22-Elec-B7 Power Systems Engineering · December 2013
Question 7 of 7: Transient Stability by the Equal-Area Criterion
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams,
December 2013 — 07-Elec-B7 Power Systems Engineering. Open-book,
three hours, any non-communicating calculator permitted. Seven problems of equal
value (20 points each); any five constitute a complete paper and only the first
five appearing in the answer book are marked. All seven are solved here,
because the set is a study resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the notation this paper uses throughout
(the ABCD two-port, the salient-pole power-angle expressions, the sequence
networks and the equal-area criterion).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters and the exact
long line (Ch. 4–5), power flow (Ch. 6), symmetrical faults (Ch. 7),
symmetrical components and unsymmetrical faults (Ch. 8–9), transient
stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — three-winding transformers, sequence networks and the
bus-impedance method.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformers (Ch. 2) and synchronous machines
(Ch. 4–5).
Canadian practice: CSA C22.3 No. 1 Overhead Systems, CAN/CSA-C88
and CSA C50 (power transformers and insulating oil), and IEEE C37.91 as adopted
by Canadian utilities for transformer protection.
Problem 7: Transient Stability by the Equal-Area Criterion (20 points)
Given. A machine of internal emf 1.2 pu feeding an
infinite bus of 1.0 pu through a step-up reactance, one series line, and two
identical parallel lines.
Given data
Quantity
Symbol
Value
Internal emf
$E$
1.20 pu
Infinite-bus voltage
$V$
1.00 pu
Transformer / step-up reactance
$x_t$
$j0.03$ pu
Line 1
$x_1$
$j0.05$ pu
Line 2
$x_2$
$j0.08$ pu
Line 3
$x_3$
$j0.08$ pu
Mechanical (real) load
$P_m$
3.00 pu
Find. The pre-fault load angle; whether the machine stays in
synchronism for a sustained mid-line fault on line 3; and, if it does, the
maximum angle the rotor swings to.
Figure (5) with the sustained three-phase fault marked at the mid-point of Line 3. The fault is never cleared, so there are only TWO power-angle curves in this problem — pre-fault and during-fault — not the usual three.
Approach. Compute the pre-fault transfer reactance
and hence the pre-fault power-angle curve, get $\delta_0$ from
$P_m=P_{\max}\sin\delta_0$, reduce the faulted network by a
delta–star–delta pair of transformations to find the during-fault
transfer reactance, then apply the equal-area criterion between the two
curves.
Part (a) — form the pre-fault transfer reactance.
Lines 2 and 3 are identical and in parallel, so
$$X_{\text{pre}}=x_t+x_1+\tfrac12 x_2=0.03+0.05+0.04=0.12\ \text{pu},$$
$$P_{\max}=\frac{EV}{X_{\text{pre}}}=\frac{(1.2)(1.0)}{0.12}=10.0\ \text{pu}.$$
Solve for the initial power angle. In the steady state the
electrical output equals the mechanical input:
$$3.0=10.0\sin\delta_0\ \Rightarrow\ \sin\delta_0=0.30,$$
$$\boxed{\delta_0=17.458^\circ=0.30469\ \text{rad}}$$
The machine is lightly loaded relative to its pull-out capability — only
30 % of $P_{\max}$ — which is what will give it the margin found
below.
Part (b) — set up the faulted network. A three-phase
short at the mid-point of line 3 splits that line into two halves of $j0.04$ pu
and grounds the junction. Calling the sending bus B (after $x_t+x_1=0.08$ pu),
the infinite bus C, and the fault point F, the elements between B, C and F form
a delta:
$$x_{BC}=0.08\ \text{(line 2)},\ x_{BF}=0.04,\ x_{CF}=0.04.$$
Convert that delta to a star. With
$\sum x=0.08+0.04+0.04=0.16$,
$$Z_B=\frac{(0.08)(0.04)}{0.16}=0.02,\ Z_C=\frac{(0.08)(0.04)}{0.16}=0.02,\ Z_F=\frac{(0.04)(0.04)}{0.16}=0.01.$$
Calling the star centre N, the network is now a simple star with $0.08+0.02=0.10$
from the machine to N, $0.02$ from N to the infinite bus, and $0.01$ from N to
ground.
Convert that star back to a delta to extract the transfer
reactance. The E-to-V branch of the equivalent delta is what carries
power, and it is
$$X_f=\frac{(0.10)(0.02)+(0.02)(0.01)+(0.01)(0.10)}{0.01}=\frac{0.0032}{0.01}=0.32\ \text{pu},$$
$$P_{\max,f}=\frac{(1.2)(1.0)}{0.32}=3.75\ \text{pu}.$$
The grounded star arm $Z_F$ appears in the denominator, which is precisely why a
fault electrically closer to the machine (smaller $Z_F$) would throttle the
transfer harder.
Establish that an equilibrium exists at all during the
fault. This is the decisive observation and it is worth making before
any integration: $P_{\max,f}=3.75\ \text{pu}\gt P_m=3.0\ \text{pu}$, so the faulted
curve still crosses the mechanical input line. It does so at
$$\delta_1=\sin^{-1}\frac{3.0}{3.75}=53.130^\circ,\ \delta_{\text{lim}}=180^\circ-53.130^\circ=126.870^\circ.$$
Had $P_{\max,f}$ fallen below 3.0 pu the rotor would have accelerated
monotonically and the machine would be unstable with no further calculation
needed.
Compute the accelerating area. From $\delta_0$ to
$\delta_1$ the input exceeds the output, and the area between them is
$$A_1=\int_{\delta_0}^{\delta_1}\!\left(P_m-P_{\max,f}\sin\delta\right)d\delta=P_m(\delta_1-\delta_0)+P_{\max,f}(\cos\delta_1-\cos\delta_0),$$
$$A_1=3.0(0.92730-0.30469)+3.75(0.60000-0.95394)=1.86781-1.32727=0.54054.$$
Compute the largest decelerating area the faulted curve can
supply. Beyond $\delta_1$ the output exceeds the input, and that
remains true until $\delta_{\text{lim}}$, past which the machine can never
recover:
$$A_{2,\max}=\int_{\delta_1}^{\delta_{\text{lim}}}\!\left(P_{\max,f}\sin\delta-P_m\right)d\delta=P_{\max,f}(\cos\delta_1-\cos\delta_{\text{lim}})-P_m(\delta_{\text{lim}}-\delta_1),$$
$$A_{2,\max}=3.75(0.60000+0.60000)-3.0(2.21430-0.92730)=4.50000-3.86100=0.63899.$$
Compare the two areas and give the verdict. The available
decelerating area exceeds the accelerating area,
$$\boxed{A_{2,\max}=0.6390 \gt A_1=0.5405\ \Rightarrow\ \text{the system REMAINS STABLE}}$$
with a stability margin of $A_{2,\max}/A_1=1.18$. Physically, the fault does not
remove the transfer path entirely — line 2 and the healthy half of line 3
keep 37.5 % of the pre-fault synchronising power available — and the
machine was only 30 % loaded, so the swing is arrested before the rotor reaches
the point of no return.
Part (c) — find the maximum swing angle by equating the two
areas. The rotor stops when the net area vanishes, so $\delta_m$ solves
$$P_m(\delta_m-\delta_0)+P_{\max,f}(\cos\delta_m-\cos\delta_0)=0,$$
$$3.0\,\delta_m+3.75\cos\delta_m=3.0(0.30469)+3.75(0.95394)=4.49135.$$
Solving this transcendental equation numerically on the interval
$(\delta_0,\delta_{\text{lim}})$ gives
$$\boxed{\delta_m=1.89333\ \text{rad}=108.480^\circ}$$
which is comfortably inside the $126.870^\circ$ limit — the same
conclusion as step 9, reached by the other route.
Check: the equal-area criterion
assumes constant mechanical input, constant internal emf behind a constant
transient reactance, and no damping. Neglecting damping is conservative for the
first swing (real damper windings would reduce $\delta_m$), but with a
sustained fault the machine sits at reduced output indefinitely, so in
practice protection must clear it: a real system would never be left in this
condition, and the 108° result is a first-swing answer only.
The equal-area construction. A₁ (red) is the accelerating area from δ₀ to δ₁; A₂ (green) is the decelerating area that stops the rotor at δ = 108.5°. Because the swing halts short of δₗ = 126.9°, where the faulted curve falls back through Pₘ, the machine stays in step.