22-Elec-B7 Power Systems Engineering · Undated paper
Nivaar worked solution (AI-drafted; not reviewed by a licensed engineer)
Paper format. National Exams, May 2019 — 16-Elec-B7 Power Systems Engineering, 3 hours, open book, any non-communicating calculator permitted. The paper prints seven questions, headed “Problem 1” to “Problem 7”, each carrying printed sub-part splits that total 20 points; the rubric states that any five questions constitute a complete paper, that only the first five questions as they appear in your answer book will be marked, and that all questions are of equal value. All seven are solved in full here, because the set is a study resource rather than a three-hour sitting. page 1 reads “National Exams May 2019” and every page footer reads “16-Elec-B7/May 2019”.
Reference texts. M. E. El-Hawary, Electrical Power Systems: Design and Analysis, rev. ed., IEEE Press / Wiley — the reference text named in the Engineers Canada syllabus for this examination code, and the source of the “cantilever” transformer model used in Problem 3. Supporting texts: J. D. Glover, M. S. Sarma and T. J. Overbye, Power System Analysis and Design, 6th ed.; J. J. Grainger and W. D. Stevenson, Power System Analysis; P. M. Anderson, Analysis of Faulted Power Systems; P. Kundur, Power System Stability and Control. Canadian practice context (grounding philosophy, protection coordination) follows CSA C22.1 and IEEE Std 142 as applied by Canadian utilities and industrial plants.
Note on the printed values. Every number used below is the one the paper prints, including B = j70, Xeq = 3.0 Ω, a utility X0 of 0.1 and a grounding resistor of 8 Ω; the printed paper governs throughout.
Check — three engineering readings that a marker may take differently.
(1) Problem 5. The prose says “the voltage at both sources is 1 p.u.” above a Figure (3) that plainly draws four generators, G1 to G4. Every drawn source is taken at 1.0 pu, which is the only reading that closes the network.
(2) Problem 6. Figure (4-c) draws the 5 000 kVA generator alongside the resistance-grounded utility transformer, while the sentence introducing it mentions only the transformer. The generator is retained for part (e), consistent with the figure. It is ungrounded either way, so it changes only the positive- and negative-sequence networks; the zero-sequence answer is identical under both readings.
(3) Problem 2. “Neglecting armature reaction” cannot mean discarding xd and xq, which are the armature-reaction reactances — the question would then have no data. It is read here in its usual examination sense: neglect saturation and armature resistance, and use the ideal two-reaction model.
Question text not reproduced: the examination questions are © Engineers and Geoscientists BC. Open the official past paper (linked at the top of this page) to read the question, then follow the worked solution below.
Part (a) — what a bundle conductor line is. A bundle conductor line replaces each single phase conductor with two, three, four or more sub-conductors held a fixed distance apart — typically 400 to 500 mm — by spacer dampers every few tens of metres along the span. Electrically the bundle behaves as one conductor whose effective radius is far larger than that of any of its members, because the current shares among sub-conductors that are separated by many conductor diameters. The quantity that captures this is the bundle geometric mean radius, which for an N-conductor bundle on a circle of radius R is $\mathrm{GMR}_b = \left[N\,r'\,R^{N-1}\right]^{1/N}$, with $r' = r e^{-1/4}$ for inductance and $r$ itself for capacitance.
The consequences follow from that one geometric fact. Series inductance falls, because $L = 2\times10^{-7}\ln(\mathrm{GMD}/\mathrm{GMR}_b)$ and the denominator has grown; a four-conductor bundle typically cuts reactance by about 30 % against a single conductor of the same total aluminium. Shunt capacitance rises for the same reason, since $C = 2\pi\varepsilon_0/\ln(\mathrm{GMD}/\mathrm{CGMR})$. Taken together these move the surge impedance $Z_c = \sqrt{L/C}$ down and the surge impedance loading $\mathrm{SIL} = V^2/Z_c$ up, so a bundled line carries substantially more power at the same voltage and the same angular separation. That is the reason no line above about 300 kV is built unbundled.
The second motivation is surface gradient. Corona onset is governed by the electric field at the conductor surface, and spreading the charge over several sub-conductors reduces the peak gradient by roughly the same factor by which the effective radius grows. Bundling therefore suppresses corona loss, radio interference and audible noise — the constraints that actually set conductor size at extra-high voltage, well before thermal rating does. The costs are mechanical: heavier towers, larger wind and ice loading, spacer maintenance, and a greater short-circuit force between sub-conductors during a fault, which is what sets the spacer interval.
Given. A symmetric, reciprocal three-phase line with $A = D = 0.95\angle 0^\circ$ and $B = j70\ \Omega$. Nominal system voltage 1800 kV; the line delivers $S_R = 2000$ MVA at $V_R = 1750$ kV (line-to-line) at unity power factor.
Find. The shunt constant $C$, then the sending-end voltage and the sending-end current at that receiving-end load.
Approach. Recover $C$ from the reciprocity identity $AD - BC = 1$, then run the two-port forward once with the receiving-end phasors as the input.
| Quantity | Value |
|---|---|
| Shunt constant $C$ | $1.3929\times10^{-3}\angle 90.00^\circ$ S |
| Receiving-end phasors | $V_R = 1010.36\angle 0^\circ$ kV/phase, $I_R = 659.83\angle 0^\circ$ A |
| Sending-end voltage (per phase) | $960.96\angle 2.755^\circ$ kV |
| Sending-end voltage (line-to-line) | 1664.4 kV |
| Sending-end current | $1540.6\angle 65.99^\circ$ A |
| Sending-end power factor | 0.450 leading |
| Sending-end complex power | $2000.0 - j3965.5$ MVA |
| Surge impedance / SIL | $224.18\ \Omega$ / 14 453 MW at 1800 kV |