22-Elec-B7 Power Systems Engineering · December 2015
Question 1 of 7: Ferranti Effect and the Long-Line Model of a 765 kV Circuit
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Notes on this paper
Paper format. National Exams, December 2015 — 07-Elec-B7 Power Systems Engineering. Open-book, 3 hours. Seven problems are printed; any five constitute a complete paper and all questions are of equal value (25 points each). All seven are solved in full below, because the set is a study resource rather than a timed sitting.
Reference texts. The syllabus for this code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation used throughout this paper (the cantilever transformer model, the ABCD two-port, the two-reaction salient-pole construction) is his. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. Grainger and W. Stevenson, Power System Analysis; and, for the machine chapters, S. J. Chapman, Electric Machinery Fundamentals, 5th ed. Canadian practice references where grounding and protection are discussed: CSA C22.1 Canadian Electrical Code, Part I and CSA C22.3 No. 1 for overhead systems.
Check: two points read off the printed figures. (i) Figure (1) of Problem 4 prints the line admittance as y = −j10 pu, i.e. a series reactance of j0.10 pu. The negative sign is the physically correct one for an inductive line and is used here. (ii) In Figure (3-a) of Problem 6, transformer T2 carries its delta on the generator side and T1 carries its delta on the motor side; both line-side windings are wye with a solidly earthed neutral. That reading governs the zero-sequence network built in Problem 6(a).
Problem 1: Ferranti Effect and the Long-Line Model of a 765 kV Circuit (25 points)
The Ferranti effect is the rise of the receiving-end voltage of a
long transmission line above its sending-end voltage when the line is
open-circuited or very lightly loaded. It is named for Sebastian Ziani de
Ferranti, who observed it on the 10 kV Deptford cables in 1890. Physically it is
the shunt capacitance of the line acting through the line’s own series
inductance: with no load current to speak of, the only current the line draws is
the capacitive charging current distributed along its length, and that current
leads the voltage by ninety degrees. A leading current flowing through a
series inductive reactance produces a voltage rise rather than a drop,
so each successive element of the line adds a little to the voltage, and the
receiving end sits highest.
The compact statement of the effect comes straight from the lossless
long-line equations. At no load the receiving-end current is zero, so
$V_S = A V_R$ with $A = \cosh(\gamma \ell)$, and for a lossless line this reduces
to $V_R / V_S = 1/\cos(\beta \ell)$. Because $\cos(\beta \ell) < 1$ for any
line shorter than a quarter wavelength, the receiving-end voltage always exceeds
the sending-end voltage, and the excess grows roughly as the square of the line
length. For this particular circuit $\beta \ell = 47.04^{\circ}$, so an open end
would sit at $1/\cos 47.04^{\circ} = 1.467$ times the sending voltage — a
47 per cent rise.
It matters operationally for three reasons. First, sustained overvoltage
stresses insulation, bushings and surge arresters, and drives transformers into
saturation, so it is a plant-damage mechanism, not merely a metering curiosity.
Second, it appears at exactly the worst moment: after a load rejection or a
remote-end breaker trip, a fully energised line is suddenly unloaded and the
receiving end can jump within a cycle. Third, it constrains commissioning and
restoration practice — energising a long EHV line from one end is a
routine step in a black start, and the Ferranti rise sets how much of the line
may be energised at once. The countermeasures are shunt reactors (fixed or
switched) at the line ends and at intermediate stations, which absorb the
charging vars before they can drive the voltage up; static var compensators or
STATCOMs where the response must be continuous; and operating rules that
require the reactors in service before the line is energised and only permit
them to be removed as load builds.
Parts (b) and (c) — long-line constants and a forward run
Given.
Quantity
Symbol
Value
Series impedance per km
z
0.02 + j0.54 Ω/km
Shunt admittance per km
y
j7.8 × 10−6 S/km
Line length
l
400 km
Nominal voltage
Vnom
765 kV line-to-line
Receiving-end voltage
VR
750 kV line-to-line
Receiving-end load
PR
100 MW at 0.955 pf lagging
Find. The characteristic impedance, propagation constant and its two components, then the sending-end voltage, current, power factor and the transmission efficiency using the exact (distributed-parameter) model.
Figure 1.1 — the line treated as a two-port. With the ABCD constants in hand, part (c) is a single matrix multiplication from the receiving end back to the sending end.
Approach. Form $Z_c=\sqrt{z/y}$ and $\gamma=\sqrt{zy}$ from the per-kilometre constants, build the exact ABCD matrix from $\gamma \ell$, then push the stated receiving-end phasors through it.
Part (b) — characteristic (surge) impedance.
The characteristic impedance is the square root of the ratio of the series
impedance to the shunt admittance, both taken per unit length:
$$Z_c=\sqrt{\frac{z}{y}}=\sqrt{\frac{0.02+j0.54}{j7.8\times10^{-6}}}
=\sqrt{\frac{0.54037\angle 87.879^{\circ}}{7.8\times10^{-6}\angle 90^{\circ}}}$$
The ratio inside the root is $69\,278\angle -2.121^{\circ}\ \Omega^2$, and taking
the square root halves the angle:
$$\boxed{Z_c=263.21\angle -1.061^{\circ}\ \Omega}$$
The angle is small and negative because the line is far more inductive than
resistive; a purely lossless line would give a real surge impedance.
Propagation constant, attenuation constant and phase
constant. The propagation constant is the geometric mean of the same
two quantities:
$$\gamma=\sqrt{zy}=\sqrt{(0.54037\angle 87.879^{\circ})(7.8\times10^{-6}\angle 90^{\circ})}
=2.0530\times10^{-3}\angle 88.939^{\circ}\ \text{km}^{-1}$$
Resolving into rectangular form separates the two constants, since
$\gamma=\alpha+j\beta$:
$$\begin{aligned}
\alpha &= 2.0530\times10^{-3}\cos 88.939^{\circ} = 3.800\times10^{-5}\ \text{Np/km}\\
\beta &= 2.0530\times10^{-3}\sin 88.939^{\circ} = 2.0527\times10^{-3}\ \text{rad/km}
\end{aligned}$$
$$\boxed{\alpha=3.800\times10^{-5}\ \text{Np/km},\ \ \beta=2.0527\times10^{-3}\ \text{rad/km}}$$
Over the whole 400 km the electrical length is
$\gamma \ell = 0.01520 + j0.82107$, that is 0.0152 nepers (only 0.132 dB of
attenuation) and 0.82107 radians, or 47.04 degrees, of phase shift. The
0.132 dB confirms that a 765 kV line is an almost lossless waveguide over this
distance; the 47 degrees is what makes it unmistakably a long line, well
past the point where a nominal-pi model is trustworthy.
Assemble the exact two-port constants. The
distributed-parameter solution of the line equations gives
$$A=D=\cosh(\gamma \ell),\quad B=Z_c\sinh(\gamma \ell),\quad
C=\frac{\sinh(\gamma \ell)}{Z_c}$$
Evaluating the hyperbolic functions of the complex argument
$0.01520+j0.82107$:
$$\begin{aligned}
A &= D = 0.68161\angle 0.935^{\circ}\\
B &= 192.68\angle 88.129^{\circ}\ \Omega\\
C &= 2.7812\times10^{-3}\angle 90.250^{\circ}\ \text{S}
\end{aligned}$$
Two free checks confirm the arithmetic before it is used. Reciprocity requires
$AD-BC=1$, which these values satisfy to seven figures. And the angle of $C$
must sit within a degree of $+90^{\circ}$ because $C$ is essentially the line
charging susceptance; at $90.25^{\circ}$ it does.
Part (c) — receiving-end phasors. Working per
phase with the receiving-end voltage as reference,
$$V_R=\frac{750\,000}{\sqrt3}=433.01\ \text{kV per phase}$$
and the load current follows from the three-phase real power:
$$I_R=\frac{P_R}{\sqrt3\,V_{R,LL}\cos\phi}
=\frac{100\times10^{6}}{\sqrt3\,(750\times10^{3})(0.955)}=80.61\ \text{A}$$
Lagging at 0.955 means the current sits at
$-\cos^{-1}(0.955)=-17.25^{\circ}$, so
$I_R=80.61\angle -17.25^{\circ}\ \text{A}$. Note how small this is: the line is
carrying 100 MW where its surge-impedance loading is
$V^2/Z_c=(765\ \text{kV})^2/263.21=2223\ \text{MW}$, so it is loaded to about
4.5 per cent of SIL.
Push the phasors back to the sending end. The two-port
relation is
$$\begin{bmatrix}V_S\\ I_S\end{bmatrix}
=\begin{bmatrix}A&B\\ C&D\end{bmatrix}
\begin{bmatrix}V_R\\ I_R\end{bmatrix}$$
Substituting the constants and the receiving-end phasors:
$$\begin{aligned}
V_S &= (0.68161\angle 0.935^{\circ})(433\,013\angle 0^{\circ})
+ (192.68\angle 88.129^{\circ})(80.61\angle -17.25^{\circ})\\
&= 300.83\angle 3.715^{\circ}\ \text{kV per phase}
\end{aligned}$$
$$\begin{aligned}
I_S &= (2.7812\times10^{-3}\angle 90.250^{\circ})(433\,013\angle 0^{\circ})
+ (0.68161\angle 0.935^{\circ})(80.61\angle -17.25^{\circ})\\
&= 1189.8\angle 87.713^{\circ}\ \text{A}
\end{aligned}$$
In line terms
$$\boxed{V_{S,LL}=\sqrt3\,(300.83)=521.05\ \text{kV},\qquad I_S=1189.8\ \text{A}}$$
Sending-end power factor and transmission efficiency.
The angle between the sending-end voltage and current is
$$\theta_S=3.715^{\circ}-87.713^{\circ}=-83.998^{\circ}
\ \Longrightarrow\ \cos\theta_S=0.1046\ \text{leading}$$
The three-phase sending-end power is
$$P_S=3V_SI_S\cos\theta_S=3(300\,827)(1189.8)(0.1046)=112.27\ \text{MW}$$
so the efficiency of transmission is
$$\eta=\frac{P_R}{P_S}\times 100=\frac{100.00}{112.27}\times 100$$
$$\boxed{\eta=89.07\ \text{per cent},\qquad \cos\theta_S=0.105\ \text{leading}}$$
The line loss is the difference, 12.27 MW.
Check: the sending-end voltage really is lower than the receiving-end voltage, and the sending-end power factor really is leading. At 521.05 kV against 750 kV this looks like a sign error, and it is not — it is part (a) made arithmetic. The line is loaded to 4.5 per cent of its 2223 MW surge-impedance loading, so the distributed charging current (about 1351 A at the receiving end, sixteen times the 80.6 A load current) dominates everything. The strictly no-load value from the same ABCD matrix is 750 × 0.68161 = 511.2 kV, and the loaded answer sits just above it, exactly as it should. In service a line in this condition would be carrying shunt reactors, which the question does not include.
Final Results.
Quantity
Value
Characteristic impedance Zc
263.21 −1.061° Ω
Propagation constant γ
2.0530 × 10−3 88.939° km−1
Attenuation constant α
3.800 × 10−5 Np/km
Phase constant β
2.0527 × 10−3 rad/km (47.04° over 400 km)
Sending-end voltage VS
521.05 kV line-to-line (300.83 kV/phase at +3.715°)