22-Elec-B7 Power Systems Engineering · December 2015
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, December 2015 — 07-Elec-B7 Power Systems Engineering. Open-book, 3 hours. Seven problems are printed; any five constitute a complete paper and all questions are of equal value (25 points each). All seven are solved in full below, because the set is a study resource rather than a timed sitting.
Reference texts. The syllabus for this code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation used throughout this paper (the cantilever transformer model, the ABCD two-port, the two-reaction salient-pole construction) is his. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. Grainger and W. Stevenson, Power System Analysis; and, for the machine chapters, S. J. Chapman, Electric Machinery Fundamentals, 5th ed. Canadian practice references where grounding and protection are discussed: CSA C22.1 Canadian Electrical Code, Part I and CSA C22.3 No. 1 for overhead systems.
Check: two points read off the printed figures. (i) Figure (1) of Problem 4 prints the line admittance as y = −j10 pu, i.e. a series reactance of j0.10 pu. The negative sign is the physically correct one for an inductive line and is used here. (ii) In Figure (3-a) of Problem 6, transformer T2 carries its delta on the generator side and T1 carries its delta on the motor side; both line-side windings are wye with a solidly earthed neutral. That reading governs the zero-sequence network built in Problem 6(a).
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Transformer losses divide into the core (no-load) losses and the copper (load) losses, and frequency touches them in quite different ways. It is essential to say at what flux density the comparison is being made, because that is where most of the confusion arises: at a fixed applied voltage the peak flux is inversely proportional to frequency, since $V \approx 4.44 f N \Phi_m$, so raising the frequency at constant voltage reduces the flux.
Hysteresis loss follows the Steinmetz relation $P_h = k_h f B_m^{n}$ with the exponent $n$ between about 1.6 and 2.0. At constant flux density it is directly proportional to frequency, because each cycle traverses the same hysteresis loop and there are more cycles per second. At constant applied voltage, however, $B_m \propto V/f$, so $P_h \propto f (V/f)^{n} = V^{n} f^{1-n}$, which falls as frequency rises. Eddy-current loss follows $P_e = k_e f^{2}B_m^{2}t^{2}$ and so rises with the square of frequency at constant flux density, but at constant voltage it becomes $P_e \propto f^{2}(V/f)^{2}=V^{2}$, that is, essentially independent of frequency. Together these give the practical rule that a transformer moved from 50 Hz to 60 Hz at its rated voltage runs with about 17 per cent less peak flux and correspondingly lower core loss, and further from saturation.
Copper loss $I^{2}R$ is nominally frequency-independent, but only nominally. The effective winding resistance rises with frequency through skin effect and proximity effect, and stray loss in the tank, clamps and core-frame — produced by leakage flux linking structural steel — rises roughly with the square of frequency. For a distribution transformer at 50/60 Hz these effects are small, of the order of a few per cent of the copper loss, but they become dominant for units serving rectifier or drive loads where harmonic currents at several hundred hertz are present; that is the entire motivation for the K-factor and factor-K derating standards. The other frequency-linked consequence is reactance: every reactance in the equivalent circuit is proportional to frequency, so a 50 Hz transformer used at 60 Hz has 20 per cent higher leakage reactance and therefore 20 per cent higher percentage impedance, giving worse regulation but proportionally lower through-fault current. The dangerous direction is the reverse one — running a 60 Hz unit on 50 Hz at rated voltage drives the flux up by 20 per cent and can push the core into saturation, with an exciting current several times normal.
Given.
| Quantity | Value at 50 Hz |
|---|---|
| Rating | 45 kVA, 230 V : 6.6 kV |
| Magnetising reactance, from the 230 V terminals | 46.00 Ω |
| Leakage reactance, 230 V winding | 28.00 mΩ |
| Leakage reactance, 6.6 kV winding | 25.00 Ω |
| New supply frequency | 60 Hz |
| Test voltages applied to the 230 V winding | 240 V (open circuit), 24 V (short circuit) |
Find. All three reactances at 60 Hz, then the primary current and secondary voltage on open circuit at 240 V, and the primary current on short circuit at 24 V.
Approach. Every reactance scales directly with frequency, so multiply each by 60/50; refer the high-voltage leakage reactance to the low- voltage side through the square of the turns ratio; then solve the open-circuit case as a simple series divider and the short-circuit case as a series-parallel combination.
Check: the magnetising reactance is treated as constant between the two tests. That is legitimate here because both tests reduce the core flux relative to the nameplate. The volts-per-hertz figure applied in part (c) is 240 / 60 = 4.00 against a rated 230 / 50 = 4.60, so the core runs at 87 per cent of rated flux and is further from saturation than it was designed to be. Had the machine been moved the other way — a 60 Hz unit put on 50 Hz at rated voltage — the flux would have risen 20 per cent, Xm would have collapsed with saturation, and no linear calculation of this kind would be defensible.
Final Results.
| Quantity | Value at 60 Hz |
|---|---|
| Magnetising reactance Xm (LV side) | 55.20 Ω |
| Leakage reactance, 230 V winding | 33.60 mΩ |
| Leakage reactance, 6.6 kV winding | 30.00 Ω (36.43 mΩ referred to LV) |
| Open-circuit primary current at 240 V | 4.345 A |
| Open-circuit secondary voltage | 6883 V (6.883 kV) |
| Short-circuit primary current at 24 V | 342.8 A |
| Corresponding secondary short-circuit current | 11.94 A |