22-Elec-B7 Power Systems Engineering · December 2015
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, December 2015 — 07-Elec-B7 Power Systems Engineering. Open-book, 3 hours. Seven problems are printed; any five constitute a complete paper and all questions are of equal value (25 points each). All seven are solved in full below, because the set is a study resource rather than a timed sitting.
Reference texts. The syllabus for this code follows M. E. El-Hawary, Electrical Power Systems: Design and Analysis (IEEE Press) — the notation used throughout this paper (the cantilever transformer model, the ABCD two-port, the two-reaction salient-pole construction) is his. Corroborating references: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. Grainger and W. Stevenson, Power System Analysis; and, for the machine chapters, S. J. Chapman, Electric Machinery Fundamentals, 5th ed. Canadian practice references where grounding and protection are discussed: CSA C22.1 Canadian Electrical Code, Part I and CSA C22.3 No. 1 for overhead systems.
Check: two points read off the printed figures. (i) Figure (1) of Problem 4 prints the line admittance as y = −j10 pu, i.e. a series reactance of j0.10 pu. The negative sign is the physically correct one for an inductive line and is used here. (ii) In Figure (3-a) of Problem 6, transformer T2 carries its delta on the generator side and T1 carries its delta on the motor side; both line-side windings are wye with a solidly earthed neutral. That reading governs the zero-sequence network built in Problem 6(a).
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
A short circuit collapses the impedance between a phase conductor and either another phase or earth, so the current is limited only by the source and network reactances and rises to many times the rated value — on the network in this question, more than seven times. The consequences fall into four families, and a competent answer treats them separately because the protection strategy for each is different.
Thermal and mechanical damage. Fault current heats conductors adiabatically, since there is no time for the heat to escape; the limit is expressed as an $I^{2}t$ withstand and is what sizes cable screens, busbars and current transformers. Simultaneously the electromagnetic force between parallel conductors scales with the square of the current, so a seven-per-unit fault imposes roughly fifty times the normal force on busbar supports and on transformer windings; winding deformation from through-faults is one of the commonest causes of subsequent transformer failure. At the fault point itself the arc energy damages insulation and, in switchgear, is the arc-flash hazard that governs personal protective equipment selection under CSA Z462.
Voltage depression. As parts (b) and (c) show quantitatively, a bolted fault holds the faulted bus at zero volts and drags every other bus down with it — here buses 1 and 2 fall to 0.42 and 0.47 pu, less than half of nominal, across the whole network rather than just near the fault. Industrial processes trip on undervoltage, motor contactors drop out, and variable-speed drives shut down; the economic loss from the ride-through failure of a large process plant routinely exceeds the cost of the damaged equipment. Induction motors also lose torque as the square of the voltage, so they decelerate and then draw a large re-acceleration current when the fault clears.
Loss of synchronism and system instability. A fault close to a generator reduces the electrical power it can export to nearly zero while the turbine keeps delivering mechanical power, so the rotor accelerates. If the fault is not cleared before the critical clearing angle — the subject of Problem 7 — the machine pulls out of step, and the resulting out-of-step condition must itself be detected and separated. Frequency and voltage excursions can then cascade through the interconnection.
Personnel safety and secondary effects. Earth-fault current returning through the station earth grid raises the ground potential and creates step and touch voltages, which is the design basis of IEEE Std 80 and of the grounding requirements in CSA C22.3. Induced voltages appear on parallel communication and pipeline circuits. The countermeasures are correspondingly layered: limiting the available fault current (neutral earthing reactors, as in Problem 6, and split bus operation), clearing it quickly with graded protection and adequately rated interrupting devices, and designing every component to survive the maximum through-fault it will ever see.
Given.
| Element | Reactance (pu) |
|---|---|
| Source at bus 1 (machine plus step-up) | j0.15 to the reference |
| Source at bus 2 (machine plus step-up) | j0.15 to the reference |
| Line 1–3 | j0.15 |
| Line 3–2 | j0.10 |
| Line 1–2 (diagonal) | j0.20 |
| Line 1–4 | j0.10 |
| Line 4–2 | j0.15 |
| Both source internal voltages | 1.0 pu, prefault, no load |
Find. The bolted three-phase fault current at bus 4, then the voltages held at buses 1 and 2 while that fault persists.
Approach. With both sources at $1.0\angle 0^{\circ}$ and no prefault load, every bus sits at 1.0 pu before the fault, so the fault current is simply $1/Z_{th}$ at bus 4. Reduce the passive network to that Thevenin reactance by series–parallel combination plus one delta–star transform, then back-substitute to recover the bus voltages.
Final Results.
| Quantity | Value |
|---|---|
| Thevenin reactance at bus 4 | j0.13561 pu |
| Fault current at bus 4 | 7.374 pu at −90° (737 MVA on a 100 MVA base) |
| Voltage at bus 1 during the fault | 0.4244 pu |
| Voltage at bus 2 during the fault | 0.4695 pu |
| Voltage at bus 3 during the fault | 0.4515 pu |
| Contribution from the bus-1 source | 3.837 pu |
| Contribution from the bus-2 source | 3.536 pu |