Restricted earth fault compares the neutral current with the
residual of the three phase currents on one grounded-wye winding, which gives it
far better sensitivity to a winding-to-core fault near the neutral end than the
phase differential can achieve.
Mechanical (gas and pressure) protection — Buchholz and
sudden-pressure relays (ANSI 63). An incipient internal fault
decomposes oil into gas. The Buchholz relay, mounted in the pipe between tank
and conservator, collects that gas: slow accumulation raises an alarm, a violent
oil surge trips. The sudden-pressure relay responds to the rate of rise of tank
pressure. Both detect faults that produce very little terminal current —
inter-turn faults, core bolt failures, partial discharge — and so are
complementary rather than redundant to the differential.
Also standard are winding- and oil-temperature protection (49) with alarm and
trip stages, and volts-per-hertz overexcitation protection (24) on generator
step-up units.
Given. The Figure (3) network, with every reactance
in per unit on a common base and both sources at 1.0 pu.
Given data
Element
Symbol
Reactance (pu)
Source behind bus 1
$x_{g1}$
$j0.200$
Source behind bus 2
$x_{g2}$
$j0.150$
Line 1–3
$x_{13}$
$j0.225$
Line 1–4
$x_{14}$
$j0.215$
Line 3–4
$x_{34}$
$j0.125$
Transformer 3–2
$x_{32}$
$j0.035$
Source voltages
$E$
$1.0\angle0^\circ$ pu (both)
Find. The bolted three-phase fault current at the mid-point
of line 1–3, and the resulting voltages at buses 1 and 2.
Figure (3) with the faulted line split into two halves of j0.1125 pu at the new node F, and the Thévenin equivalent the reduction produces. Because both sources are 1.0∠0°, their internal nodes merge into one node in the passive network.
Approach. Split the faulted line at its mid-point to
create a new node F, kill both (identical) sources to find the Thévenin
reactance seen from F, divide 1.0 pu by it for the fault current, then
back-substitute through the reduction to recover the bus voltages.
Part (c) — introduce the fault node. A fault at the
mid-point of line 1–3 splits that line into two equal halves, so
$$x_{1F}=x_{F3}=\tfrac12(0.225)=0.1125\ \text{pu}.$$
Because the two internal emfs are identical at $1.0\angle0^\circ$, no
circulating current flows between them before the fault, the pre-fault voltage
is 1.0 pu everywhere, and in the passive (source-killed) network the two
internal nodes become a single reference node.
Collapse the radial branches that carry no choice.
Bus 2 has only one connection to the rest of the network, through the
transformer to bus 3, so the source behind it and that transformer are in
series:
$$x_{\text{ref}\to3}=x_{g2}+x_{32}=0.150+0.035=0.185\ \text{pu}.$$
Similarly bus 4 lies between buses 1 and 3 with nothing else attached, so it is
a plain series path:
$$x_{1\to3\ \text{(via 4)}}=x_{14}+x_{34}=0.215+0.125=0.340\ \text{pu}.$$
Convert the surviving delta to a star. What remains between
the reference node, bus 1 and bus 3 is a delta of $0.200$ (reference–1),
$0.185$ (reference–3) and $0.340$ (1–3). Its sum is $0.725$, so the
equivalent star arms are
$$Z_1=\frac{(0.340)(0.200)}{0.725}=0.093793,\ Z_3=\frac{(0.340)(0.185)}{0.725}=0.086759,\ Z_{\text{ref}}=\frac{(0.200)(0.185)}{0.725}=0.051034.$$
Call the star centre N.
Combine the two paths from F to the star centre. Node F
reaches N through $0.1125+Z_1$ one way and $0.1125+Z_3$ the other, and those two
are in parallel:
$$\frac{(0.206293)(0.199259)}{0.206293+0.199259}=\frac{0.041105}{0.405552}=0.101357\ \text{pu}.$$
Add the last series arm to get the Thévenin
reactance. The reference node reaches N through $Z_{\text{ref}}$, so
$$\boxed{X_{\text{Th}}=0.101357+0.051034=j0.152392\ \text{pu}}$$
Divide to get the fault current. With pre-fault voltage
1.0 pu at F and a bolted (zero-impedance) three-phase fault,
$$\boxed{I_F=\frac{1.0\angle0^\circ}{j0.152392}=6.5620\angle-90^\circ\ \text{pu}}$$
The current lags 90° because every element in the model is a pure reactance;
in a real network with resistance the angle would be a few degrees less. On a
100 MVA base this is 656 MVA of fault duty at the mid-line point.
Part (d) — back-substitute for the voltage at the star
centre. The whole fault current flows through $Z_{\text{ref}}$, so
$$V_N=1.0-I_F Z_{\text{ref}}=1.0-6.56203(0.051034)=0.665106\ \text{pu}.$$
(The $j$ of the reactance and the $-j$ of the current cancel, leaving a real
result in phase with the sources.)
Divide the fault current between the two paths and recover
$V_1$. The share flowing through the bus-1 side, and the drop it
causes in the star arm $Z_1$, give the bus-1 voltage directly:
$$I_{F,1}=\frac{V_N}{0.206293}=3.22412\ \text{pu},\ I_{F,3}=\frac{V_N}{0.199259}=3.33792\ \text{pu},$$
$$\boxed{V_1=V_N-I_{F,1}Z_1=0.665106-3.22412(0.093793)=0.3627\ \text{pu}}$$
The two shares add to 6.56204 pu, which is the fault current again — a
free check that the division is right.
Recover $V_3$, then walk out to bus 2. The same
construction on the other arm gives
$$V_3=V_N-I_{F,3}Z_3=0.665106-3.33792(0.086759)=0.375514\ \text{pu}.$$
Bus 2 is fed radially from its own source through $0.150+0.035$, so the current
in that path and the drop across the machine reactance are
$$I_{g2}=\frac{1.0-V_3}{0.185}=\frac{0.624486}{0.185}=3.37560\ \text{pu},$$
$$\boxed{V_2=1.0-I_{g2}(0.150)=1.0-0.506340=0.4937\ \text{pu}}$$
Sanity-check the voltage profile. The depressed voltages
should fall away with electrical distance from F, and they do: $V_1=0.363$ and
$V_3=0.376$ at the two ends of the faulted line, $V_4=0.371$ on the parallel
path, and $V_2=0.494$ — the highest of the four because it sits behind the
whole $0.150$ pu of its own machine reactance. Nowhere in the network does the
voltage exceed the pre-fault 1.0 pu, as it must not for a bolted shunt
fault.