Question 6 of 7: Unsymmetrical Faults Seen at Breaker B 2
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, May 2013 —
07-Elec-B7 Power Systems Engineering. Open-book, three hours, non-communicating
calculator permitted. Seven problems of equal value (20 points each); any five
constitute a complete paper and only the first five appearing in the answer book
are marked. All seven are solved here, because the set is a study
resource.
Reference texts.
M. E. El-Hawary, Electrical Power Systems: Design and Analysis,
rev. ed., IEEE Press/Wiley — the source of this paper's notation
(ABCD two-port, the “cantilever” transformer equivalent, and the
equal-area treatment of transient stability).
J. D. Glover, T. J. Overbye and M. S. Sarma, Power System Analysis and
Design, 6th ed., Cengage — transmission-line parameters (Ch. 4–5),
power flow (Ch. 6), symmetrical faults (Ch. 7), symmetrical components and
unsymmetrical faults (Ch. 8–9), transient stability (Ch. 11).
J. J. Grainger and W. D. Stevenson, Power System Analysis,
McGraw-Hill — sequence networks and fault calculations.
S. J. Chapman, Electric Machinery Fundamentals, 5th ed.,
McGraw-Hill — transformers (Ch. 2) and synchronous machines (Ch. 4–5).
Canadian practice: CSA C22.3 No. 1 Overhead Systems (conductor
temperature, sag and clearance), CAN/CSA-C88 and CSA C50 (power transformers and
insulating oil), and CSA C22.3 No. 1 Annex on fault-current duty.
Problem 6: Unsymmetrical Faults Seen at Breaker B2(20 points)
Find. The fault current for a three-phase, a single-line-to-ground,
a double-line-to-ground and a line-to-line fault at bus 3, and the identification of
the least severe of the four.
Approach. Build the three sequence networks looking back from
bus 3, then apply the standard sequence-network interconnections: series-parallel
for each fault type, transform back to phase currents. Because the system is
radial — source, transformer, bus 1, line, bus 2, line, bus 3 — every
ampere reaching a fault at bus 3 must pass through breaker B2, so the
currents asked for are the total fault currents.
[Figure not reproduced: Figure 6.1 — the three sequence networks seen from bus 3. The delta winding of the transformer blocks zero-sequence current from the source, so the grounded wye is the only zero-sequence source and the transformer contributes only its own j5 Ω. See the official exam paper.]
Assemble the sequence impedances at the fault point. Positive
and negative sequence see the transformer and both line sections in series:
$$Z_1=Z_2=j5+j10+j10=j25\ \Omega .$$
Zero sequence is different. The transformer is delta on the source side and
grounded-wye on the line side, so zero-sequence current can circulate in the delta
but cannot pass through to the generator: looking back from the line, the zero
network sees the transformer's own $j5\ \Omega$ to the reference bus, and nothing
beyond. Adding the two line sections at their much larger zero-sequence value,
$$Z_0=j5+j30+j30=j65\ \Omega .$$
The prefault voltage at bus 3 is the phase value
$V_f = 34.5/\sqrt{3} = 19919$ V.
Part (a) — symmetrical three-phase fault. A balanced
fault excites only the positive-sequence network:
$$I_f^{(3\phi)}=\frac{V_f}{Z_1}
=\frac{19919}{j25}
\;\Longrightarrow\;\boxed{I_f^{(3\phi)}=796.7\ \text{A}
\ \text{(lagging }90^\circ)}$$
Part (b) — single line to ground. A phase-a-to-ground
fault puts the three sequence networks in series, so
$I_{a1}=I_{a2}=I_{a0}=V_f/(Z_1+Z_2+Z_0)$ and the faulted-phase current is three
times that:
$$I_a=\frac{3V_f}{Z_1+Z_2+Z_0}
=\frac{3\times19919}{j(25+25+65)}
=\frac{59756}{j115}$$
$$\boxed{I_f^{(\text{SLG})}=519.6\ \text{A}}$$
It is smaller than the three-phase value precisely because
$Z_0 = j65\ \Omega$ is much larger than $Z_1$ — the long zero-sequence path
of the two lines dominates the series sum.
Part (c) — double line to ground, sequence components.
A b–c–ground fault puts the negative and zero networks in
parallel and that combination in series with the positive network:
$$I_{a1}=\frac{V_f}{Z_1+\dfrac{Z_2Z_0}{Z_2+Z_0}}
=\frac{19919}{j\left(25+\dfrac{25\times65}{90}\right)}
=\frac{19919}{j43.056}
=462.6\ \text{A}\ \angle-90^\circ$$
The other two sequence currents follow from the current-division rule at that
parallel pair:
$$I_{a2}=-I_{a1}\frac{Z_0}{Z_0+Z_2}=334.1\ \text{A}
\ \angle+90^\circ,\qquad
I_{a0}=-I_{a1}\frac{Z_2}{Z_0+Z_2}=128.5\ \text{A}
\ \angle+90^\circ .$$
Double line to ground, phase currents. Recombining with
$a = 1\angle120^\circ$,
$$I_b=I_{a0}+a^{2}I_{a1}+aI_{a2},\qquad
I_c=I_{a0}+aI_{a1}+a^{2}I_{a2}$$
$$\boxed{|I_b|=|I_c|=716.4\ \text{A}}$$
and the current returning through earth is
$$I_g=3I_{a0}=385.5\ \text{A}.$$
The healthy phase carries $I_a = I_{a0}+I_{a1}+I_{a2} = 0$, as it must. Both
numbers matter in practice: the phase elements of the relay at
B2 see 716 A while the ground element sees
386 A.
Part (d) — line to line. A b–c fault clear of
ground excites no zero sequence; the positive and negative networks are connected
in opposition, so $I_{a1}=-I_{a2}=V_f/(Z_1+Z_2)$ and
$$I_b=-I_c=-j\sqrt{3}\,\frac{V_f}{Z_1+Z_2}
=-j\sqrt{3}\times\frac{19919}{j50}$$
$$\boxed{|I_f^{(\text{LL})}|=690.0\ \text{A}}$$
which is $\sqrt{3}/2 = 0.866$ of the three-phase value — the classic result
for a fault fed through equal positive and negative sequence impedances.
Part (e) — which fault is the least severe? Collecting
the four magnitudes of the current that flows in the faulted phase
conductors, and therefore through breaker B2:
Fault type
Faulted-phase current (A)
Ground return 3Ia0 (A)
Ratio to 3-phase
Three-phase (a)
796.7
0
1.000
Single line to ground (b)
519.6
519.6
0.652
Double line to ground (c)
716.4
385.5
0.899
Line to line (d)
690.0
0
0.866
$$\boxed{\text{smallest fault current: single line-to-ground, }
519.6\ \text{A}}$$
The reason is worth stating rather than merely quoting the number. In most
solidly grounded systems close to a generator, $Z_0$ is smaller than
$Z_1$ and the single-line-to-ground fault is the most severe of the four. Here the
opposite holds: the zero-sequence impedance of an overhead line is typically two
to three times its positive-sequence value (the return path is the earth and the
shield wires, not the other two phases), and with two line sections in the path
$Z_0 = j65\ \Omega$ against $Z_1 = j25\ \Omega$. The series sum
$Z_1+Z_2+Z_0 = j115\ \Omega$ is then so much larger than $Z_1$ alone that the
ground fault is the mildest case. Note also that the double-line-to-ground
ground current, 386 A, is lower still —
but that is the earth-return current, not the current the breaker's phase contacts
must interrupt.
Check: Figure 4 gives one set of
line impedances beside a two-section route, which is read here as the impedance
of each section — hence $j10+j10$ and $j30+j30$. Read instead as the
total for the whole route, the values would be $Z_1=j15$ and $Z_0=j35\ \Omega$,
giving 1327.9 A (three-phase), 919.3 A (single line-to-ground),
1202.5 A (double line-to-ground, phase) and 1150.0 A (line-to-line); the
ordering of the four faults, and therefore the answer to part (e), is unchanged.
The system is radial, so in either reading the current at B2 equals the
current at the fault.