Question 3 of 7: Transformer Insulating Oil and the Cantilever Equivalent Circuit
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2013 —
07-Elec-B7 Power Systems Engineering. Open-book, three hours, non-communicating
calculator permitted. Seven problems of equal value (20 points each); any five
constitute a complete paper and only the first five appearing in the answer book
are marked. All seven are solved here, because the set is a study
resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the source of this paper's notation
(ABCD two-port, the “cantilever” transformer equivalent, and the
equal-area treatment of transient stability).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters (Ch. 4–5),
power flow (Ch. 6), symmetrical faults (Ch. 7), symmetrical components and
unsymmetrical faults (Ch. 8–9), transient stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — sequence networks and fault calculations.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformers (Ch. 2) and synchronous machines (Ch. 4–5).
Canadian practice: CSA C22.3 No. 1 Overhead Systems (conductor
temperature, sag and clearance), CAN/CSA-C88 and CSA C50 (power transformers and
insulating oil), and CSA C22.3 No. 1 Annex on fault-current duty.
Problem 3: Transformer Insulating Oil and the Cantilever Equivalent Circuit (20 points)
Part (a) — what the oil in the tank is for. Mineral
insulating oil (or a synthetic ester in modern fire-point-sensitive installations)
performs four distinct duties simultaneously, and a complete answer names all
four.
Dielectric. The oil is first of all an insulant. Its dielectric
strength, of the order of 30 kV across a 2.5 mm gap for new oil to
ASTM D877 / CSA test methods, is far higher than that of air, so it permits much
smaller clearances between windings and between winding and tank than a dry design
of the same rating. Just as importantly it impregnates the cellulose
paper and pressboard, displacing air from voids where partial discharge would
otherwise start; a paper-oil composite is a far better insulation system than
either component alone because the oil fills the pores and the paper subdivides
the oil gaps.
Coolant. The oil is the heat-transfer medium. Losses generated in the
windings and core are carried by natural or forced convection to the tank walls,
radiators or heat exchangers — the ONAN, ONAF, OFAF and ODAF cooling classes
are simply descriptions of how the oil and the outside air or water are moved. Oil
has roughly 1600 times the volumetric heat capacity of air, which is why an
oil-filled unit can be a fraction of the size of a dry-type unit of the same
rating.
Arc quenching and protection of the insulation system. The oil
suppresses and extinguishes incipient arcing, for instance at a tap-changer
contact, by cooling the arc column and by the de-ionising action of the gases
evolved. It also excludes oxygen and moisture from the cellulose, which is what
actually determines transformer life: paper degrades by hydrolysis and oxidation,
and it is the water and oxygen dissolved in the oil that drive both.
Diagnostic medium. Because every incipient fault decomposes oil or
paper into characteristic gases, the oil is also the transformer's condition
monitor. Dissolved-gas analysis (hydrogen and acetylene for arcing, ethylene for
hot spots, carbon oxides for paper degradation), together with routine tests for
breakdown voltage, acidity, interfacial tension, water content and furanic
compounds, allows a fault to be identified and trended long before it becomes a
failure. In Canadian practice these tests and the acceptance limits are covered by
the CSA C50 / CAN-CSA-C88 series and by IEEE C57.104 for the gas
interpretation.
Check: the “cantilever”
equivalent circuit of Figure 1 places the entire excitation branch
($G_c$ in parallel with $-jB_m$) directly across the primary terminals,
with $R_{eq}+jX_{eq}$ between that node and the referred secondary. All four
parts below are solved on that topology, as the question directs. (The more
familiar “exact” T-circuit splits the series impedance either side of
the shunt branch; on this transformer the difference in $|V_1|$ is under
0.1 %, but the cantilever model is what makes parts (b) and (d) closed-form
rather than iterative.)
[Figure not reproduced: Figure 3.1 — the cantilever equivalent circuit referred to the 2200 V side, redrawn from Figure (1) of the paper. See the official exam paper.]
Given.
Quantity
Value
Meaning
Rating
250 kVA, 2200/220 V, 60 Hz, 1-phase
nameplate
$a$
$2200/220 = 10$
turns ratio (HV : LV)
$R_{eq}$
$0.475\ \Omega$
equivalent series resistance, HV referred
$X_{eq}$
$2.15\ \Omega$
equivalent series reactance, HV referred
$G_c$
$2.5\times10^{-4}\ \text{S}$
core-loss conductance
$B_m$
$4\times10^{-4}\ \text{S}$
magnetising susceptance
Find. (b) $|V_1|$ and $|I_1|$ for a 180 kVA, 0.8 lagging load;
(c) $S_1$, primary power factor and voltage regulation at that load; (d) working
backwards from a stated primary condition of 125 A at 2200 V and 0.8 lagging, the
secondary kVA, the efficiency and the load power factor.
Approach. Refer everything to the 2200 V side once, then walk
the cantilever circuit in the direction the data allows: outward from the load in
(b) and (c), inward from the primary in (d).
Part (b) — refer the load to the high-voltage side.
With $a = 10$, a secondary at rated 220 V refers to
$V_2' = a V_2 = 2200\angle 0^\circ$ V, taken as the reference phasor. The referred
load current follows from the apparent power, which is invariant under referral:
$$I_2'=\frac{S_2}{V_2'}\angle{-\cos^{-1}(0.8)}
=\frac{180\,000}{2200}\angle-36.87^\circ
=81.8182\,\text{A}\angle-36.87^\circ$$
(the actual secondary current is ten times this, 818.2 A).
Primary voltage. In the cantilever model the whole series
impedance lies between the referred secondary and the primary node, and the entire
load current flows through it:
$$V_1=V_2'+I_2'\left(R_{eq}+jX_{eq}\right)
=2200+\left(81.8182\angle-36.87^\circ\right)\left(0.475+j2.15\right)$$
$$\boxed{V_1=2339.58\,\text{V}\angle2.88^\circ\ \ \Rightarrow\ \ |V_1|
=2339.6\ \text{V}}$$
The magnitude of the series drop is 180.2 V,
about 8.2 % of rated; the voltage regulation computed in part (c) is
smaller (6.34 %) because that compares magnitudes rather than the phasor
difference. Both are what a 0.8-lagging load does to a unit with an $X/R$ ratio of
4.5.
Excitation current, then primary current. The shunt branch
sees the primary voltage in this model, so
$$I_\varphi=V_1\left(G_c-jB_m\right)
=\left(2339.58\angle2.88^\circ\right)\left(2.5\times10^{-4}-j4\times10^{-4}\right)
=1.1036\,\text{A}\angle-55.12^\circ$$
and by Kirchhoff's current law at the primary node
$$I_1=I_2'+I_\varphi=81.8182\angle-36.87^\circ+1.1036\angle-55.12^\circ
\;\Longrightarrow\;\boxed{|I_1|=82.87\ \text{A}}$$
The excitation current is only 1.10 A, about 1.3 % of
the load current, which is why it is so often dropped — but it is what
parts (c) and (d) are testing, so it is kept.
Part (c) — apparent power and power factor at the primary.
$$S_1=V_1I_1^{*}=193874.3\,\text{VA}\angle39.99^\circ
\;\Longrightarrow\;\boxed{S_1=193.87\ \text{kVA}}$$
with $P_1 = 148.55$ kW and
$Q_1 = 124.58$ kvar. The primary power-factor angle
is $\angle V_1-\angle I_1 =
39.99^\circ$, so
$$\boxed{\cos\varphi_1=0.7662\ \text{lagging}}$$
Note it is worse than the 0.8 of the load: the magnetising branch draws
0.91 A of extra lagging current, and the series
reactance absorbs a further
14.39 kvar.
Voltage regulation. Regulation compares the secondary voltage
at no load with the secondary voltage on load, at constant primary voltage. In the
cantilever model no load means no current through $R_{eq}+jX_{eq}$, so the
no-load referred secondary voltage is exactly $|V_1|$:
$$\text{VR}=\frac{|V_1|-|V_2'|}{|V_2'|}\times100\,\%
=\frac{2339.6-2200}{2200}\times100\,\%
\;\Longrightarrow\;\boxed{\text{VR}=6.34\,\%}$$
As a by-product, the efficiency at this load is
$\eta = P_2/P_1 = 144.0/
148.5 = 96.94\,\%$.
Part (d) — now work inward from the primary. The data
changes: $V_1 = 2200\angle 0^\circ$ V is now the reference and
$I_1 = 125\angle-36.87^\circ$ A is given. Because the shunt branch is across the
primary in this model, its current is known immediately and does not depend on the
load at all:
$$I_\varphi=V_1(G_c-jB_m)=2200\left(2.5\times10^{-4}-j4\times10^{-4}\right)
=1.0377\,\text{A}\angle-57.99^\circ$$
Referred secondary current and voltage. Subtracting the
excitation current from the primary current leaves the load branch,
$$I_2'=I_1-I_\varphi=125.0000\angle-36.87^\circ-1.0377\angle-57.99^\circ
=124.0326\,\text{A}\angle-36.70^\circ$$
and the series drop then gives the referred secondary voltage
$$V_2'=V_1-I_2'\left(R_{eq}+jX_{eq}\right)=2001.39\,\text{V}\angle-5.12^\circ$$
On the real 220 V winding that is
200.1 V at
1240.3 A.
Secondary loading, efficiency and load power factor.
$$S_2=V_2'I_2'^{*}=248237.4\,\text{VA}\angle31.58^\circ
\;\Longrightarrow\;\boxed{|S_2|=248.24\ \text{kVA}}$$
which is 99.3 % of the 250 kVA nameplate — the transformer is essentially
fully loaded, a useful sanity check on the arithmetic. With
$P_1 = |V_1||I_1|\cos\varphi_1 = 2200\times125\times0.8 =
220.0$ kW,
$$\eta=\frac{P_2}{P_1}=\frac{211.48}
{220.0}\times100\,\%
\;\Longrightarrow\;\boxed{\eta=96.13\,\%}$$
and the load power factor is the cosine of the angle between $V_2'$ and $I_2'$,
$$\cos\varphi_2=\cos\!\left(-5.12^\circ
-\left(-36.70^\circ\right)\right)
\;\Longrightarrow\;\boxed{\cos\varphi_2=0.8519\ \text{lagging}}$$
The load is better than the 0.80 seen at the primary, for the same reason
as in part (c) read backwards: the magnetising branch and the leakage reactance
have already taken their share of the reactive power upstream of the load.